1-3. Dry operation
The compressor rotation frequency shall change according to the temperature, set temperature, and
room temperature variation which the room temperature sensor of the indoor unit has detected as
shown in the table below.
Zone is defined by set temperature and room temperature.
•
Compressor frequency range
Unit: rps
Model name
Outdoor temperature zone
Operating frequency
ASUG09LZAS
ASUG12LZAS
X zone
24
J zone
18
Y zone
0
ASUG15LZAS
X zone
22
J zone
16
Y zone
0
•
Compressor control based on room temperature
Ts+1°F
(Ts+0.5°C)
Ts-3°F
(Ts-1.5
°C)
Ts+3°F
(Ts+1.5
°C)
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
Ts-1°F
(Ts-0.5°C)
1-4. Compressor frequency at normal start-up
¢
Models: AOUG09LZAS1, AOUG12LZAS1, and AOUG15LZAS1
Compressor frequency soon after starting is controlled as below.
Rotation number I
Rotation number II
Rotation number III
Rotation number IV
Rotation number V
Rotation number VI
Time 1
Time 2
Time 3
Time 4
Time 5
Time 6
Frequency
(rps)
I
II
III
IV
V
VI
35
52
64
71
89
97
Time (sec)
1
2
3
4
5
6
60
140
170
200
350
410
1-3. Dry operation
- (04-4) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AOUG09LZAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 10 12 SR_CH01_AS024EF_03 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 10 12 SR_CH02_AS024EF_05 ...
Страница 33: ...3 TROUBLESHOOTING 2022 10 12 SR_CH03_AS024EF_07 ...
Страница 36: ......
Страница 117: ...4 CONTROL AND FUNCTIONS 2022 10 12 SR_CH04_AS024EF_03 ...
Страница 151: ...5 FILED WORKING 2022 10 12 SR_CH05_AS024EF_04 ...