1-3. Error code table (Indoor unit and wired remote controller)
The operation, timer, and economy indicators operate according to the error contents.
For confirmation of the error contents, refer the flashing pattern as follows.
Error contents
Indoor unit display
Wired
remote
controller
display
Operation [ ]
(Green)
Timer [ ]
(Orange)
Economy [ ]
(Green)
E: 11. Serial communication error (Serial
reverse transfer error) (Outdoor unit)
1 times
1 times
Continuous
11
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
1 times
1 times
Continuous
11
E: 12. Wired remote controller
communication error (Indoor unit)
1 times
2 times
Continuous
12
E: 18. External communication error (Indoor
unit)
1 times
8 times
Continuous
18
E: 18. External communication error
between indoor unit and WLAN adapter
1 times
8 times
Continuous
18
1 times
8 times
Continuous
18
E: 18. Wireless LAN adapter non-energized
1 times
8 times
Continuous
18
E: 32. Indoor unit main PCB error (Indoor
unit)
3 times
2 times
Continuous
32
E: 35. MANUAL AUTO button error (Indoor
unit)
3 times
5 times
Continuous
35
E: 41. Room temperature sensor error
(Indoor unit)
4 times
1 times
Continuous
41
E: 42. Indoor unit heat exchanger sensor
error (Indoor unit)
4 times
2 times
Continuous
42
E: 51. Indoor unit fan motor error (Indoor
unit)
5 times
1 times
Continuous
51
E: 58. Intake grille error (Indoor unit)
5 times
8 times
Continuous
58
E: 62. Outdoor unit main PCB error
(Outdoor unit)
6 times
2 times
Continuous
62
E: 63. Inverter error (Outdoor unit)
6 times
3 times
Continuous
63
E: 64. PFC circuit error (Outdoor unit)
6 times
4 times
Continuous
64
E: 65. IPM error (Outdoor unit)
6 times
5 times
Continuous
65
E: 71. Discharge thermistor error (Outdoor
unit)
7 times
1 times
Continuous
71
E: 72. Compressor thermistor error
(Outdoor unit)
7 times
2 times
Continuous
72
E: 73. Outdoor unit heat exchanger
thermistor error (Outdoor unit)
7 times
3 times
Continuous
73
E: 74. Outdoor temperature thermistor error
(Outdoor unit)
7 times
4 times
Continuous
74
E: 84. Current sensor error (Outdoor unit)
8 times
4 times
Continuous
84
E: 94. Trip detection (Outdoor unit)
9 times
4 times
Continuous
94
E: 95. Compressor motor control error
(Outdoor unit)
9 times
5 times
Continuous
95
E: 97. Outdoor unit fan motor error
(Outdoor unit)
9 times
7 times
Continuous
97
E: 99. 4-way valve error (Outdoor unit)
9 times
9 times
Continuous
99
E: A1. Discharge temperature error
(Outdoor unit)
10 times
1 times
Continuous
A1
E: A3. Compressor temperature error
(Outdoor unit)
10 times
3 times
Continuous
A3
1-3. Error code table (Indoor unit and wired remote controller)
- (03-2) -
1. Error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AOUG09LZAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS024EF_03 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 10 12 SR_CH02_AS024EF_05 ...
Страница 33: ...3 TROUBLESHOOTING 2022 10 12 SR_CH03_AS024EF_07 ...
Страница 36: ......
Страница 117: ...4 CONTROL AND FUNCTIONS 2022 10 12 SR_CH04_AS024EF_03 ...
Страница 151: ...5 FILED WORKING 2022 10 12 SR_CH05_AS024EF_04 ...