8-2. External output
Use an external output cable with appropriate external dimension, depending on the number of
cables to be installed.
¢
External input and output PCB
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V±2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to
"Combination of external input and output"
on page 23.
•
When indicator or other components are connected directly:
Example:
Function setting 60 is set to "00".
1
2
Connector
(CN310)
LED 1
(Operation status)
PCB
Resistor
Connected unit
+
-
1
2
Connector
(CN311)
LED 2
(Error status)
Resistor
+
-
1
2
Connector
(CN312)
LED 3
(Indoor unit fan
operation status)
Resistor
+
-
•
When connecting with a device equipped with a power supply:
Example:
Function setting 60 is set to "00".
1
2
Connected device 1
Connector
(CN310)
PCB
Connected unit
Relay
(Operation status)
-
+
1
2
Connected device 2
Connector
(CN311)
(Error status)
-
+
1
2
Connected device 3
Connector
(CN312)
(Indoor unit fan
operation status)
-
+
DESIGN & TECHNICAL MANUAL
- 22 -
WALL MOUNTED
ASYG07-14KGTA
Содержание AOYG07KGCA
Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA ...
Страница 10: ...3 Wiring diagrams 3 1 Models ASYG07KGTA ASYG09KGTA ASYG12KGTA and ASYG14KGTA 6 WALL MOUNTED ASYG07 14KGTA ...
Страница 47: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA ...
Страница 54: ...5 Wiring diagrams 5 1 Models AOYG07KGCA AOYG09KGCA AOYG12KGCA and AOYG14KGCA 50 OUTDOOR UNIT AOYG07 14KGCA ...