En-5

Base

2 in 
(50 mm) 
or over

Do not install directly on the ground, this may result in equipment 
failure.
Make sure the height of the base is 2 in (50 mm) from the 
ground. Otherwise, there is a risk that the drainage water will 
freeze between the device and the surface, disabling drainage.

CAUTION

If the unit is installed in a region that is exposed 
to high winds, freezing conditions, freezing rain, 
snow fall or heavy snow accumulation, take 
appropriate measures to protect it from those el-
ements. To ensure stable operation, the outdoor 
unit must be installed on a raised stand or rack, 
at or above the anticipated snow depth for the 
region. The installation of snow hoods and drift 
prevention fencing is recommended when blow-
ing and drifting snow is common to the region.

4. SYSTEM CONFIGURATION

4. 1.  System con

fi

 guration

CAUTION

Always keep to the limit on the total amount of refrigerant. Exceeding the limit on the 
total amount of refrigerant when charging will lead to malfunction.

• Between outdoor unit and the farthest indoor unit

a + f 

 393 ft (120 m), a + p 

 393 ft (120 m)

• Between the 

fi

 rst separation tube and the farthest indoor unit

 131 ft (40 m), p 

 131 ft (40 m)

•  Between the nearest indoor unit and the outdoor unit

a + b + h 

 16 ft (5 m), a+c+q 

 16 ft (5 m)

• Between outdoor unit and the 

fi

 rst separation tube

 9 ft (3 m)

•  Difference in height between outdoor units and indoor  units (H1)

164 ft (50 m) or less: Outdoor unit is higher than indoor unit
131 ft (40 m) or less: Outdoor unit is lower than indoor unit

•  Difference in height between indoor units and indoor units

H2 

 49 ft (15 m), H3 

 49 ft (15 m)

• Maximum total equivalent pipe length

a + f + h + j + l + n + p + q + s + u 

 590 ft (180 m)

• Total refrigerant amount 

 34 lbs (15.7 kg)

Fig. A 

Outdoor 

unit 

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

H1

H2

H3

f

h

p

q

j

s

u

l

n

b

c

a

4. 2.  Pipe selection

CAUTION

This unit is designed speci

fi

 cally for use with the R410A refrigerant.

Pipes for R407C or R22 may not be used with this unit.

Do not use existing pipes.

Improper pipe selection will degrade performance.

First separation 

tube (optional)

Separation tube 

(optional)

Pipe size 

(table B)

Pipe size 

(table C)

Pipe size 

(table D)

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

3. 3. 3.  Outdoor units installation in multi row

 

 Unit: in (mm)

*  The following settings are not recommended in case of cooling by a low outside tempera-

ture.

(1)  Single parallel unit arrangement

6 (150)

24 (600)

40 (1000)

79 (2000) or more

(2)  Multiple parallel unit arrangement

20 (500)

24 (600)

60 (1500)

119 (3000) or more

3. 4.  Transporting the unit

WARNING

Do not touch the 

fi

 ns. Otherwise, personal injury could result.

CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or 

fi

 ngers may be pinched.

•  Carry slowly in the manner as shown on “Fig. B” holding the handles “Fig. A” in right and 

left sides. (Be careful not to touch with hands or objects.)

•  Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on the 

sides of the unit may be deformed.

Front view

Rear view

Fig. B

Handle

Handle

Suction grille

Fig. A

3. 5.  Installing the unit

• Please install the outdoor unit without slant. (within 3 degrees )
•  Install 4 anchor bolts at the locations indicated with arrows in the 

fi

 gure.

•  To reduce vibration, do not install the unit directly on the ground. Install it on a secure 

base (such as concrete blocks).

•  The foundation shall support the legs of the unit and have a width of 1 in (50 mm) or more.
•  Depending on the installation conditions, the outdoor unit may spread its vibration during 

operation, which may cause noise and vibration. Therefore, attach damping materials 
(such as damping pads) to the outdoor unit during installation.

• Install the foundation, making sure that there is enough space for installing the connec-

tion pipes.

•  Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially avail-

able M10 bolts, nuts, and washers.)

• The bolts should protrude 13/16 in (20 mm). (Refer to the 

fi

 gure.)

•  If overturning prevention is required, purchase the necessary commercially available 

items.

6-9/16 

(166)

AIR

25-9/16 

(650)

6-1/16 

(154)

1-15/16

(50)

1-15/16

(50)

5/8 (16)

13/16 (20)

16-1/8 (410)

Unit: in (mm)

Bolt

Nut

Base

9380545095_IM.indb   5

9380545095_IM.indb   5

11/17/2015   4:14:25 PM

11/17/2015   4:14:25 PM

Содержание AOU36RLAVM

Страница 1: ...tage Parts for the Fujitsu LonWorks cables are the following Cable Type Pairs Details Catalog Number Level 4 NEMA 22AWG 1 250ft LonWorks Shielded cable K00250LW 1 500ft LonWorks Shielded cable K00500LW This addendum information shall supersede any LonWorks cable requirements listed in any of the Airstage Design Technical Manuals or Installation Manuals Design Technical Manual for Airstage V II 208...

Страница 2: ...STALACIÓN OUTDOOR UNIT UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel agréé uniquement Solo para personal de servicio autorizado AOU36RLAVM AOU48RLAVM AOU60RLAVM 9380545095_IM indb cover1 9380545095_IM indb cover1 11 17 2015 4 14 24 PM 11 17 2015 4 14 24 PM ...

Страница 3: ...your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be neces sary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweat...

Страница 4: ...g Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury If there is a possibility of touching the fan during maintenance make sure to turn OFF the power before implementing the maintenance Even if operations are suspended the fan of outdoor unit sometim...

Страница 5: ...otal cooling capacity of indoor unit kw UTP AX054A ALL 2 4 2 Header Header uses the following parts A header is used for connecting the indoor units Header Total cooling capacity of indoor unit kw 3 6 Branches 3 8 Branches UTR H0906L UTR H0908L ALL 2 4 3 External connect kit Model Usage UTY XWZXZ6 For External input CN131 CN132 CN133 CN134 For External output Error status CN136 Operation status CN...

Страница 6: ...ure sufficient space or consult your distributing agent as it may affect the performance due to short circuit and other problems Consider the transportation route installation space maintenance space and access and install the unit in a location with sufficient space for the refrigerant piping Observe the installation space specifications that are shown in the figures Keep the same space at rear a...

Страница 7: ...rformance First separation tube optional Separation tube optional Pipe size table B Pipe size table C Pipe size table D Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit 3 3 3 Outdoor units installation in multi row Unit in mm The following settings are not recommended in case of cooling by a low outside tempera ture 1 Single parallel unit arrangement 6 150 24 600 40 1000 79 ...

Страница 8: ...tion Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters t...

Страница 9: ...ut CAUTION Hold the torque wrench at its grip keeping it in a right angle with the pipe in order to tighten the flare nut correctly Outer panel may be distorted if fastened only with a wrench Be sure to fix the elementary part with a holding wrench spanner and fasten with a torque wrench refer to below dia gram Do not apply force to the blank cap of the valve or hang a wrench etc on the cap If bla...

Страница 10: ...portion of the connector cable with the cord clamp A damaged insulation can cause a short circuit Never install a power factor improvement condenser Instead of improving the power fac tor the condenser may overheat CAUTION Risk of Electric Shock Before servicing the unit turn the power supply switch OFF Then do not touch electric parts for 20 minutes due to the risk of electric shock Always use a ...

Страница 11: ...er MAX CKT BKR GOOD Transmission cable Remote controller cable 208 230 V 60 Hz Breaker 1 208 230 V 60 Hz Outdoor unit power supply cable Indoor unit power supply cable Breaker 2 Breaker 1 Breaker 2 6 4 Transmission line CAUTION Caution when wiring cable When stripping off the coating of lead wire always use the exclusive tool such as a wire stripper If there is no exclusive tool available necessar...

Страница 12: ...mote control Remote control Remote control Power supply Power supply Power supply Indoor unit Power supply 208 230V 60Hz Remote controller 1 1 1 Remote controller Remote controller Power supply 208 230V 60Hz Power supply 208 230V 60Hz Indoor unit Indoor unit Breaker 1 Breaker 1 Breaker 1 Breaker 1 Breaker 2 Breaker 2 Breaker 2 Breaker 2 1 The number of power supply terminals is different depending...

Страница 13: ...e Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circu...

Страница 14: ...t guarantee the regulations of each country For this reason sufficient checking is necessary regarding use Especially since the fact that the equipment may not be emergency stopped in the case of breaking of the wiring to the external input terminals and communication line communication error due to noise VRF external input circuit trouble etc must be considered the provision of double measures th...

Страница 15: ...ow many outdoor units are connected to 1 refrigerant system Configure the setting DIP switch SET 5 of the terminal resistor of the outdoor units as shown below from conditions 1 to 3 SET 5 Terminal resistor Remarks 4 OFF Disable ON Enable Factory setting Figure Terminal resistor setting NS2 Network segment 2 NS3 Network segment 3 NS4 Network segment 4 NS1 Network segment 1 Set terminal resistor at...

Страница 16: ...n Technical Manual 36 Outdoor tempera ture zone bound ary temperature A 1 4 0 F 20 C 3 6 0 0 0 4 F 18 C 0 1 3 2 F 16 C 0 2 6 8 F 14 C 0 3 10 4 F 12 C 0 4 14 0 F 10 C 0 5 17 6 F 8 C 0 6 21 2 F 6 C 0 7 24 8 F 4 C 0 8 For more details on settings for this item see the Design Technical Manual 37 Outdoor tempera ture zone bound ary temperature B 1 42 8 F 6 C 3 7 0 0 14 0 F 10 C 0 1 17 6 F 8 C 0 2 21 2 ...

Страница 17: ...segment LED display LED 105 LED 104 Flashing First 2 digits Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Contin...

Страница 18: ...2 3 4 Indoor unit wiring example Connect the indoor and outdoor units of the same refrigerant system as shown below Refrigerant system1 Refrigerant system2 Refrigerant system3 Master unit Master unit Master unit Signal amplifier Signal amplifier NOTE The automatic address function can be used for a maximum of 9 indoor units installed to the same refrigerant system When network is connected to othe...

Страница 19: ...microns 100 7 kPa even after depressurizing for at least 2 hours repeat the vacuum breakdown vacuum process perform triple evacu ation procedure as necessary to bring the vacuum down to 500 microns 100 7 kPa or lower After vacuum process maintain the vacuum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge Evacuation procedure 1 Remove the caps of the gas pipe ...

Страница 20: ...charged amount lbs kg Diameter of liquid pipe in mm a Additional amount for pipe length lbs ft kg m AOU36RLAVM 10 58 4 80 AOU48RLAVM 11 68 5 30 Ø 1 4 6 35 0 014 0 021 AOU60RLAVM 11 68 5 30 Ø 3 8 9 52 0 039 0 058 1 Calculation of additional amount for pipe length A Total length of ø 3 8 in ø 9 52 mm liquid pipe a 0 039 0 058 lbf ft kg m Total length of ø 1 4 in ø 6 35 mm liquid pipe a 0 014 0 021 l...

Страница 21: ...NTER button for more than 3 seconds Turn on the power of indoor unit and outdoor unit Press the ENTER button for more than 3 seconds This will be displayed when the Indoor unit connection check starts MODE EXIT SELECT ENTER ENTER ENTER 1 2 1 The number of connected indoor units 2 Volume ratio of the indoor units connection Ex When 8 units are connected Ex When the ratio is 120 Please refer to the ...

Страница 22: ...cient length of time before restarting the operation Perform test operation for each refrigerant system You can set cooling test operation or heating test operation with the push button on the outdoor unit PC board Test operation setting method Use the MODE EXIT SELECT and ENTER buttons on the indoor unit PC board to configure settings according to the procedures below Settings for starting test r...

Страница 23: ...rush current limiting resister temp rise error protective operation E 6 9 1 Outdoor unit transmission PCB parallel communi cation error Outdoor unit sen sor error E 7 1 1 Outdoor unit discharge temp thermistor 1 error E 7 2 1 Outdoor unit compressor temp thermistor 1 error E 7 3 3 Outdoor unit heat ex liquid temp thermistor error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit sucti...

Отзывы: