02-01
2-1 ERROR DISPLAY
2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY
Please refer the flashing pattern as follows.
Indoor Unit : AS*G07/ 09/ 12/ 14KMTA
The OPERATION, TIMER and ECONOMY lamps operate as follows according to the error contents.
Error Contents
Continuous
1 times
1 times
Trouble
shooting
(Green)
(Orange)
(Green)
Serial communication error
1.2
Indoor Unit Display
Wired Remote
Controller
Display
11
Continuous
1 times
8 times
External Communication Error
3
18
Continuous
1 times
2 times
Wired Remote Controller
Communication Error
12
Continuous
2 times
2 times
Indoor Unit Capacity Error
4
22
Continuous
2 times
3 times
Combination Error
5
23
6
7
Continuous
3 times
2 times
8
32
9
[ ]
[ ]
[ ]
OPERATION
TIMER
ECONOMY
Indoor unit main PCB error
Continuous
3 times
5 times
10
35
Manual auto switch error
Continuous
4 times
1 times
12
41
Indoor Room Thermistor Error
Continuous
4 times
2 times
13
42
Indoor Heat Ex. Thermistor Error
Continuous
5 times
1 times
14
51
Indoor Unit Fan Motor Error
Continuous
5 times
15 times
15
5U
Continuous
6 times
2 times
16
62
Indoor Unit Error
11
2-11
Outdoor unit main PCB error
Continuous
6 times
4 times
17
64
PFC circuit error
Continuous
6 times
5 times
18
65
IPM Error
Continuous
7 times
1 times
19
71
Discharge Thermistor Error
Continuous
7 times
4 times
Outdoor Thermistor Error
21
74
Continuous
7 times
3 times
Heat Ex. Liquid Outlet
Thermistor Error
20
73
Continuous
8 times
4 times
Current Sensor Error
84
Continuous
9 times
4 times
Over Current Error
94
Continuous
9 times
5 times
Compressor Control Error
95
Continuous
9 times
7 times
Outdoor Unit Fan Motor Error
97
Содержание AOYG07KMTA
Страница 35: ...1801G4693 ...
Страница 39: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Страница 61: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Страница 97: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Страница 105: ...March 2018 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...