En-17

8. 1.  Sealing test - Pressure (leak) testing

CAUTION

Use only nitrogen gas.
Never use refrigerant gas, oxygen, 

fl

 ammable gas or poisonous gas to pressurize the 

system. (If oxygen is used. There is danger of an explosion.)

Do not shock during sealing test.
It can rupture the pipes and cause serious injury.

Do not turn on the power unless all operations are complete.

Do not block the walls and the ceiling until the sealing test and charging of the refrigerant 
gas have been completed.

After connecting the pipes, perform a sealing test.
Recheck that the spindle of the 3-way valve are closed before performing a sealing test. 
(Fig. B)
Pour nitrogen gas through both the liquid pipe and the gas pipe.
Pressurize nitrogen gas to 609 psi (4.2 MPa) to perform the sealing test.

Check all 

fl

 are connection and brazed areas.

Then, check that the pressure has not decreased.
Compare the pressures after pressurizing and letting it stand for 24 hours, and check that 
the pressure did not decreased.
*  When the outdoor temperature changes 9 degrees F (5 degrees C), the test pressure 

changes 7.25 psi (0.05 MPa.).
If the pressure has dropped, the pipe joints may be leaking.

If a leakage is found, immediately repair it and perform a sealing test again.
* Decrease the pressure of nitrogen gas before brazing

After completing the sealing test, release the nitrogen gas from both valves.
Release the nitrogen gas slowly.

8. 2.  Vacuum process

CAUTION

Do not turn on the power unless all operations are complete.

If the system is not evacuated suf

fi

 ciently, its performance will drop.

Be sure to evacuate the refrigerant system using a vacuum pump.

The refrigerant pressure may sometimes not rise when a closed valve is opened after 
the system is evacuated using a vacuum pump. This is caused by the closure of the re-
frigerant system of the outdoor unit by the electronic expansion valve. This will not affect 
the operation of the unit.

Use a clean gauge manifold and charging hose that were designed speci

fi

 cally for use 

with R410A. Using the same vacuum equipment for different refrigerants may damage 
the vacuum pump or the unit.

Do not purge the air with refrigerants, but use a vacuum pump to evacuate the system.

•  If moisture enter the piping, follow below. (i.e., if doing work during the rainy season, 

if the actual work takes long enough that condensation may form on the inside of the 
pipes, if rain might enter the pipes during work, etc.)

•  After operating the vacuum pump for 2 hours, pressurize to 7.25 psi (0.05 MPa) 

(i.e., vacuum breakdown) with nitrogen gas, then depressurize down to 500 microns 
(-100.7 kPa) for an hour using the vacuum pump (vacuum process).

•  If the pressure does not reach 500 microns (-100.7 kPa) even after depressurizing for 

at least 2 hours, repeat the vacuum breakdown - vacuum process perform triple evacu-
ation procedure as necessary to bring the vacuum down to 500 microns (-100.7 kPa) 
or lower.

After vacuum process, maintain the vacuum for an hour and make sure the pressure 
does not rise by monitoring with a vacuum gauge.

Evacuation procedure

(1)  Remove the caps of the gas pipe and liquid pipe and check that the valves are closed.
(2)  Remove the charging cap.
(3)  Connect a vacuum pump and a pressure gauge to a charging hose and connect it to 

the charging port.

(4) Activate 

the 

vacuum 

pump 

and vacuum the indoor unit and connection piping until the 

pressure gauge becomes 500 microns (-100.7 kPa).
Evacuate from both the gas pipe and the liquid pipe.

(5) Continue 

evacuating 

the 

system 

for 

1 hour after the pressure gauge reads 

500 microns (-100.7 kPa).

(6) Remove 

the 

charging 

hose 

and reinstall the charging cap.

7. 7.   Resistance measurement of transmission cable 

(Measure with breaker OFF)

CAUTION

Do not turn on the power if the resistance between the terminals of the transmission 
cable is abnormal. Otherwise, the PC board may be damaged.

Measure the resistance between 2 terminals of a transmission cable.

(1)  Transmission cable connecting indoor units, outdoor units, and signal ampli

fi

 ers

Measure the resistance of the signal ampli

fi

 er terminal and the terminal of the indoor and 

outdoor units connected farthest away from the device where terminal resistor is mea-
sured.
A value from the table is displayed, depending on the distance from the signal ampli

fi

 er and 

the device where the terminal resistor is set.
This value is an estimate.

(2)  Transmission cable connecting outdoor units in a refrigerant system

The resistance between the terminals of the transmission cable is 45 to 60 

Ω

.

This value is an estimate.

Distance from terminal resistor [ft (m)]

0 ~328 

(0 ~100)

~656 

(~200)

~984 

(~300)

~1,312 

(~400)

~1,640 

(~500)

Approximate resistance (

Ω

)

0 ~ 50

A short circuit somewhere or 2 or more terminal resistors are con-
nected

50
60
70
80
90

100

110

120
130
140
150
160
170
180

190 ~

Faulty contact or wiring length over 1,640 ft (500 mm)

1K ~

Faulty contact, open circuit, or no termination resistor

8.  PIPE INSTALLATION II

Fig. A  Connection  system

Outdoor unit

Pressure gauge

Vacuum 

pump

Scale

Pressure regulating valve

Nitrogen

Indoor 

unit

Indoor 

unit

Fig. B

Service hose with valve core

Charging port

Charging port cap

3-way valve

Connecting pipe

Blank cap

Hexagon wrench

3/16 in (4mm)

Table. A

Pipe

3-way valve

Blank cap

Charging  port  cap

Liquid 
valve

5.2 to 6.6 lbf·ft

(7.0 to 9.0 N·m)

14.8 to 18.5 lbf·ft

(20.0 to 25.0 N·m)

9.2 to 11.8 lbf·ft

(12.5 to 16.0 N·m)

Gas 
valve

8.1 to 9.6 lbf·ft

(11.0 to 13.0 N·m)

22.1 to 25.8 lbf·ft

(30.0 to 35.0 N·m)

9.2 to 11.8 lbf·ft

(12.5 to 16.0 N·m)

9380545095_IM.indb   17

9380545095_IM.indb   17

11/17/2015   4:14:29 PM

11/17/2015   4:14:29 PM

Содержание AOU36RLAVM

Страница 1: ...tage Parts for the Fujitsu LonWorks cables are the following Cable Type Pairs Details Catalog Number Level 4 NEMA 22AWG 1 250ft LonWorks Shielded cable K00250LW 1 500ft LonWorks Shielded cable K00500LW This addendum information shall supersede any LonWorks cable requirements listed in any of the Airstage Design Technical Manuals or Installation Manuals Design Technical Manual for Airstage V II 208...

Страница 2: ...STALACIÓN OUTDOOR UNIT UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel agréé uniquement Solo para personal de servicio autorizado AOU36RLAVM AOU48RLAVM AOU60RLAVM 9380545095_IM indb cover1 9380545095_IM indb cover1 11 17 2015 4 14 24 PM 11 17 2015 4 14 24 PM ...

Страница 3: ...your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be neces sary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweat...

Страница 4: ...g Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury If there is a possibility of touching the fan during maintenance make sure to turn OFF the power before implementing the maintenance Even if operations are suspended the fan of outdoor unit sometim...

Страница 5: ...otal cooling capacity of indoor unit kw UTP AX054A ALL 2 4 2 Header Header uses the following parts A header is used for connecting the indoor units Header Total cooling capacity of indoor unit kw 3 6 Branches 3 8 Branches UTR H0906L UTR H0908L ALL 2 4 3 External connect kit Model Usage UTY XWZXZ6 For External input CN131 CN132 CN133 CN134 For External output Error status CN136 Operation status CN...

Страница 6: ...ure sufficient space or consult your distributing agent as it may affect the performance due to short circuit and other problems Consider the transportation route installation space maintenance space and access and install the unit in a location with sufficient space for the refrigerant piping Observe the installation space specifications that are shown in the figures Keep the same space at rear a...

Страница 7: ...rformance First separation tube optional Separation tube optional Pipe size table B Pipe size table C Pipe size table D Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit 3 3 3 Outdoor units installation in multi row Unit in mm The following settings are not recommended in case of cooling by a low outside tempera ture 1 Single parallel unit arrangement 6 150 24 600 40 1000 79 ...

Страница 8: ...tion Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters t...

Страница 9: ...ut CAUTION Hold the torque wrench at its grip keeping it in a right angle with the pipe in order to tighten the flare nut correctly Outer panel may be distorted if fastened only with a wrench Be sure to fix the elementary part with a holding wrench spanner and fasten with a torque wrench refer to below dia gram Do not apply force to the blank cap of the valve or hang a wrench etc on the cap If bla...

Страница 10: ...portion of the connector cable with the cord clamp A damaged insulation can cause a short circuit Never install a power factor improvement condenser Instead of improving the power fac tor the condenser may overheat CAUTION Risk of Electric Shock Before servicing the unit turn the power supply switch OFF Then do not touch electric parts for 20 minutes due to the risk of electric shock Always use a ...

Страница 11: ...er MAX CKT BKR GOOD Transmission cable Remote controller cable 208 230 V 60 Hz Breaker 1 208 230 V 60 Hz Outdoor unit power supply cable Indoor unit power supply cable Breaker 2 Breaker 1 Breaker 2 6 4 Transmission line CAUTION Caution when wiring cable When stripping off the coating of lead wire always use the exclusive tool such as a wire stripper If there is no exclusive tool available necessar...

Страница 12: ...mote control Remote control Remote control Power supply Power supply Power supply Indoor unit Power supply 208 230V 60Hz Remote controller 1 1 1 Remote controller Remote controller Power supply 208 230V 60Hz Power supply 208 230V 60Hz Indoor unit Indoor unit Breaker 1 Breaker 1 Breaker 1 Breaker 1 Breaker 2 Breaker 2 Breaker 2 Breaker 2 1 The number of power supply terminals is different depending...

Страница 13: ...e Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circu...

Страница 14: ...t guarantee the regulations of each country For this reason sufficient checking is necessary regarding use Especially since the fact that the equipment may not be emergency stopped in the case of breaking of the wiring to the external input terminals and communication line communication error due to noise VRF external input circuit trouble etc must be considered the provision of double measures th...

Страница 15: ...ow many outdoor units are connected to 1 refrigerant system Configure the setting DIP switch SET 5 of the terminal resistor of the outdoor units as shown below from conditions 1 to 3 SET 5 Terminal resistor Remarks 4 OFF Disable ON Enable Factory setting Figure Terminal resistor setting NS2 Network segment 2 NS3 Network segment 3 NS4 Network segment 4 NS1 Network segment 1 Set terminal resistor at...

Страница 16: ...n Technical Manual 36 Outdoor tempera ture zone bound ary temperature A 1 4 0 F 20 C 3 6 0 0 0 4 F 18 C 0 1 3 2 F 16 C 0 2 6 8 F 14 C 0 3 10 4 F 12 C 0 4 14 0 F 10 C 0 5 17 6 F 8 C 0 6 21 2 F 6 C 0 7 24 8 F 4 C 0 8 For more details on settings for this item see the Design Technical Manual 37 Outdoor tempera ture zone bound ary temperature B 1 42 8 F 6 C 3 7 0 0 14 0 F 10 C 0 1 17 6 F 8 C 0 2 21 2 ...

Страница 17: ...segment LED display LED 105 LED 104 Flashing First 2 digits Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Contin...

Страница 18: ...2 3 4 Indoor unit wiring example Connect the indoor and outdoor units of the same refrigerant system as shown below Refrigerant system1 Refrigerant system2 Refrigerant system3 Master unit Master unit Master unit Signal amplifier Signal amplifier NOTE The automatic address function can be used for a maximum of 9 indoor units installed to the same refrigerant system When network is connected to othe...

Страница 19: ...microns 100 7 kPa even after depressurizing for at least 2 hours repeat the vacuum breakdown vacuum process perform triple evacu ation procedure as necessary to bring the vacuum down to 500 microns 100 7 kPa or lower After vacuum process maintain the vacuum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge Evacuation procedure 1 Remove the caps of the gas pipe ...

Страница 20: ...charged amount lbs kg Diameter of liquid pipe in mm a Additional amount for pipe length lbs ft kg m AOU36RLAVM 10 58 4 80 AOU48RLAVM 11 68 5 30 Ø 1 4 6 35 0 014 0 021 AOU60RLAVM 11 68 5 30 Ø 3 8 9 52 0 039 0 058 1 Calculation of additional amount for pipe length A Total length of ø 3 8 in ø 9 52 mm liquid pipe a 0 039 0 058 lbf ft kg m Total length of ø 1 4 in ø 6 35 mm liquid pipe a 0 014 0 021 l...

Страница 21: ...NTER button for more than 3 seconds Turn on the power of indoor unit and outdoor unit Press the ENTER button for more than 3 seconds This will be displayed when the Indoor unit connection check starts MODE EXIT SELECT ENTER ENTER ENTER 1 2 1 The number of connected indoor units 2 Volume ratio of the indoor units connection Ex When 8 units are connected Ex When the ratio is 120 Please refer to the ...

Страница 22: ...cient length of time before restarting the operation Perform test operation for each refrigerant system You can set cooling test operation or heating test operation with the push button on the outdoor unit PC board Test operation setting method Use the MODE EXIT SELECT and ENTER buttons on the indoor unit PC board to configure settings according to the procedures below Settings for starting test r...

Страница 23: ...rush current limiting resister temp rise error protective operation E 6 9 1 Outdoor unit transmission PCB parallel communi cation error Outdoor unit sen sor error E 7 1 1 Outdoor unit discharge temp thermistor 1 error E 7 2 1 Outdoor unit compressor temp thermistor 1 error E 7 3 3 Outdoor unit heat ex liquid temp thermistor error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit sucti...

Отзывы: