The maximum value of the indoor fan speed is set as shown in Fig.6 based on the detected
temperature by the indoor heat-exchanger sensor on heating mode.
( Fig.6 : Cool air prevension control )
01-06
5. HEATING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Fig. 5
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow
of [Heat] operation modes Quiet, Lo, Me, High, as shown in Table 5.
6. COOL AIR PREVENTION CONTROL (Heating mode)
( Fig.5 : Airflow change - over ( Heating : Auto ) )
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C > TR-Ts > -2.5°C
=
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C
=
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
Lo mode
Me mode
Me+ mode
42°C
30°C
34°C
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
Hi
Me+
Lo
Cool air
prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.7.
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.7.
It depends on the Function setting "Indoor unit fan control for energy saving."
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
8. INDOOR UNIT FAN (CONTROL FOR ENERGY SAVING (Cooling mode)
( Fig.7 : Indoor fan control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 7)
S-Lo
OFF
10
30
60
180
60
180
60
10
30
(sec)
( Table 6 : Indoor fan speed )
X zone
J zone
AS*G07/09/12KMTA
550rpm
550rpm
550rpm
AS*G14KMTA
580rpm
580rpm
580rpm
Dry
Cooling
42°C
30°C
34°C
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
Powerful
Hi
Lo
Cool air
prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
<Normal operation>
<Powerful operation>
Содержание AOYG07KMTA
Страница 35: ...1801G4693 ...
Страница 39: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Страница 61: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Страница 97: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Страница 105: ...March 2018 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...