6. 6. 2.  External input terminal

Setting to low noise mode, cooling priority/heating priority selection, outdoor unit operation 
peak control setting, emergency/batch stop and electricity meter pulse are possible from 
the outside.

When connecting cable to Input 2

Cable (for external 
input and output)

Cable tie (tightened with 
transmission cable)

Cable (for external input and output)
*  If the outdoor unit is not installed in the wall, cover 

the exposed part of cable with a 1 mm thick or more 
insulation 

tubing.

About 2

1-5/8 in (550 mm)

Wiring method and speci

fi

 cations

*  A twisted pair cable (22 AWG (0.33 mm²)) should be used. Maximum length of cable is 

492 ft (150 m).

*  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed

*  For each input, pin No. 1 is of positive polarity and pin No. 2 is of ground level.

connected unit connected unit connected unit

connected unit connected unit

Input1

CN131 

(Yellow)

Input2

CN132 

(Green)

Input3

CN133 

(White)

Input4

CN134 

(Red)

Input5

CN135 

(Orange)

P.C.B

Operation behavior

Each input terminal works as follows.

Connector

Input signal

Status

Input1
CN131 (Yellow)

OFF

Normal operation

ON

Low noise mode operation

Input2
CN132 (Green) *1

OFF

Cooling priority

ON

Heating priority

Input3
CN133 (White)

OFF

Normal operation

ON

Outdoor unit operation peak control

Input4
CN134 (Red)

OFF

Normal operation

ON

Batch stop or Emergency stop operation *2, *3

Input5
CN135 (Orange) *4

No pulse

No information from electricity meter

Pulse

Power usage information from electricity meter

The operations of each input terminal and the selection of function are set with the push 
button on the PC board of outdoor unit. About the setting, please refer to “7. 4. Push button 
setting”.

NOTE:

*1:  The “external input priority mode” must be set by pressing push button on PC board 

of outdoor unit. (Refer to “7. FIELD SETTING”.)

*2:  Batch stop or Emergency stop pattern can be selected by outdoor unit PC board 

push button. (Refer to “7. FIELD SETTING”.)

*3:  The emergency stop function mounted in the J-II does not guarantee the regulations of 

each country. For this reason, suf

fi

 cient checking is necessary regarding use. 

Especially, since the fact that the equipment may not be emergency-stopped in the 
case of breaking of the wiring to the external input terminals and communication line, 
communication error due to noise, VRF external input circuit trouble, etc. must be 
considered, the provision of double measures that add direct interruption of the power 
supply by switch, etc. is recommended as a precaution.

*4:  Pulse input to CN135 must be width 50 ms or more, and must be interval 50 ms or more.

6. 6. 3.  External output terminal

You can detect the operation condition of outdoor unit and the abnormal situation of both 
indoor and outdoor unit.
Wiring method and speci

fi

 cations

Error status

This output indicates the outdoor unit and connected indoor unit's “Normal” or “Error” 
status.

Operation status

This output indicates the outdoor unit's “Operation” status.

Connector

Output voltage

Status

Output1
CN136 (Black)

0V

Normal

DC 12-24 V  *5

Error

Output2
CN137 (Blue)

0V

Stop

DC 12-24 V  *5

Operation

+

+

-

P.C.B

*7

*5

*6

1

2

CN136 
(Black) 
or CN137 
(Blue)

DC power supply 
(External) 12 - 24V

Connected load 
(Operation Indicator 
or Error Indicator)

connected unit

*5:  Provide a DC 12 to 24 V power supply. 

Select a power supply capacity with an ample surplus for the connected load.

*6:  The allowable current is 30 mA or less. 

Provide a load resistance such that the current becomes 30 mA or less.

*7:  Polarity is [+] for pin 1 and [-] for pin 2. Connect correctly.

Do not impress a voltage exceeding 24 V across pins 1-2.

*  A twisted pair cable (22 AWG (0.33 mm²)) should be used. Maximum length of cable is 

492 ft (150 m).

*  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

6. 6. 4.  Base heater terminal

This is the output signal for base heater. Output signal ON, when the outdoor temperature 
goes down below 2°C, and signal OFF at the outdoor temperature 4°C.

1

2

3

4

  

Voltage:  power supply 

input voltage

cable

(18AWG (0.82mm²))

P.C.B.

Base heater *9

CN115 

(Black)

*8

*  8: Connect to pin 1 and pin 3. No connection pin 2 and pin 4.
* 9: The allowable current is 1 A or less.

9380545095_IM.indb   12

9380545095_IM.indb   12

11/17/2015   4:14:27 PM

11/17/2015   4:14:27 PM

Содержание AOU36RLAVM

Страница 1: ...tage Parts for the Fujitsu LonWorks cables are the following Cable Type Pairs Details Catalog Number Level 4 NEMA 22AWG 1 250ft LonWorks Shielded cable K00250LW 1 500ft LonWorks Shielded cable K00500LW This addendum information shall supersede any LonWorks cable requirements listed in any of the Airstage Design Technical Manuals or Installation Manuals Design Technical Manual for Airstage V II 208...

Страница 2: ...STALACIÓN OUTDOOR UNIT UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel agréé uniquement Solo para personal de servicio autorizado AOU36RLAVM AOU48RLAVM AOU60RLAVM 9380545095_IM indb cover1 9380545095_IM indb cover1 11 17 2015 4 14 24 PM 11 17 2015 4 14 24 PM ...

Страница 3: ...your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be neces sary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweat...

Страница 4: ...g Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury If there is a possibility of touching the fan during maintenance make sure to turn OFF the power before implementing the maintenance Even if operations are suspended the fan of outdoor unit sometim...

Страница 5: ...otal cooling capacity of indoor unit kw UTP AX054A ALL 2 4 2 Header Header uses the following parts A header is used for connecting the indoor units Header Total cooling capacity of indoor unit kw 3 6 Branches 3 8 Branches UTR H0906L UTR H0908L ALL 2 4 3 External connect kit Model Usage UTY XWZXZ6 For External input CN131 CN132 CN133 CN134 For External output Error status CN136 Operation status CN...

Страница 6: ...ure sufficient space or consult your distributing agent as it may affect the performance due to short circuit and other problems Consider the transportation route installation space maintenance space and access and install the unit in a location with sufficient space for the refrigerant piping Observe the installation space specifications that are shown in the figures Keep the same space at rear a...

Страница 7: ...rformance First separation tube optional Separation tube optional Pipe size table B Pipe size table C Pipe size table D Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit 3 3 3 Outdoor units installation in multi row Unit in mm The following settings are not recommended in case of cooling by a low outside tempera ture 1 Single parallel unit arrangement 6 150 24 600 40 1000 79 ...

Страница 8: ...tion Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters t...

Страница 9: ...ut CAUTION Hold the torque wrench at its grip keeping it in a right angle with the pipe in order to tighten the flare nut correctly Outer panel may be distorted if fastened only with a wrench Be sure to fix the elementary part with a holding wrench spanner and fasten with a torque wrench refer to below dia gram Do not apply force to the blank cap of the valve or hang a wrench etc on the cap If bla...

Страница 10: ...portion of the connector cable with the cord clamp A damaged insulation can cause a short circuit Never install a power factor improvement condenser Instead of improving the power fac tor the condenser may overheat CAUTION Risk of Electric Shock Before servicing the unit turn the power supply switch OFF Then do not touch electric parts for 20 minutes due to the risk of electric shock Always use a ...

Страница 11: ...er MAX CKT BKR GOOD Transmission cable Remote controller cable 208 230 V 60 Hz Breaker 1 208 230 V 60 Hz Outdoor unit power supply cable Indoor unit power supply cable Breaker 2 Breaker 1 Breaker 2 6 4 Transmission line CAUTION Caution when wiring cable When stripping off the coating of lead wire always use the exclusive tool such as a wire stripper If there is no exclusive tool available necessar...

Страница 12: ...mote control Remote control Remote control Power supply Power supply Power supply Indoor unit Power supply 208 230V 60Hz Remote controller 1 1 1 Remote controller Remote controller Power supply 208 230V 60Hz Power supply 208 230V 60Hz Indoor unit Indoor unit Breaker 1 Breaker 1 Breaker 1 Breaker 1 Breaker 2 Breaker 2 Breaker 2 Breaker 2 1 The number of power supply terminals is different depending...

Страница 13: ...e Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circu...

Страница 14: ...t guarantee the regulations of each country For this reason sufficient checking is necessary regarding use Especially since the fact that the equipment may not be emergency stopped in the case of breaking of the wiring to the external input terminals and communication line communication error due to noise VRF external input circuit trouble etc must be considered the provision of double measures th...

Страница 15: ...ow many outdoor units are connected to 1 refrigerant system Configure the setting DIP switch SET 5 of the terminal resistor of the outdoor units as shown below from conditions 1 to 3 SET 5 Terminal resistor Remarks 4 OFF Disable ON Enable Factory setting Figure Terminal resistor setting NS2 Network segment 2 NS3 Network segment 3 NS4 Network segment 4 NS1 Network segment 1 Set terminal resistor at...

Страница 16: ...n Technical Manual 36 Outdoor tempera ture zone bound ary temperature A 1 4 0 F 20 C 3 6 0 0 0 4 F 18 C 0 1 3 2 F 16 C 0 2 6 8 F 14 C 0 3 10 4 F 12 C 0 4 14 0 F 10 C 0 5 17 6 F 8 C 0 6 21 2 F 6 C 0 7 24 8 F 4 C 0 8 For more details on settings for this item see the Design Technical Manual 37 Outdoor tempera ture zone bound ary temperature B 1 42 8 F 6 C 3 7 0 0 14 0 F 10 C 0 1 17 6 F 8 C 0 2 21 2 ...

Страница 17: ...segment LED display LED 105 LED 104 Flashing First 2 digits Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Contin...

Страница 18: ...2 3 4 Indoor unit wiring example Connect the indoor and outdoor units of the same refrigerant system as shown below Refrigerant system1 Refrigerant system2 Refrigerant system3 Master unit Master unit Master unit Signal amplifier Signal amplifier NOTE The automatic address function can be used for a maximum of 9 indoor units installed to the same refrigerant system When network is connected to othe...

Страница 19: ...microns 100 7 kPa even after depressurizing for at least 2 hours repeat the vacuum breakdown vacuum process perform triple evacu ation procedure as necessary to bring the vacuum down to 500 microns 100 7 kPa or lower After vacuum process maintain the vacuum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge Evacuation procedure 1 Remove the caps of the gas pipe ...

Страница 20: ...charged amount lbs kg Diameter of liquid pipe in mm a Additional amount for pipe length lbs ft kg m AOU36RLAVM 10 58 4 80 AOU48RLAVM 11 68 5 30 Ø 1 4 6 35 0 014 0 021 AOU60RLAVM 11 68 5 30 Ø 3 8 9 52 0 039 0 058 1 Calculation of additional amount for pipe length A Total length of ø 3 8 in ø 9 52 mm liquid pipe a 0 039 0 058 lbf ft kg m Total length of ø 1 4 in ø 6 35 mm liquid pipe a 0 014 0 021 l...

Страница 21: ...NTER button for more than 3 seconds Turn on the power of indoor unit and outdoor unit Press the ENTER button for more than 3 seconds This will be displayed when the Indoor unit connection check starts MODE EXIT SELECT ENTER ENTER ENTER 1 2 1 The number of connected indoor units 2 Volume ratio of the indoor units connection Ex When 8 units are connected Ex When the ratio is 120 Please refer to the ...

Страница 22: ...cient length of time before restarting the operation Perform test operation for each refrigerant system You can set cooling test operation or heating test operation with the push button on the outdoor unit PC board Test operation setting method Use the MODE EXIT SELECT and ENTER buttons on the indoor unit PC board to configure settings according to the procedures below Settings for starting test r...

Страница 23: ...rush current limiting resister temp rise error protective operation E 6 9 1 Outdoor unit transmission PCB parallel communi cation error Outdoor unit sen sor error E 7 1 1 Outdoor unit discharge temp thermistor 1 error E 7 2 1 Outdoor unit compressor temp thermistor 1 error E 7 3 3 Outdoor unit heat ex liquid temp thermistor error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit sucti...

Отзывы: