Control output function
•
Operation/Stop status
Function
setting /
Rotary SW on
External input and
output PCB
External output
Output
signal
Command
60-00 / 1
External input and output
PCB
CN310
Off → On
Operation
On → Off
Stop
The output is low when the unit is stopped.
Operation
Stop
On
Off
CN310
Indoor unit
•
Error status
Function
setting /
Rotary SW on
External input and
output PCB
External output
Output
signal
Command
60-00 / 1
External input and output
PCB
CN311
Off → On
Error
On → Off
Normal
The output is ON when an error is generated for the indoor unit.
Error
Normal
On
Off
CN310―312
Indoor unit
•
Indoor unit fan operation status
Function
setting /
Rotary SW on
External
input and output PCB
External output
Output
signal
Command
60-00 / 1
External input and output
PCB
CN312
Off → On
Fan run
On → Off
Fan stop
Output signal
Condition
On
The indoor unit fan is operating.
Low → High
Off
The fan is stopped or during cold air prevention.
High → Low
During thermostat off when in dry mode operation.
Fan run
Fan stop
On
Off
CN311―312
Indoor unit
- 29 -
WALL MOUNTED
ASYG07-14KGTA
Содержание AOYG07KGCA
Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA ...
Страница 10: ...3 Wiring diagrams 3 1 Models ASYG07KGTA ASYG09KGTA ASYG12KGTA and ASYG14KGTA 6 WALL MOUNTED ASYG07 14KGTA ...
Страница 47: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA ...
Страница 54: ...5 Wiring diagrams 5 1 Models AOYG07KGCA AOYG09KGCA AOYG12KGCA and AOYG14KGCA 50 OUTDOOR UNIT AOYG07 14KGCA ...