(2) When electricity meter used is specified by pulse constant
The connection configuration is shown below.
Touch panel
controller
measurement
line
measurement
line
Pulse constant
reference point
Pulse constant
reference point
pulse
transmission
line
pulse transmission line
CT
VT
(PT)
3ø
1ø
VT
(PT)
System Controller
Transmission line (VRF Network)
Outdoor unit
Indoor unit
RB unit
Power cable
Electricity meter
Electricity meter
to CN135
to CN135
For the electricity meter specified by pulse constant, the Input Power indicated by output pulse
must be corrected by VT/CT ratio. In this case, the settings are as follows:
Set point
Set item
Set value
Description
Remarks
Electricity
meter
Set in
accordance
with the product
manual.
-
When there is a product unique setting,
setting is performed in accordance with
the product manual. (Pulse constant
value, output coefficient, etc.)
Outdoor unit Meter No.
setting
Arbitrary
Set an unique electricity meter No. for
electricity meter identification.
The information
will become
necessary when
setting System
Controller or
ECA Tool later.
Refer also to
2-1.OUTDOOR
UNIT
Electricity meter
pulse setting
The pulse constant
value / (VT ratio x
CT ratio). However,
truncated after the
decimal point
Set the approximate number of power
meter pulses that are equivalent to
1kWh.
When set number of pulses come
from the electricity meter, the outdoor
unit communicates “1” to the System
Controller or ECA Tool.
System
Controller or
ECA Tool
Electricity meter
system setting
Unit to be measured by
electricity meter
Sets the outdoor unit and indoor unit,
measured by the electricity meter of
the meter No. set at the outdoor unit.
The value set
by each outdoor
unit is used.
Pulse setting
(Electricity meter pulse
setting value) x (VT
ratio x CT ratio)/pulse
constant
Values after the
decimal point must be
also input. *1
Set the standard number of kWh for the
value communicated from the outdoor
unit.
Set the number of kWh that
corresponds to the “1” communicated
from the outdoor unit.
Refer to the
value set by
each outdoor
unit.
*1: Input up to 6 decimal digits
[Setting example]
Equipment conditions: VT ratio=1 (not used), CT ratio=500(2500/5A), electricity meter=3200 pulse/kWh
Set value: Electricity meter pulse setting=6 (3200/ (1x500)),
Pulse setting=0.9375 (6x (1x500)/3200) ---Refer to the calculating formula of the table above.
NOTE:
Be sure to select an electricity meter that sends more pulses per 1kWh than VT ratio x CT ratio. Other-
wise, the measurement error of the power will be larger than 1kWh, thus affecting the accuracy of ECA.
- (07 - 171) -
FUN
C
TI
O
N
SE
TTI
N
G
FUN
C
TI
O
N
SE
TTI
N
G
Содержание Airstage AGUA12TLAV1
Страница 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Страница 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Страница 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Страница 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Страница 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Страница 194: ... INSTALLATION PLACE Unit in mm 1 25 3 70 5 122 8 200 3 62 4 80 60 1 500 71 1 800 04 61 INDOOR UNITS INDOOR UNITS ...
Страница 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Страница 204: ... MODELS AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV 04 71 INDOOR UNITS INDOOR UNITS ...
Страница 206: ...4 3 CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 04 73 INDOOR UNITS INDOOR UNITS ...
Страница 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Страница 209: ...4 6 MEDIUM STATIC PRESSURE DUCT TYPE MODELS ARUM24TLAV ARUM30TLAV ARUM36TLAV 04 76 INDOOR UNITS INDOOR UNITS ...
Страница 210: ...4 7 HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 04 77 INDOOR UNITS INDOOR UNITS ...
Страница 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Страница 213: ...4 9 COMPACT FLOOR TYPE MODELS AGUA4TLAV1 AGUA7TLAV1 AGUA9TLAV1 AGUA12TLAV1 AGUA14TLAV1 04 80 INDOOR UNITS INDOOR UNITS ...
Страница 214: ...4 10 FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 04 81 INDOOR UNITS INDOOR UNITS ...
Страница 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Страница 216: ...4 12 WALL MOUNTED TYPE MODELS ASUA4TLAV1 ASUA7TLAV1 ASUA9TLAV1 04 83 INDOOR UNITS INDOOR UNITS ...
Страница 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Страница 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Страница 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Страница 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Страница 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Страница 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Страница 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Страница 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Страница 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Страница 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Страница 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Страница 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Страница 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Страница 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...