manualshive.com logo in svg
background image

En-5

Thicknesses of Annealed Copper Pipes (R410A)

Pipe outside diameter [in (mm)]

Thickness [in (mm)]

1/4 (6.35)

0.032 (0.80)

3/8 (9.52)

0.032 (0.80)

1/2 (12.70)

0.032 (0.80)

5/8 (15.88)

0.039 (1.00)

3/4 (19.05)

0.039 (1.20)

4.2. Pipe 

requirement

 

CAUTION

Refer to the installation manual for the outdoor unit for description of allowable pipe 
length and height difference.

Use pipe with water-resistant heat insulation.

 

CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause 
water leaks.
Use heat insulation with heat resistance above 248 °F (120 °C). (Reverse cycle model 
only)
In addition, if the humidity level at the installation location of the refrigerant piping is 
expected to exceed 70 %, install heat insulation around the refrigerant piping. If the 
expected humidity level is 70 to 80 %, use heat insulation that is 9/16 in (15 mm) or 
thicker and if the expected humidity exceeds 80 %, use heat insulation that is 13/16 in 
(20 mm) or thicker. If heat insulation is used that is not as thick as specified, condensa-
tion may form on the surface of the insulation. In addition, use heat insulation with heat 
conductivity of 0.045 W/(m·K) or less (at 68 °F (20 °C)).

4.3.  Flare connection (pipe connection)

 

WARNING

Tighten the flare nuts with a torque wrench using the specified tightening method. Other-
wise, the flare nuts could break after a prolonged period, causing refrigerant to leak and 
generate hazardous gas if the refrigerant comes into contact with a flame.

4.3.1. Flaring

Use special 

fl

 are tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3)  Insert the flare nut (always use the flare nut attached to the indoor and outdoor units 

(or RB unit) respectively) onto the pipe and perform the flare processing with a flare 
tool. Use the special R410A flare tool. Leakage of refrigerant may result if other flare 
nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

B

A

L

Check if [L] is flared uniformly and 
is not cracked or scratched.

Pipe

Die

Pipe outside diameter 

[in (mm)]

Dimension A [in (mm)]

Dimension B 

0 (0)  

-0.015 (-0.4)

  

[in (mm)]

Flare tool for R410A, 

clutch type

1/4 (6.35)

0 to 0.020

(0 to 0.5)

3/8 (9.1)

3/8 (9.52)

1/2 (13.2)

1/2 (12.70)

5/8 (16.6)

5/8 (15.88)

3/4 (19.7)

3/4 (19.05)

15/16 (24.0)

When using conventional (R22) flare tools to flare R410A pipes, the dimension A should 
be approximately 0.020 in (0.5 mm) more than indicated in the table (for flaring with 
R410A flare tools) to achieve the specified flaring. Use a thickness gauge to measure the 
dimension A. It is recommended that a R410A flaring tool is used.

Width across 

flats

Pipe outside diameter 

[in (mm)]

Width across flats of Flare 

nut [in (mm)]

1/4 (6.35)

11/16 (17)

3/8 (9.52)

7/8 (22)

1/2 (12.70)

1 (26)

5/8 (15.88)

1-1/8 (29)

3/4 (19.05)

1-7/16 (36)

4.3.2. Bending pipes

• The pipes are shaped by your hands or pipe bender. Be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bent or stretched, the material will harden, making it difficult 

to bend or stretch them anymore. Do not bend or stretch the pipes more than 3 times.

 

CAUTION

To prevent breaking of the pipe, avoid sharp bends. 

If the pipe is bent repeatedly at the same place, it will break.

4.3.3. Pipe connection

 

CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the flare nut cannot tightened smoothly. If the flare 
nut is forced to turn, the threads will be damaged.

Do not remove the flare nut from the indoor unit pipe until immediately before connect-
ing the connection pipe.

Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as 
this would reduce the lifetime of the units.

Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to 
tighten the flare nut correctly.

When the flare nut is tight-
ened properly by your hand, 
hold the body side coupling 
with a separate spanner, then 
tighten with a torque wrench. 
(See the table below for the 
flare nut tightening torques.)

Tighten with 2 
wrenches.

Holding wrench

Flare nut 

Connection pipe

Indoor unit pipe (Body side)

Torque wrench

Flare nut [in (mm)]

Tightening torque [lbf·ft (N·m)]

1/4 (6.35) dia.

11.8 to 13.3 (16 to 18)

3/8 (9.52) dia.

23.6 to 31.0 (32 to 42)

1/2 (12.70) dia.

36.1 to 45.0 (49 to 61)

5/8 (15.88) dia.

46.5 to 55.3 (63 to 75)

3/4 (19.05) dia.

66.4 to 81.1 (90 to 110)

5.  FORMING THE DRAIN HOSE AND PIPE

 

CAUTION

Do not remove the flare nut from the indoor unit pipe until immediately before 
connecting the connection pipe.

To prevent breaking of the pipe, avoid sharp bends.

If the pipe is bent repeatedly at the same place, it will break.

[For 

1

 Rear piping, 

2

 Right piping and 

3

 Bottom piping]

•  Install the indoor unit piping in the direction of the wall hole and bind the drain hose and 

pipe together with vinyl tape. 

•  Install the piping so that the drain hose is at the bottom.
•  Wrap the pipes of the indoor unit that are visible from the outside with decorative tape.

Pipe (Top)

Cloth tape
  (Accessories)

2

 Right piping

3

 Bottom piping

Bind with vinyl tape

Drain hose (Bottom)

1

 Rear piping

9373370444_IM.indb   5

9373370444_IM.indb   5

29/11/2017   AM 11:48:43

29/11/2017   AM 11:48:43

Содержание Airstage ASUB18TLAV1

Страница 1: ...Français Español MANUEL D INSTALLATION MANUAL DE INSTALACIÓN UNITÉ INTÉRIEURE Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado PART No 9373370444 9373370444_IM indb 1 9373370444_IM indb 1 29 11 2017 AM 11 48 42 29 11 2017 AM 11 48 42 ...

Страница 2: ...aker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical c...

Страница 3: ...ump adapter A conventional vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not back flow into the system Use one capable for vacuum suction of 5 Torr 755 mm Hg 100 7 kPa Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or othe...

Страница 4: ... install the unit where it will be exposed to direct sunlight 3 2 Installation dimension For the drain hose exten sion use a drain hose with a 5 8 in 16 mm inside diameter 71 in 1800 mm or more 60 in 1500 mm or more Right side 8 in 200 mm or more 3 in 60 mm or more Left side 2 in 50 mm or more Wall hook bracket 3 3 Installing the unit WARNING Install the air conditioner in a location which can wit...

Страница 5: ...f copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are avail able on the market Wall hook bracket Tapping screw big 3 3 2 Cutting the hole in the wall for the connecting piping WARNING If the wall pipe is not used the cable may touch metal and cause electric leakage 1 Cut a 3 1 8 in 80 mm diameter hole in the wall ...

Страница 6: ...A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A It is recommended that a R410A flaring tool is used Width across flats Pipe outside diameter in mm Width across flats of Flare nut in mm 1 4 6 35 11 16 17 3 8 9 52 7 8 22 1 2 12 70 1 26 5 8 15 88 1 1 8 29 3 4 19 05 1 7 16 36 4 3 2 Bending pipes The pipes are shaped by your hands or pipe bender Be carefu...

Страница 7: ...nd positively Connect the connection cable firmly to the terminal board Imperfect installation may cause a fire If the supply cable is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable ...

Страница 8: ...WORKS compatible cable Remote con troller cable 2 wire type 22 AWG to 16 AWG 0 33 to 1 25 mm Sheathed PVC cable Non polar 2 core twisted pair 18AWG Thermostat cable 2 core Use sheathed non twisted pair cable Remote con troller cable 3 wire type 22 AWG 0 33 mm Sheathed PVC cable Polar 3 core 6 2 Wiring method Example 2 2 2 Outdoor unit or RB unit 1 Breaker 1 Ground Fault Equipment Breaker GFEB Brea...

Страница 9: ...loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be dam aged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break...

Страница 10: ...al parts 6 6 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 49...

Страница 11: ... Connected unit c Select very low current use contacts usable at DC 12 V DC 1 mA or less d The wiring is different from Apply voltage terminals Be sufficiently careful when wiring When connected to Dry contact terminals of multiple indoor units with a connected unit insulate each indoor unit with relay etc as shown on below example K1 CNA02 CNA02 CNA02 K2 K3 K4 K5 K6 Power supply for relay Indoor ...

Страница 12: ...ing when turning ON output to the connected external heater can be set by changing Dip switch on PC board Dip switch SET2 SW3 Fan setting when ON is output to the external heater Explanation OFF Factory setting OFF For the fan setting details see the Design Technical Manual ON ON 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Please set by either of the methods...

Страница 13: ...lt in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from 0 Setting Setting range Type of switch Remote controller ad dress 0 to 15 Setting example 0 RC AD Example If 4 indoor units are connected Remote controller Indoor unit Indoor unit In...

Страница 14: ...t Stop Allow an external controller to start or stop the system or to perform an emergency stop If an emergency stop is performed from an external controller all refrigerant sys tems will be disabled If forced stop is set indoor unit stops by the input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced Stop Error report target 47 00 All ...

Страница 15: ... Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0s 1 0s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON...

Страница 16: ...e used for the test run 9 2 Test run using remote controller Refer to the Installation Manual for the remote controller to perform the test run using the remote controller When the air conditioner is being test run the OPERATION and TIMER indicator lamp flash slowly at the same time 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is...

Страница 17: ...1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circula tion 13 1 RB unit error Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Wired remote controller display UTY RNKU ...

Отзывы: