2-4. SELECTION OF PIPE HEAT INSULATING MATERIAL
●
Always insulate the refrigerant pipe to prevent condensation and water droplets by the
refrigerant pipe.
●
Decide the thickness of the heat insulating material by referring to the recommended
minimum thickness in Table 1. (For installation condition T=90°F DB (32°C DB),
humidity≤70%, humidity≤75%, humidity≤80%, humidity≤85%)
● When the outdoor unit is installed in a higher position than the indoor unit, fill the connecting
part gap with putty, etc. to prevent the dew condensation water of the valve of the outdoor
unit from flowing to the indoors from the gap between the pipe and the heat insulating
material.
● Liquid pipe and gas pipe should be completely insulated with same specification.
●
In case not to insulate and not to seal refrigerant pipe completely, it will become the cause of
water leak.
●
Table1 Size of refrigerant pipe and recommended minimum thickness of heat insulating
material
(In case a heat insulating material which thermal conductivity is equal to or less than 0.040 W/(m·k)
is used. )
Recommended minimum thickness for heat
insulating material [in. (mm)]
Relative humidity
≤70%
≤75%
≤80%
≤85%
Refrigerant
pipe
Outside
diameter [in.
(mm)]
1/4" (6.35)
5/16" (8) 13/32" (10) 1/2" (13) 21/32" (17)
3/8" (9.52)
11/32" (9) 7/16" (11) 9/16" (14) 23/32" (18)
1/2" (12.70)
13/32" (10) 15/32" (12) 19/32" (15) 3/4" (19)
5/8" (15.88)
13/32" (10) 15/32" (12) 5/8" (16) 25/32" (20)
3/4" (19.05)
13/32" (10) 1/2" (13)
5/8" (16) 13/16" (21)
●
When an ambient temperature and relative humidity exceed 90°F DB (32°C DB)and 85%
respectively, strengthen heat insulation of refrigerant pipe. If necessary put a heat insulation
on indoor unit casing. When not strengthening heat insulation of refrigerant pipe, the
surface of the heat insulation may be dewed.
●
Since gas pipe becomes high temperature at heating operation for heatpump type, select
the heat insulating material which heat-resistant temperature is 248°F (120°C) or more.
Gas pipe
Gas pipe
Connection cable
Finishing tape
Heat insulation
Heat insulation
Liquid pipe
Liquid pipe
●
Make sure that pipe is covered completely by the heat insulation,not exploding to air.
Inadequate heat insulation may cause condensation.
● Do not cover heat insulation gas and liquid pipes together as above figure. It may cause
condensation and capacity drop by heat loss.
- (06 - 20) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Содержание Airstage AGUA12TLAV1
Страница 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Страница 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Страница 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Страница 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Страница 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Страница 194: ... INSTALLATION PLACE Unit in mm 1 25 3 70 5 122 8 200 3 62 4 80 60 1 500 71 1 800 04 61 INDOOR UNITS INDOOR UNITS ...
Страница 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Страница 204: ... MODELS AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV 04 71 INDOOR UNITS INDOOR UNITS ...
Страница 206: ...4 3 CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 04 73 INDOOR UNITS INDOOR UNITS ...
Страница 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Страница 209: ...4 6 MEDIUM STATIC PRESSURE DUCT TYPE MODELS ARUM24TLAV ARUM30TLAV ARUM36TLAV 04 76 INDOOR UNITS INDOOR UNITS ...
Страница 210: ...4 7 HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 04 77 INDOOR UNITS INDOOR UNITS ...
Страница 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Страница 213: ...4 9 COMPACT FLOOR TYPE MODELS AGUA4TLAV1 AGUA7TLAV1 AGUA9TLAV1 AGUA12TLAV1 AGUA14TLAV1 04 80 INDOOR UNITS INDOOR UNITS ...
Страница 214: ...4 10 FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 04 81 INDOOR UNITS INDOOR UNITS ...
Страница 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Страница 216: ...4 12 WALL MOUNTED TYPE MODELS ASUA4TLAV1 ASUA7TLAV1 ASUA9TLAV1 04 83 INDOOR UNITS INDOOR UNITS ...
Страница 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Страница 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Страница 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Страница 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Страница 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Страница 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Страница 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Страница 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Страница 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Страница 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Страница 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Страница 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Страница 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Страница 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...