WIRING SPECIFICATIONS
Use
Size
Wire type
Remarks
Power supply cable
Maximum
16 AWG
(1.25 mm
2
)
60245 IEC 57 or equivalent
1 ø AC208-
240 V 50/60 Hz,
2-Wire + ground
(Always ground the unit)
Minimum
20 AWG
(0.5 mm
2
)
Transmission cable
Ethernet category 5 or higher
STP LAN cable with RJ45
Straight cable
Fuse capacity
1.25 A
Always ground the unit
CONFIGURATION PROCEDURES
The following procedures presume that all VRF indoor/outdoor units are commissioned
and operational, and that BACnet
®
network toward the BMS workstation is operational.
1. Power device
The first step to perform is to power up the device. To do so, a power supply working with any
of the voltage range allowed is needed. Once connected the LED_PWR will turn on.
2. Connect to BACnet
®
interface
Connect the communication cable coming from the network hub or switch to the Ethernet port
(Figure above) of the gateway. The cable to be used is a straight Ethernet STP CAT5 or higher
cable.
In case there is no response from the BACnet
®
devices to the frames sent by gateway, check
that they are operational and reachable from the network connection used by the gateway.
Check the gateway Ethernet interface sending Pings to its IP address using a PC connected to
the same Ethernet IP network. If the problem persists communicating through the LAN of the
building, contact the network administrator.
The BACnet Gateway for VRF System comes with DHCP functionality enabled by default.
3. Connect to VRF network
Use the LON connector in the left bottom corner of the gateway in order to connect the VRF
network to the UTY-VBGX.
UTY-VBGX(LON terminal block)
C2
VRF network connection through LON
VRF network
Cable(Three wires)
Cable(Three wires)
A
-
-
X1
B
+
+
X2
SGND
SGND
4. Connect to PC (Configuration tool)
This action allows the user to have access to configuration and monitoring of the device. Two
methods to connect to the PC can be used:
● USB cable: To connect the device to the PC the USB cable supplied should be plugged to
the USB Console port.This method is recommended.
● Ethernet: Using the ETH port of the gateway.
● Install the configuration tool to the PC before connecting to the Gateway.
- (05 - 158) -
C
O
N
TRO
L
SY
ST
EM
C
O
N
TRO
L
SY
ST
EM
Содержание Airstage AGUA12TLAV1
Страница 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Страница 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Страница 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Страница 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Страница 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Страница 194: ... INSTALLATION PLACE Unit in mm 1 25 3 70 5 122 8 200 3 62 4 80 60 1 500 71 1 800 04 61 INDOOR UNITS INDOOR UNITS ...
Страница 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Страница 204: ... MODELS AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV 04 71 INDOOR UNITS INDOOR UNITS ...
Страница 206: ...4 3 CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 04 73 INDOOR UNITS INDOOR UNITS ...
Страница 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Страница 209: ...4 6 MEDIUM STATIC PRESSURE DUCT TYPE MODELS ARUM24TLAV ARUM30TLAV ARUM36TLAV 04 76 INDOOR UNITS INDOOR UNITS ...
Страница 210: ...4 7 HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 04 77 INDOOR UNITS INDOOR UNITS ...
Страница 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Страница 213: ...4 9 COMPACT FLOOR TYPE MODELS AGUA4TLAV1 AGUA7TLAV1 AGUA9TLAV1 AGUA12TLAV1 AGUA14TLAV1 04 80 INDOOR UNITS INDOOR UNITS ...
Страница 214: ...4 10 FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 04 81 INDOOR UNITS INDOOR UNITS ...
Страница 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Страница 216: ...4 12 WALL MOUNTED TYPE MODELS ASUA4TLAV1 ASUA7TLAV1 ASUA9TLAV1 04 83 INDOOR UNITS INDOOR UNITS ...
Страница 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Страница 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Страница 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Страница 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Страница 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Страница 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Страница 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Страница 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Страница 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Страница 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Страница 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Страница 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Страница 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Страница 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...