En-14

(

1

 Rear, 

2

 Right and 

3

 Bottom piping)

Indoor unit pipe 
(heat insulation)

Overlap the insulation.

Connection pipe
(heat insulation)

Bind the pipes together so 
that there is no gap.

Vinyl tape

(For 

4

 Left bottom piping, 

5

 Left piping, 

6

 Center piping and 

7

 Left rear piping)

•  Wrap the area which accommodates the rear piping housing section with cloth tape.
•  Bind the connection cable with vinyl tape.
•  Bundle the piping and drain hose together by wrapping them with cloth tape over the 

range within which they 

fi

 t into the rear piping housing section.

Connection pipe

Indoor unit pipe

Cloth tape 
(Accessories)

Wrap with cloth tape.

Connection cable (Transmission and Remote controller cable)

Connection cable (Power supply cable)

Vinyl tape

Pipe

Pipe

Cloth tape

Drain hose

Wrap with cloth tape

(2) Temporarily fasten the connection cable along the connection pipe with vinyl tape.
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain 

water and wind cannot blow in.

(5) Fasten the drain hose to the outside wall, etc.

Saddle*

Pipe

Outside wall cap*

*Locally purchased

Wall

(Outdoors)

Sealer putty*

GOOD

Drain hose

Saddle

Lifted up

Wave

End in water

PROHIBITED

7.3.2. Checking the function settings

Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check 
the function settings. It is necessary to disconnect the power in order to return to normal 
operation mode.

(1) Indoor unit and refrigerant address indication

Indication pattern

Indicator name

Indication pattern

Indoor unit address

Refrigerant address

OPERATION indicator lamp (Green)

ON

Flash (1.0s ON/1.0s OFF)

TIMER indicator lamp (Orange)

Address: tens place (0.5s ON/0.5s OFF)

FILTER indicator lamp (Red)

Address: ones place (0.5s ON/0.5s OFF)

• Indoor unit address example

(Example) ADDRESS : 24

OPERATION indicator 
lamp (Green)

TIMER indicator lamp 
(Orange)

FILTER indicator lamp 
(Red)

10 sec

1 cycle 12 sec

8 sec

ON

OFF

0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s

0.5s 0.5s 0.5s 0.5s

ON

OFF

ON

OFF

ON

• Refrigerant address example

(Example) ADDRESS : 30

OPERATION indicator 
lamp (Green)

TIMER indicator lamp 
(Orange)

FILTER indicator lamp 
(Red)

9 sec

1 cycle 12 sec

ON

OFF

1.0s

1.0s

1.0s

1.0s

1.0s

1.0s

1.0s

0.5s 0.5s 0.5s 0.5s 0.5s 0.5s

ON

OFF

ON

OFF

OFF

• Setting details

Function number

Item

Setting number

01

Indoor unit address

00 to 63

02

Refrigeration address

00 to 99

For use with a remote controller, set all rotary switches to 0, and refer to “7.1. Setting the 
address” for details.
All switches are set to 0 at the factory.

(2) Others

Indication pattern

Indicator Name

Indication pattern

OPERATION indicator lamp (Green)

Function number; tens place (0.5s ON/0.5s OFF)

TIMER indicator lamp (Orange)

Function number; ones place (0.5s ON/0.5s OFF)

FILTER indicator lamp (Red)

Setting number: (0 to 9) (0.5s ON/0.5s OFF)

(Example) Function : 31, Setting number : 2

OPERATION indicator 
lamp (Green)

TIMER indicator lamp 
(Orange)

FILTER indicator lamp 
(Red)

11 sec

10 sec

9 sec

1 cycle 12 sec

ON

OFF

0.5s 0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s 0.5s 0.5s

ON

OFF

ON

OFF

8. FINISHING

 CAUTION

After checking for gas leaks (refer to the Installation Manual of the outdoor unit), 
perform this section.

Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do 
so may cause water leaks.

8.1.  Connection pipe, cable and drain hose

Insulate the drain hose, if necessary, to prevent it from freezing.

(1) Insulate between pipes.

• For 

1

 Rear, 

2

 Right and 

3

 Bottom piping, overlap the connection pipe heat insulation 

and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no 
gap.

• For 

4

 Left bottom piping, 

5

 Left piping, 

6

 Center piping and 

7

 Left rear piping, butt 

the connection pipe heat insulation and indoor unit pipe heat insulation together and 
bind them with vinyl tape so that there is no gap.

9373370444_IM.indb   14

9373370444_IM.indb   14

29/11/2017   AM 11:48:44

29/11/2017   AM 11:48:44

Содержание Airstage ASUB18TLAV1

Страница 1: ...Français Español MANUEL D INSTALLATION MANUAL DE INSTALACIÓN UNITÉ INTÉRIEURE Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado PART No 9373370444 9373370444_IM indb 1 9373370444_IM indb 1 29 11 2017 AM 11 48 42 29 11 2017 AM 11 48 42 ...

Страница 2: ...aker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical c...

Страница 3: ...ump adapter A conventional vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not back flow into the system Use one capable for vacuum suction of 5 Torr 755 mm Hg 100 7 kPa Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or othe...

Страница 4: ... install the unit where it will be exposed to direct sunlight 3 2 Installation dimension For the drain hose exten sion use a drain hose with a 5 8 in 16 mm inside diameter 71 in 1800 mm or more 60 in 1500 mm or more Right side 8 in 200 mm or more 3 in 60 mm or more Left side 2 in 50 mm or more Wall hook bracket 3 3 Installing the unit WARNING Install the air conditioner in a location which can wit...

Страница 5: ...f copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are avail able on the market Wall hook bracket Tapping screw big 3 3 2 Cutting the hole in the wall for the connecting piping WARNING If the wall pipe is not used the cable may touch metal and cause electric leakage 1 Cut a 3 1 8 in 80 mm diameter hole in the wall ...

Страница 6: ...A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A It is recommended that a R410A flaring tool is used Width across flats Pipe outside diameter in mm Width across flats of Flare nut in mm 1 4 6 35 11 16 17 3 8 9 52 7 8 22 1 2 12 70 1 26 5 8 15 88 1 1 8 29 3 4 19 05 1 7 16 36 4 3 2 Bending pipes The pipes are shaped by your hands or pipe bender Be carefu...

Страница 7: ...nd positively Connect the connection cable firmly to the terminal board Imperfect installation may cause a fire If the supply cable is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable ...

Страница 8: ...WORKS compatible cable Remote con troller cable 2 wire type 22 AWG to 16 AWG 0 33 to 1 25 mm Sheathed PVC cable Non polar 2 core twisted pair 18AWG Thermostat cable 2 core Use sheathed non twisted pair cable Remote con troller cable 3 wire type 22 AWG 0 33 mm Sheathed PVC cable Polar 3 core 6 2 Wiring method Example 2 2 2 Outdoor unit or RB unit 1 Breaker 1 Ground Fault Equipment Breaker GFEB Brea...

Страница 9: ...loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be dam aged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break...

Страница 10: ...al parts 6 6 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 49...

Страница 11: ... Connected unit c Select very low current use contacts usable at DC 12 V DC 1 mA or less d The wiring is different from Apply voltage terminals Be sufficiently careful when wiring When connected to Dry contact terminals of multiple indoor units with a connected unit insulate each indoor unit with relay etc as shown on below example K1 CNA02 CNA02 CNA02 K2 K3 K4 K5 K6 Power supply for relay Indoor ...

Страница 12: ...ing when turning ON output to the connected external heater can be set by changing Dip switch on PC board Dip switch SET2 SW3 Fan setting when ON is output to the external heater Explanation OFF Factory setting OFF For the fan setting details see the Design Technical Manual ON ON 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Please set by either of the methods...

Страница 13: ...lt in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from 0 Setting Setting range Type of switch Remote controller ad dress 0 to 15 Setting example 0 RC AD Example If 4 indoor units are connected Remote controller Indoor unit Indoor unit In...

Страница 14: ...t Stop Allow an external controller to start or stop the system or to perform an emergency stop If an emergency stop is performed from an external controller all refrigerant sys tems will be disabled If forced stop is set indoor unit stops by the input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced Stop Error report target 47 00 All ...

Страница 15: ... Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0s 1 0s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON...

Страница 16: ...e used for the test run 9 2 Test run using remote controller Refer to the Installation Manual for the remote controller to perform the test run using the remote controller When the air conditioner is being test run the OPERATION and TIMER indicator lamp flash slowly at the same time 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is...

Страница 17: ...1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circula tion 13 1 RB unit error Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Wired remote controller display UTY RNKU ...

Отзывы: