Fujitsu AOU36RLAVM Скачать руководство пользователя страница 20

En-18

8. 3.  Additional charging

CAUTION

Do not turn on the power unless all operations are complete.

After evacuating the system, add refrigerant.

Do not charge the system with a refrigerant other than R410A.

Always keep to the limit on the total amount of refrigerant. Exceeding the limit on the 
total amount of refrigerant will lead to malfunction during charging of refrigerant.

Do not reuse recovered refrigerant.

Use an electronic scale to measure the charging amount of refrigerant. 
Adding more refrigerant than the speci

fi

 ed amount will cause a malfunction.

Charge refrigerant using the liquid pipe.
Adding refrigerant through the gas pipe will cause a malfunction.

Add refrigerant by charging the system with the refrigerant in the liquid state. If the refrig-
erant cylinder is equipped with a siphon, it is not necessary to place the cylinder upright.

Check if the steel cylinder has a siphon installed or not before 

fi

lling. (There is an indica-

tion “with siphon for 

fi

lling liquid” on the steel cylinder.)

Filling method for cylinder with siphon

Set the cylinder vertical and 

fi

ll with the 

liquid.
(Liquid can be 

fi

lled without turning bot-

tom up with the siphon inside.)

Liquid

Gas

R410A

Filling method for other cylinders

Turn bottom up and 

fi

ll with liquid.

(Be careful to avoid turning over the 
cylinder.)

Liquid

Gas

R410A

Be sure to use the special tools for R410A for pressure resistance and to avoid mixing of 
impure substances.

If the units are further apart than the maximum pipe length, correct operation can not be 
guaranteed.

Make sure to back closing valve after refrigerant charging. Otherwise, the compressor 
may fail.

Minimize refrigerant release to the air. Excessive release is prohibited under the Freon 
Collection and Destruction Law.

8. 3. 1.  Procedure for charging the system with refrigerant

(1) Remove 

the 

charging 

port 

cap from the liquid pipe.

(2)  Attach a charging hose to the refrigerant cylinder, and connect it to the charging port.
(3) Add 

refrigerant 

by 

calculating 

the 

additional refrigerant volume in accordance with the 

calculation formula indicated below.

(4) Remove 

the 

charging 

hose 

and install the charging port cap.

(5) Remove 

the 

blank 

caps 

(gas 

pipe 

and liquid pipe) and open the valves.

(6) Close 

the 

blank 

caps.

(7) After 

adding 

refrigerant, 

indicate 

the added charging volume on the unit.

*  Tighten the blank caps and charging port caps to the torque values speci

fi

 ed in the Table 

A. To open and close the valves, use an M4 hexagon wrench.

8. 3. 2.  Checking total amount of refrigerant and calculating the 

amount of refrigerant charge to be added

•  The amount of refrigerant charge to be added is the total value of the basic refrigerant 

charge amount and the value calculated from the length of the liquid pipe.

•  Round up the value to 2 decimal places.

Model

“B”

Factory charged 

amount [lbs (kg)]

Diameter of liquid 

pipe [in (mm)]

“a”

Additional amount 

for pipe length [lbs/ft 

(kg/m)]

AOU36RLAVM

10.58 (4.80)

AOU48RLAVM

11.68 (5.30)

Ø 1/4 (6.35)

0.014 (0.021)

AOU60RLAVM

11.68 (5.30)

Ø 3/8 (9.52)

0.039 (0.058)

(1)  Calculation of additional amount for pipe length

A =

Total length of ø 3/8 in
(ø 9.52 mm) liquid pipe

× 0.039

(× 0.058)

[lbf/ft (kg/m)]

+

Total length of ø 1/4 in
(ø 6.35 mm) liquid pipe

× 0.014

(× 0.021)

[lbf/ft (kg/m)]

ft (m)

ft (m)

lbs (kg)

lbs (kg)

=

Total

lbs (kg)

(Round up A to 2 decimal place)

(2) Calculation 

of 

total 

refrigerant 

amount

C = A+B =

lbs (kg)

(B : Factory charged amount)

NOTE:

Check the total refrigerant amount under the following conditions

Condition

Computational formula

Total amount of refrigerant

 34.61 lbs (15.7 kg)

<Calculation>

Outdoor unit: AOU60RLAVM
(1)  Calculation of additional amount for outdoor unit

If liquid pipe piping length is the following
Ø 3/8 in: 164 ft, Ø 1/4 in: 114 ft
(Ø 9.52 mm: 50 m , Ø 6.35 mm: 35 m)

Additional charge volume: 

A = 164 ft × 0.039 lbf/ft +114 ft × 0.014 lbf/ft
(A = 50 m × 0.058 kg/m +35 m × 0.021 kg/m)
= 8.01 lbs 
(= 3.635 kg 

 3.64 kg)

(2)  Check the total amount of refrigerant

C = A + B = 8.01 lbs + 11.68 lbs = 19.69 lbs 

 34.61 lbs

(C = A + B = 3.64 kg + 5.30 kg = 8.94 kg 

 15.7 kg)

No problem if the above condition is satis

fi

 ed.

8. 4.  Installing insulation

•  Install insulation material after conducting the “8.1 Sealing test”.
•  To prevent condensation and water droplets, install insulation material on the refrigerant 

pipe.

•  Refer to the table to determine the thickness of the insulation material.
•  If the outdoor unit is installed at a level that is higher than the indoor unit, the water that 

has condensed in the 3-way valve of the outdoor unit could travel to the indoor unit. 
Therefore, use putty in the space between the pipe and the insulation to prevent the 
entry of water.

Table. Selection  of  insulation
[Use an insulation material with equal heat transmission rate or below 
0.023 BTU/ft·h·°F(0.040 W/m·k)]

Insulation material

Minimum thickness [in (mm)]

Relative humidity

 70%

 75%

 80%

 85%

Pipe diameter 
[in (mm)]

1/4 (6.35)

5/16 (8)

3/8 (10)

1/2 (13)

11/16 (17)

3/8 (9.52)

3/8 (9)

7/16 (11)

9/16 (14)

11/16 (18)

1/2 (12.70)

3/8 (10)

1/2 (12)

9/16 (15)

3/4 (19)

5/8 (15.88)

3/8 (10)

1/2 (12)

5/8 (16)

13/16 (20)

3/4 (19.05)

3/8 (10)

1/2 (13)

5/8 (16)

13/16 (21)

*  When an ambient temperature and relative humidity exceed 90 °F (32 °C), please 

strengthen heat insulation of refrigerant pipe.

8. 5.  Filling with putty

WARNING

Putty

Insulation

Fig. A

Fill the piping holes and wiring holes with putty (supplied 
locally) to avoid any gap (Fig A). If small animals such 
as insects enter the external unit, a short circuit may be 
caused near electrical components in the service panel.

If the outdoor unit is installed at a level that is higher than 
the indoor unit, the water that has condensed in the 3-way 
valve of the outdoor unit could travel to the indoor unit. 
Therefore, use putty in the space between the pipe and the 
insulation to prevent the entry of water to the indoor units.

9380545095_IM.indb   18

9380545095_IM.indb   18

11/17/2015   4:14:29 PM

11/17/2015   4:14:29 PM

Содержание AOU36RLAVM

Страница 1: ...tage Parts for the Fujitsu LonWorks cables are the following Cable Type Pairs Details Catalog Number Level 4 NEMA 22AWG 1 250ft LonWorks Shielded cable K00250LW 1 500ft LonWorks Shielded cable K00500LW This addendum information shall supersede any LonWorks cable requirements listed in any of the Airstage Design Technical Manuals or Installation Manuals Design Technical Manual for Airstage V II 208...

Страница 2: ...STALACIÓN OUTDOOR UNIT UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel agréé uniquement Solo para personal de servicio autorizado AOU36RLAVM AOU48RLAVM AOU60RLAVM 9380545095_IM indb cover1 9380545095_IM indb cover1 11 17 2015 4 14 24 PM 11 17 2015 4 14 24 PM ...

Страница 3: ...your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be neces sary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweat...

Страница 4: ...g Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury If there is a possibility of touching the fan during maintenance make sure to turn OFF the power before implementing the maintenance Even if operations are suspended the fan of outdoor unit sometim...

Страница 5: ...otal cooling capacity of indoor unit kw UTP AX054A ALL 2 4 2 Header Header uses the following parts A header is used for connecting the indoor units Header Total cooling capacity of indoor unit kw 3 6 Branches 3 8 Branches UTR H0906L UTR H0908L ALL 2 4 3 External connect kit Model Usage UTY XWZXZ6 For External input CN131 CN132 CN133 CN134 For External output Error status CN136 Operation status CN...

Страница 6: ...ure sufficient space or consult your distributing agent as it may affect the performance due to short circuit and other problems Consider the transportation route installation space maintenance space and access and install the unit in a location with sufficient space for the refrigerant piping Observe the installation space specifications that are shown in the figures Keep the same space at rear a...

Страница 7: ...rformance First separation tube optional Separation tube optional Pipe size table B Pipe size table C Pipe size table D Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit 3 3 3 Outdoor units installation in multi row Unit in mm The following settings are not recommended in case of cooling by a low outside tempera ture 1 Single parallel unit arrangement 6 150 24 600 40 1000 79 ...

Страница 8: ...tion Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters t...

Страница 9: ...ut CAUTION Hold the torque wrench at its grip keeping it in a right angle with the pipe in order to tighten the flare nut correctly Outer panel may be distorted if fastened only with a wrench Be sure to fix the elementary part with a holding wrench spanner and fasten with a torque wrench refer to below dia gram Do not apply force to the blank cap of the valve or hang a wrench etc on the cap If bla...

Страница 10: ...portion of the connector cable with the cord clamp A damaged insulation can cause a short circuit Never install a power factor improvement condenser Instead of improving the power fac tor the condenser may overheat CAUTION Risk of Electric Shock Before servicing the unit turn the power supply switch OFF Then do not touch electric parts for 20 minutes due to the risk of electric shock Always use a ...

Страница 11: ...er MAX CKT BKR GOOD Transmission cable Remote controller cable 208 230 V 60 Hz Breaker 1 208 230 V 60 Hz Outdoor unit power supply cable Indoor unit power supply cable Breaker 2 Breaker 1 Breaker 2 6 4 Transmission line CAUTION Caution when wiring cable When stripping off the coating of lead wire always use the exclusive tool such as a wire stripper If there is no exclusive tool available necessar...

Страница 12: ...mote control Remote control Remote control Power supply Power supply Power supply Indoor unit Power supply 208 230V 60Hz Remote controller 1 1 1 Remote controller Remote controller Power supply 208 230V 60Hz Power supply 208 230V 60Hz Indoor unit Indoor unit Breaker 1 Breaker 1 Breaker 1 Breaker 1 Breaker 2 Breaker 2 Breaker 2 Breaker 2 1 The number of power supply terminals is different depending...

Страница 13: ...e Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circu...

Страница 14: ...t guarantee the regulations of each country For this reason sufficient checking is necessary regarding use Especially since the fact that the equipment may not be emergency stopped in the case of breaking of the wiring to the external input terminals and communication line communication error due to noise VRF external input circuit trouble etc must be considered the provision of double measures th...

Страница 15: ...ow many outdoor units are connected to 1 refrigerant system Configure the setting DIP switch SET 5 of the terminal resistor of the outdoor units as shown below from conditions 1 to 3 SET 5 Terminal resistor Remarks 4 OFF Disable ON Enable Factory setting Figure Terminal resistor setting NS2 Network segment 2 NS3 Network segment 3 NS4 Network segment 4 NS1 Network segment 1 Set terminal resistor at...

Страница 16: ...n Technical Manual 36 Outdoor tempera ture zone bound ary temperature A 1 4 0 F 20 C 3 6 0 0 0 4 F 18 C 0 1 3 2 F 16 C 0 2 6 8 F 14 C 0 3 10 4 F 12 C 0 4 14 0 F 10 C 0 5 17 6 F 8 C 0 6 21 2 F 6 C 0 7 24 8 F 4 C 0 8 For more details on settings for this item see the Design Technical Manual 37 Outdoor tempera ture zone bound ary temperature B 1 42 8 F 6 C 3 7 0 0 14 0 F 10 C 0 1 17 6 F 8 C 0 2 21 2 ...

Страница 17: ...segment LED display LED 105 LED 104 Flashing First 2 digits Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Contin...

Страница 18: ...2 3 4 Indoor unit wiring example Connect the indoor and outdoor units of the same refrigerant system as shown below Refrigerant system1 Refrigerant system2 Refrigerant system3 Master unit Master unit Master unit Signal amplifier Signal amplifier NOTE The automatic address function can be used for a maximum of 9 indoor units installed to the same refrigerant system When network is connected to othe...

Страница 19: ...microns 100 7 kPa even after depressurizing for at least 2 hours repeat the vacuum breakdown vacuum process perform triple evacu ation procedure as necessary to bring the vacuum down to 500 microns 100 7 kPa or lower After vacuum process maintain the vacuum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge Evacuation procedure 1 Remove the caps of the gas pipe ...

Страница 20: ...charged amount lbs kg Diameter of liquid pipe in mm a Additional amount for pipe length lbs ft kg m AOU36RLAVM 10 58 4 80 AOU48RLAVM 11 68 5 30 Ø 1 4 6 35 0 014 0 021 AOU60RLAVM 11 68 5 30 Ø 3 8 9 52 0 039 0 058 1 Calculation of additional amount for pipe length A Total length of ø 3 8 in ø 9 52 mm liquid pipe a 0 039 0 058 lbf ft kg m Total length of ø 1 4 in ø 6 35 mm liquid pipe a 0 014 0 021 l...

Страница 21: ...NTER button for more than 3 seconds Turn on the power of indoor unit and outdoor unit Press the ENTER button for more than 3 seconds This will be displayed when the Indoor unit connection check starts MODE EXIT SELECT ENTER ENTER ENTER 1 2 1 The number of connected indoor units 2 Volume ratio of the indoor units connection Ex When 8 units are connected Ex When the ratio is 120 Please refer to the ...

Страница 22: ...cient length of time before restarting the operation Perform test operation for each refrigerant system You can set cooling test operation or heating test operation with the push button on the outdoor unit PC board Test operation setting method Use the MODE EXIT SELECT and ENTER buttons on the indoor unit PC board to configure settings according to the procedures below Settings for starting test r...

Страница 23: ...rush current limiting resister temp rise error protective operation E 6 9 1 Outdoor unit transmission PCB parallel communi cation error Outdoor unit sen sor error E 7 1 1 Outdoor unit discharge temp thermistor 1 error E 7 2 1 Outdoor unit compressor temp thermistor 1 error E 7 3 3 Outdoor unit heat ex liquid temp thermistor error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit sucti...

Отзывы: