WIRED R.C.
z
Step1: RB unit function setting (Case of VR-II series)
Set SET2 of DIP switch to "Priority given to administrative indoor unit" with function setting of
RB unit. (SET2-1:OFF, SET2-2:ON)
→Refer to 2-9. RB UNIT
z
Step1: Outdoor unit function setting (Case of V-II)
Set to "Priority given to administrative indoor unit" with function setting of outdoor unit.
→Refer to 2-1. OUTDOOR UNIT
z
Step2: Wired remote controller setting
(1) After the indoor unit stops operation, press the “MODE” button of wired remote controller
for 5 seconds continuously.
The operating mode of the wired remote controller display lights on after 5 seconds as
follows.
(1)-a) The indication not
set as "Administrative
indoor unit"
(1)-b) The indication
set as "Administrative
indoor unit"
NOTES
●
“MODE ” button is locked by below reasons while the marking lights on.
In such case, “Administrative Indoor Unit” cannot be set or released.
●
“Priority on Administrative Indoor Unit” is not selected in the setting of priority mode of outdoor unit.
→Set “Administrative Indoor Unit” in the wired remote controller after selecting “Priority on
Administrative Indoor Unit” in setting of priority mode of outdoor unit.
●
Another indoor unit was set to “Administrative Indoor Unit” already.
→Release the setting “Administrative Indoor Unit” of another indoor unit.
Operation Lock Display
(2) Press the “MODE ” button.
Display (1)-b) when setting, and display (1)-a) when releasing.
→ The display blinks when the “MODE ” button is pressed, and the display of (1)-a) and (1)-b)
alters whenever the “MODE ” button is pressed.
→ The contents set in the wired remote controller are transferred to the indoor unit
immediately after the display is selected. It may take 10 seconds depending on
communication conditions. While this period, the button operation will be suspended.
→ It returns to the normal display after 20 seconds automatically if the operation button is
not pressed.
→ When setting or releasing is completed, the indication on wired remote controller changes
to the normal indication from blinking.
(3) Complete the setting or releasing of “Administrative Indoor Unit”.
Press the “MODE ” button of the wired remote controller again for 5 seconds continuously.
→ The indication returns to normal display if the “MODE” button is pressed for 5 seconds
continuously.
(It returns to normal indication after 20 seconds even if the “MODE ” button is not pressed.)
- (07 - 145) -
FUN
C
TI
O
N
SE
TTI
N
G
FUN
C
TI
O
N
SE
TTI
N
G
Содержание Airstage AGUA12TLAV1
Страница 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Страница 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Страница 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Страница 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Страница 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Страница 194: ... INSTALLATION PLACE Unit in mm 1 25 3 70 5 122 8 200 3 62 4 80 60 1 500 71 1 800 04 61 INDOOR UNITS INDOOR UNITS ...
Страница 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Страница 204: ... MODELS AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV 04 71 INDOOR UNITS INDOOR UNITS ...
Страница 206: ...4 3 CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 04 73 INDOOR UNITS INDOOR UNITS ...
Страница 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Страница 209: ...4 6 MEDIUM STATIC PRESSURE DUCT TYPE MODELS ARUM24TLAV ARUM30TLAV ARUM36TLAV 04 76 INDOOR UNITS INDOOR UNITS ...
Страница 210: ...4 7 HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 04 77 INDOOR UNITS INDOOR UNITS ...
Страница 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Страница 213: ...4 9 COMPACT FLOOR TYPE MODELS AGUA4TLAV1 AGUA7TLAV1 AGUA9TLAV1 AGUA12TLAV1 AGUA14TLAV1 04 80 INDOOR UNITS INDOOR UNITS ...
Страница 214: ...4 10 FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 04 81 INDOOR UNITS INDOOR UNITS ...
Страница 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Страница 216: ...4 12 WALL MOUNTED TYPE MODELS ASUA4TLAV1 ASUA7TLAV1 ASUA9TLAV1 04 83 INDOOR UNITS INDOOR UNITS ...
Страница 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Страница 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Страница 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Страница 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Страница 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Страница 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Страница 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Страница 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Страница 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Страница 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Страница 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Страница 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Страница 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Страница 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...