01-15
17. COMPRESSOR PREHEATING
18. 10°C HEAT OPERATION
10°C HEAT operation performs as below when pressing 10°C HEAT button or Weekly timer setting on the remote
controller.
Mode Heating
Setting temperature 10°C
Fan mode Auto
LED display Economy
Defrost operation Operate as normal
( Table 18 : 10°C HEAT operation )
19. ECONOMY OPERATION
The ECONOMY operation functions by pressing ECONOMY button on the remote controller.
At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation
for cooling and heating.
The ECONOMY operation is almost the same operation as below settings.
Mode Cooling/ Dry Heating
Target temperature Setting temp.+1°C Setting temp.-1°C
( Table 19 )
When the outdoor heat exchanger temperature is lower than -4°C and the heating operation has
been stopped for 30 minutes, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor temperature rises to -2°C or greater,
preheating is ended.