manualshive.com logo in svg
background image

En-13

7.3. Function 

setting

 WARNING

Please make this setting after completing all construction works.

• FUNCTION SETTING can be performed with the wired or wireless remote controller.

(The remote controller is optional equipment)

• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address 

settings.

• Turn the power of the indoor unit ON before starting the setting.
*  Turning on the power to the indoor units initializes EEV, so make sure the piping air tight 

test and vacuuming have been conducted before turning on the power.

*  Also check again to make sure no wiring mistakes were made before turning on the 

power.

Function details

Function

Function 

number

Setting number

Default

Details

Filter indica-
tor interval

11

00 Standard

Adjust the filter cleaning interval 
notification. If the notification 
is too early, change to setting 
01. If the notification is too late, 
change to setting 02.

01 Longer

02 Shorter

Filter indica-
tor action

13

00 Enable

Enable or disable the filter indi-
cator. Setting 02 is for use with 
a central remote controller.

01 Disable

02

Display only 
on central 
remote 
controller

Horizontal 
swing 
airflow direc-
tion

24

00 Standard

Adjust the horizontal swing 
airflow direction.
(For horizontal swing equipped 
models)

01 Left half

02 Right half

Cool air 
temperature 
trigger

30

00 Standard

Adjust the cool air trigger tem-
perature. To lower the trigger 
temperature, use setting 01. To 
raise the trigger temperature, 
use setting 02.

01 Adjust (1)

02 Adjust (2)

Heat air 
temperature 
trigger

31

00 Standard

Adjust the heat air trigger 
temperature. To lower the trig-
ger temperature by 6 degrees 
C, use setting 01. To lower 
the trigger temperature by 4 
degrees C, use setting 02. To 
raise the trigger temperature, 
use setting 03.

01 Adjust (1)

02 Adjust (2)

03 Adjust (3)

Auto restart

40

00 Enable

Enable or disable automatic 
system restart after a power 
outage.
*  Auto restart is an emergency 

function such as for power 
failure etc.
Do not start and stop the 
indoor unit by this function in 
normal operation.
Be sure to operate by the con-
trol unit, converter or external 
input device.

01 Disable

Cool Air 
Prevention

43

00 Super low

Restrain the cold airflow with 

making the airflow lower when 

starting heating operation. To 

correspond to the ventilation, 

set to 01.

01

Follow the 
setting on 
the remote 
controller

External 
control

46

00 Start/Stop

Allow an external controller to 
start or stop the system, or to 
perform an emergency stop.
*  If an emergency stop is 

performed from an external 
controller, all refrigerant sys-
tems will be disabled. 

*  If forced stop is set, indoor 

unit stops by the input to 
the external input terminals, 
and Start/Stop by a remote 
controller is restricted.

01

Emergency 
stop

02 Forced Stop

Error report 
target

47

00 All

Change the target for reporting 
errors. Errors can either be re-
ported in all locations, or only on 
the central remote controller.

01

Display only 
on central 
remote 
controller

Fan set-
ting when 
cooling 
thermostat 
OFF

49

00

Follow the 
setting on 
the remote 
controller

When set to 01, the fan stops 
when the thermostat is OFF in 
cooling operation. Connection 
of the wired remote controller 
(2-wire type or 3-wire type) 
and switching its thermistor are 
necessary.

01 Stop

Switching 
functions 
for external 
inputs and 
external 
outputs 
terminals

60

00 Mode 0

• Set this function when con-

necting the VRF system to a 
ventilator, economizer, humidi-
fier, or other external device. 

• The connection terminal 

functions can be changed 
depending on the type of ex-
ternal device. For details of the 
connection terminal functions, 
see the Design & Technical 
Manual. 

01 Mode 1

02 Mode 2

03 Mode 3

04 Mode 4

05 Mode 5

06 Mode 6

07 Mode 7

08 Mode 8

Control 
switching 
of external 
heaters

61

00

Auxiliary 
heater con-
trol 1

Sets the control method for the 
external heater being used. For 
details of the control method, 
see the Design & Technical 
Manual.

01

Auxiliary 
heater con-
trol 2

02

Heat pump 
prohibition 
control

03

Heater selec-
tion control 
using outdoor 
tempera-
ture 1

04

Heater selec-
tion control 
using outdoor 
tempera-
ture 2

Operating 
temperature 
switching 
of external 
heaters

62

00 Setting 0

• Sets the temperature condi-

tions when the external heater 
is ON. 

• For the temperature condi-

tions, see "Temperature condi-
tions when the external heater 
is ON". For a more detailed 
explanation, see the Design & 
Technical Manual. 

01 Setting 1

02 Setting 2

03 Setting 3

04 Setting 4

05 Setting 5

(Forbidden)

70

00

 

Temperature conditions when the external heater is ON

Temperature (t) when the external heater is ON= Room temperature - set temperature 

Set value of function: 61

00

01

02

03

04

Set value of func-

tion: 62

00

t < -5.4°F (-3°C)

 -0.9°F (-0.5°C)

01

t < -3.6°F (-2°C)

 -1.8°F (-1°C)

02

t < -3.6°F (-2°C)

 -3.6°F (-2°C)

03

t < -5.4°F (-3°C)

 -5.4°F (-3°C)

04

t < -7.2°F (-4°C)

 -7.2°F (-4°C)

05

t < -9.0°F (-5°C)

 -9.0°F (-5°C)

7.3.1. Button name and function

OPERATION indicator lamp (Green)

FILTER indicator lamp (Red)

TIMER indicator lamp (Orange)

9373370444_IM.indb   13

9373370444_IM.indb   13

29/11/2017   AM 11:48:44

29/11/2017   AM 11:48:44

Содержание Airstage ASUB18TLAV1

Страница 1: ...Français Español MANUEL D INSTALLATION MANUAL DE INSTALACIÓN UNITÉ INTÉRIEURE Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado PART No 9373370444 9373370444_IM indb 1 9373370444_IM indb 1 29 11 2017 AM 11 48 42 29 11 2017 AM 11 48 42 ...

Страница 2: ...aker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical c...

Страница 3: ...ump adapter A conventional vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not back flow into the system Use one capable for vacuum suction of 5 Torr 755 mm Hg 100 7 kPa Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or othe...

Страница 4: ... install the unit where it will be exposed to direct sunlight 3 2 Installation dimension For the drain hose exten sion use a drain hose with a 5 8 in 16 mm inside diameter 71 in 1800 mm or more 60 in 1500 mm or more Right side 8 in 200 mm or more 3 in 60 mm or more Left side 2 in 50 mm or more Wall hook bracket 3 3 Installing the unit WARNING Install the air conditioner in a location which can wit...

Страница 5: ...f copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are avail able on the market Wall hook bracket Tapping screw big 3 3 2 Cutting the hole in the wall for the connecting piping WARNING If the wall pipe is not used the cable may touch metal and cause electric leakage 1 Cut a 3 1 8 in 80 mm diameter hole in the wall ...

Страница 6: ...A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A It is recommended that a R410A flaring tool is used Width across flats Pipe outside diameter in mm Width across flats of Flare nut in mm 1 4 6 35 11 16 17 3 8 9 52 7 8 22 1 2 12 70 1 26 5 8 15 88 1 1 8 29 3 4 19 05 1 7 16 36 4 3 2 Bending pipes The pipes are shaped by your hands or pipe bender Be carefu...

Страница 7: ...nd positively Connect the connection cable firmly to the terminal board Imperfect installation may cause a fire If the supply cable is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable ...

Страница 8: ...WORKS compatible cable Remote con troller cable 2 wire type 22 AWG to 16 AWG 0 33 to 1 25 mm Sheathed PVC cable Non polar 2 core twisted pair 18AWG Thermostat cable 2 core Use sheathed non twisted pair cable Remote con troller cable 3 wire type 22 AWG 0 33 mm Sheathed PVC cable Polar 3 core 6 2 Wiring method Example 2 2 2 Outdoor unit or RB unit 1 Breaker 1 Ground Fault Equipment Breaker GFEB Brea...

Страница 9: ...loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be dam aged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break...

Страница 10: ...al parts 6 6 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected with function setting of indoor unit Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04 A twisted pair cable 22 AWG should be used Maximum length of cable is 49...

Страница 11: ... Connected unit c Select very low current use contacts usable at DC 12 V DC 1 mA or less d The wiring is different from Apply voltage terminals Be sufficiently careful when wiring When connected to Dry contact terminals of multiple indoor units with a connected unit insulate each indoor unit with relay etc as shown on below example K1 CNA02 CNA02 CNA02 K2 K3 K4 K5 K6 Power supply for relay Indoor ...

Страница 12: ...ing when turning ON output to the connected external heater can be set by changing Dip switch on PC board Dip switch SET2 SW3 Fan setting when ON is output to the external heater Explanation OFF Factory setting OFF For the fan setting details see the Design Technical Manual ON ON 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Please set by either of the methods...

Страница 13: ...lt in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from 0 Setting Setting range Type of switch Remote controller ad dress 0 to 15 Setting example 0 RC AD Example If 4 indoor units are connected Remote controller Indoor unit Indoor unit In...

Страница 14: ...t Stop Allow an external controller to start or stop the system or to perform an emergency stop If an emergency stop is performed from an external controller all refrigerant sys tems will be disabled If forced stop is set indoor unit stops by the input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced Stop Error report target 47 00 All ...

Страница 15: ... Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0s 1 0s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON...

Страница 16: ...e used for the test run 9 2 Test run using remote controller Refer to the Installation Manual for the remote controller to perform the test run using the remote controller When the air conditioner is being test run the OPERATION and TIMER indicator lamp flash slowly at the same time 10 CHECK LIST Pay special attention to the check items below when installing the indoor unit s After installation is...

Страница 17: ...1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circula tion 13 1 RB unit error Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Wired remote controller display UTY RNKU ...

Отзывы: