En-21

9. 4.  Checklist

Check description

Check method

Criteria

1

High and low pressure 
values are normal.

Check it with a 
pressure gauge.

Cooling: low pressure approx. 
116 psi (0.8 MPa)
Heating: high pressure approx. 
435 psi (3.0 MPa)

2

Drain water is discharged 
smoothly through the drain 
hose.

Check it by pour-
ing water.

3

Indoor and outdoor unit 
fans are operating.

Check them visu-
ally.

4

Compressor operates after 
the indoor unit operates.

Check the operat-
ing sound.

5

Difference between inlet 
and outlet temperatures is 
normal.

Measure the 
inlet and outlet 
temperatures.

Temperature difference 10 degrees

6 Error is not displayed

Check the 7 seg-
ment LED display

Error blinking or no error code 
display

10. LED STATUS

You can determine the operating status by the lighting up and blinking of the LED display.
Check the status using the table below.

10. 1.  Normal operation codes

Mode

CODE

DESCRIPTION

Operation

C L

Cooling

H

t

Heating

o

r During oil recovery operation

d F During defrosting operation

P C During power saving operation

L n During low noise operation

10. 2.  Error codes

Mode

CODE

DESCRIPTION

Communication 
error

E

1

4.

2 Outdoor unit network communication 2 error

E

1

4.

5 The number of indoor unit shortage

Function setting er-
ror

E

2

2.

1 Indoor unit capacity error

E

2

4.

2 Connection unit number error (Indoor unit)

E

2

6.

1 Indoor unit duplicate address error

E

2

8.

1 Auto address setting error

E

2

8.

4 Signal ampli

fi

 er auto address error

Indoor unit 
actuator error

E

5

U.

1 Indoor unit miscellaneous error

Outdoor unit PCB/
Electrical compo-
nent/ Switch error

E

6

2.

3 Outdoor  unit  EEPROM  access  error

E

6

2.

6 Outdoor unit inverters communication error

E

6

2.

8 Outdoor unit EEPROM data corruption error

E

6

3.

1 Outdoor unit inverter error

E

6

7.

2

Outdoor unit inverter PCB power short interrup-
tion error

E

6

8.

2

Outdoor unit rush current limiting resister temp. 
rise error (protective operation)

E

6

9.

1

Outdoor unit transmission PCB parallel communi-
cation error

Outdoor unit sen-
sor error

E

7

1.

1 Outdoor unit discharge temp. thermistor 1 error

E

7

2.

1 Outdoor unit compressor temp. thermistor 1 error

E

7

3.

3 Outdoor unit heat ex. liquid temp. thermistor error

E

7

4.

1 Outside air temp. thermistor error

E

7

5.

1 Outdoor unit suction gas temp. thermistor error

E

7

7.

1 Outdoor unit heat sink temp. thermistor error

E

8

2.

1

Outdoor unit sub-cool heat ex. gas inlet temp. 
thermistor error

E

8

2.

2

Outdoor unit sub-cool heat ex. gas outlet temp. 
thermistor error

E

8

3.

2 Outdoor unit liquid pipe temp. thermistor 2 error

E

8

4.

1

Outdoor unit current sensor 1 error 
(permanent stop)

E

8

6.

1 Outdoor unit discharge pressure sensor error

E

8

6.

3 Outdoor unit suction pressure sensor error

E

8

6.

4 Outdoor unit high pressure switch 1 error

Outdoor unit 
actuator error

E

9

3.

1 Outdoor unit inverter compressor start up error

E

9

4.

1 Outdoor unit trip detection

E

9

5.

5

Outdoor unit compressor motor loss of synchroni-
zation

E

9

7.

1 Outdoor unit fan motor 1 lock error

E

9

7.

4 Outdoor unit fan motor 1 undervoltage error

E

9

7.

5

Outdoor unit fan motor 1 temperature error 
(protective action)

E

9

8.

1 Outdoor  unit  fan  motor  2  lock  error

E

9

8.

5

Outdoor unit fan motor 2 temperature error 
(protective action)

E

9

A.

1 Outdoor unit coil 1 (expansion valve 1) error

E

9

A.

2 Outdoor unit coil 2 (expansion valve 2) error

Refrigerant sys-
tem error

E

A

1.

1

Outdoor unit discharge temperature 1 error (per-
manent stop)

E

A

3.

1 Outdoor unit compressor 1 temperature error

E

A

4.

1 Outdoor unit high pressure error

E

A

4.

2 Outdoor unit high pressure protective action 1

E

A

5.

1 Outdoor unit low pressure error

E

A

C.

4 Outdoor unit heat sink temperature error

㪣㪜㪛㩷㫃㪸㫄㫇㩷㪑

㪣㪑

㪟㪑

㪡㪑

㪍㪑

㫅㪑

㫆㪑

㫉㪑

㫋㪑

㪬㪑

㪐㪑

㪏㪑

㪧㪑

㪻㪑

㪪㪑

㪘㪑

㪝㪑

㪚㪑

㪜㪑

㪇㪑

㪌㪑

㪊㪑

㪈㪑

㪉㪑

㪎㪑

㪋㪑

9380545095_IM.indb   21

9380545095_IM.indb   21

11/17/2015   4:14:29 PM

11/17/2015   4:14:29 PM

Содержание AOU36RLAVM

Страница 1: ...tage Parts for the Fujitsu LonWorks cables are the following Cable Type Pairs Details Catalog Number Level 4 NEMA 22AWG 1 250ft LonWorks Shielded cable K00250LW 1 500ft LonWorks Shielded cable K00500LW This addendum information shall supersede any LonWorks cable requirements listed in any of the Airstage Design Technical Manuals or Installation Manuals Design Technical Manual for Airstage V II 208...

Страница 2: ...STALACIÓN OUTDOOR UNIT UNITÉ EXTÉRIEURE UNIDAD EXTERIOR For authorized service personnel only Pour le personnel agréé uniquement Solo para personal de servicio autorizado AOU36RLAVM AOU48RLAVM AOU60RLAVM 9380545095_IM indb cover1 9380545095_IM indb cover1 11 17 2015 4 14 24 PM 11 17 2015 4 14 24 PM ...

Страница 3: ...your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be neces sary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweat...

Страница 4: ...g Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury If there is a possibility of touching the fan during maintenance make sure to turn OFF the power before implementing the maintenance Even if operations are suspended the fan of outdoor unit sometim...

Страница 5: ...otal cooling capacity of indoor unit kw UTP AX054A ALL 2 4 2 Header Header uses the following parts A header is used for connecting the indoor units Header Total cooling capacity of indoor unit kw 3 6 Branches 3 8 Branches UTR H0906L UTR H0908L ALL 2 4 3 External connect kit Model Usage UTY XWZXZ6 For External input CN131 CN132 CN133 CN134 For External output Error status CN136 Operation status CN...

Страница 6: ...ure sufficient space or consult your distributing agent as it may affect the performance due to short circuit and other problems Consider the transportation route installation space maintenance space and access and install the unit in a location with sufficient space for the refrigerant piping Observe the installation space specifications that are shown in the figures Keep the same space at rear a...

Страница 7: ...rformance First separation tube optional Separation tube optional Pipe size table B Pipe size table C Pipe size table D Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit 3 3 3 Outdoor units installation in multi row Unit in mm The following settings are not recommended in case of cooling by a low outside tempera ture 1 Single parallel unit arrangement 6 150 24 600 40 1000 79 ...

Страница 8: ...tion Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters t...

Страница 9: ...ut CAUTION Hold the torque wrench at its grip keeping it in a right angle with the pipe in order to tighten the flare nut correctly Outer panel may be distorted if fastened only with a wrench Be sure to fix the elementary part with a holding wrench spanner and fasten with a torque wrench refer to below dia gram Do not apply force to the blank cap of the valve or hang a wrench etc on the cap If bla...

Страница 10: ...portion of the connector cable with the cord clamp A damaged insulation can cause a short circuit Never install a power factor improvement condenser Instead of improving the power fac tor the condenser may overheat CAUTION Risk of Electric Shock Before servicing the unit turn the power supply switch OFF Then do not touch electric parts for 20 minutes due to the risk of electric shock Always use a ...

Страница 11: ...er MAX CKT BKR GOOD Transmission cable Remote controller cable 208 230 V 60 Hz Breaker 1 208 230 V 60 Hz Outdoor unit power supply cable Indoor unit power supply cable Breaker 2 Breaker 1 Breaker 2 6 4 Transmission line CAUTION Caution when wiring cable When stripping off the coating of lead wire always use the exclusive tool such as a wire stripper If there is no exclusive tool available necessar...

Страница 12: ...mote control Remote control Remote control Power supply Power supply Power supply Indoor unit Power supply 208 230V 60Hz Remote controller 1 1 1 Remote controller Remote controller Power supply 208 230V 60Hz Power supply 208 230V 60Hz Indoor unit Indoor unit Breaker 1 Breaker 1 Breaker 1 Breaker 1 Breaker 2 Breaker 2 Breaker 2 Breaker 2 1 The number of power supply terminals is different depending...

Страница 13: ...e Screw with special washer Ring terminal Cable Shielding the transmission cable Connect both ends of the shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circu...

Страница 14: ...t guarantee the regulations of each country For this reason sufficient checking is necessary regarding use Especially since the fact that the equipment may not be emergency stopped in the case of breaking of the wiring to the external input terminals and communication line communication error due to noise VRF external input circuit trouble etc must be considered the provision of double measures th...

Страница 15: ...ow many outdoor units are connected to 1 refrigerant system Configure the setting DIP switch SET 5 of the terminal resistor of the outdoor units as shown below from conditions 1 to 3 SET 5 Terminal resistor Remarks 4 OFF Disable ON Enable Factory setting Figure Terminal resistor setting NS2 Network segment 2 NS3 Network segment 3 NS4 Network segment 4 NS1 Network segment 1 Set terminal resistor at...

Страница 16: ...n Technical Manual 36 Outdoor tempera ture zone bound ary temperature A 1 4 0 F 20 C 3 6 0 0 0 4 F 18 C 0 1 3 2 F 16 C 0 2 6 8 F 14 C 0 3 10 4 F 12 C 0 4 14 0 F 10 C 0 5 17 6 F 8 C 0 6 21 2 F 6 C 0 7 24 8 F 4 C 0 8 For more details on settings for this item see the Design Technical Manual 37 Outdoor tempera ture zone bound ary temperature B 1 42 8 F 6 C 3 7 0 0 14 0 F 10 C 0 1 17 6 F 8 C 0 2 21 2 ...

Страница 17: ...segment LED display LED 105 LED 104 Flashing First 2 digits Last 2 digits When F3 to F9 are displayed continue to press the SELECT button until F2 is displayed 2 Setting the first 2 digits 3 Setting the last 2 digits Continue to press the SELECT button until the desired number appears at the last 2 digits Every press of the SELECT button will change the setting number for the first 2 digits Contin...

Страница 18: ...2 3 4 Indoor unit wiring example Connect the indoor and outdoor units of the same refrigerant system as shown below Refrigerant system1 Refrigerant system2 Refrigerant system3 Master unit Master unit Master unit Signal amplifier Signal amplifier NOTE The automatic address function can be used for a maximum of 9 indoor units installed to the same refrigerant system When network is connected to othe...

Страница 19: ...microns 100 7 kPa even after depressurizing for at least 2 hours repeat the vacuum breakdown vacuum process perform triple evacu ation procedure as necessary to bring the vacuum down to 500 microns 100 7 kPa or lower After vacuum process maintain the vacuum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge Evacuation procedure 1 Remove the caps of the gas pipe ...

Страница 20: ...charged amount lbs kg Diameter of liquid pipe in mm a Additional amount for pipe length lbs ft kg m AOU36RLAVM 10 58 4 80 AOU48RLAVM 11 68 5 30 Ø 1 4 6 35 0 014 0 021 AOU60RLAVM 11 68 5 30 Ø 3 8 9 52 0 039 0 058 1 Calculation of additional amount for pipe length A Total length of ø 3 8 in ø 9 52 mm liquid pipe a 0 039 0 058 lbf ft kg m Total length of ø 1 4 in ø 6 35 mm liquid pipe a 0 014 0 021 l...

Страница 21: ...NTER button for more than 3 seconds Turn on the power of indoor unit and outdoor unit Press the ENTER button for more than 3 seconds This will be displayed when the Indoor unit connection check starts MODE EXIT SELECT ENTER ENTER ENTER 1 2 1 The number of connected indoor units 2 Volume ratio of the indoor units connection Ex When 8 units are connected Ex When the ratio is 120 Please refer to the ...

Страница 22: ...cient length of time before restarting the operation Perform test operation for each refrigerant system You can set cooling test operation or heating test operation with the push button on the outdoor unit PC board Test operation setting method Use the MODE EXIT SELECT and ENTER buttons on the indoor unit PC board to configure settings according to the procedures below Settings for starting test r...

Страница 23: ...rush current limiting resister temp rise error protective operation E 6 9 1 Outdoor unit transmission PCB parallel communi cation error Outdoor unit sen sor error E 7 1 1 Outdoor unit discharge temp thermistor 1 error E 7 2 1 Outdoor unit compressor temp thermistor 1 error E 7 3 3 Outdoor unit heat ex liquid temp thermistor error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit sucti...