6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
6-1. Models:AOYG07LLCE and AOYG09LLCE
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15
-
-
-
0.872
0.910
10
-
-
0.961
0.886
0.925
7.5
-
0.979
0.965
0.890
0.929
5
0.992
0.983
0.969
0.893
0.933
0
1.000
0.991
0.976
0.901
0.940
Indoor unit is lower than
outdoor unit *2
-5
1.000
0.991
0.976
0.901
0.940
-7.5
-
0.991
0.976
0.901
0.940
-10
-
-
0.976
0.901
0.940
-15
-
-
-
0.901
0.940
HEATING
Pipe length (m)
5
7.5
10
15
20
Height difference H (m)
Indoor unit is higher than
outdoor unit *1
15
-
-
-
0.832
0.822
10
-
-
0.917
0.832
0.822
7.5
-
0.961
0.917
0.832
0.822
5
1.000
0.961
0.917
0.832
0.822
0
1.000
0.961
0.917
0.832
0.822
Indoor unit is lower than
outdoor unit *2
-5
0.995
0.956
0.912
0.828
0.818
-7.5
-
0.954
0.910
0.826
0.816
-10
-
-
0.908
0.824
0.814
-15
-
-
-
0.815
0.805
- 31 -
OUTDOOR UNIT
AOYG07-12LLCE
Содержание AOYG07LLCE
Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG07LLCE ASYG09LLCE ASYG12LLCE ...
Страница 10: ...3 Wiring diagrams 3 1 Models ASYG07LLCE ASYG09LLCE and ASYG12LLCE 6 WALL MOUNTED ASYG07 12LLCE ...
Страница 16: ...6 2 Sound level check point 0 8 m 1 m Microphone Microphone 12 WALL MOUNTED ASYG07 12LLCE ...
Страница 27: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG07LLCE AOYG09LLCE AOYG12LLCE ...
Страница 34: ...5 Wiring diagrams 5 1 Models AOYG07LLCE AOYG09LLCE and AOYG12LLCE 30 OUTDOOR UNIT AOYG07 12LLCE ...
Страница 44: ...12 Accessories Part name Exterior Q ty Part name Exterior Q ty Drain pipe 1 40 OUTDOOR UNIT AOYG07 12LLCE ...