9-5 Precautions for installation
9-6 Precautions for Servicing
COPPER PIPES
(1) It is necessary to choose adequate materials.
If new synthetic oil is mixed with residual oil(ex : min-
eral type) ,they may deteriorate, and block the capil-
lary tubes, or cause the compressor to fail.
So it is desirable that the amount of residual oil in
connection pipes is less than 40 mg/10 m.
Thickness of copper pipes is shown below.
(2) Control contaminants
Since new synthetic oil is easily influenced by conta-
minants (water, residual oil, etc.), it must be handled
with care more than the conventional lubricating oil.
(3) Refrigerant charge
When charging refrigerant, take into account the
slight change in the composition of the gas and liquid
phases, and always charge from the liquid phase
side whose composition is stable.
(4) Correct refrigerant charge
As there are air conditioner models using different
refrigerant such as R22, R407C, make sure to check
and not to use wrong refrigerant when installing and
servicing.
(5) Air purge
Always use a vacuum pump to purge the air.
In the case of Fujitsu General's new refrigerant
model, refrigerant for purging the air is not charged in
the outdoor unit at the factory.
Nominal
Outer diameter
Thickness
diameter (inch)
(mm)
(mm)
1/4
ø 6.35
0.8
3/8
ø 9.52
0.8
1/2
ø 12.70
0.8
5/8
ø 15.88
1.0
3/4
ø 19.05
1.0
1. Countermeasure when the refrigerant leaks
As R407C is geotropic refrigerant, the composition of
the remaining refrigerant changes when the refrigerant
leaks.
Therefore, recharging refrigerant cannot be done.
Recover the remaining refrigerant and charge the spec-
ified amount of new refrigerant.
2. Never use the existing refrigerant piping
The existing piping used for R22 cannot be used for the
cycle of HFC series refrigerant as the conventional min-
eral oils are adhering to the piping.
Due to the deteriorated mineral oils, compressor may
be damaged.
Therefore, basically use a brand new piping.
However,in case of the existing piping buried in the wall
and replacement with new piping is difficult, wash the
piping fully with detergent.
3. Replacement of refrigeration cycle parts
As refrigeration cycle parts are basically different from
conventional parts, be sure to use the parts suitable for
the refrigerant when replacing.
For R407C, the materials are being reviewed.
4. Charging wrong refrigerant
As there are air conditioner models using different
refrigerant such as R22, R407C, make sure to check
and not to use wrong refrigerant when installing and
servicing.
5. Storage of parts
When storing parts, make such treatment as packing
the parts in bags so as to avoid dusts, water, etc.
6. Replacing parts
When replacing parts, be sure to check if the parts are
suitable for the refrigerant(model).
For most refrigeration cycle parts which have same
appearance, the inside material is changed.
When changing compressor, complete brazing within
15 minutes after opening the cap. After opening the
cap, the moist air enters the compressor, and oil
absorbs the moisture causing sludge. When changing
dryer, complete brazing within one hour after the pack-
age of dryer is opened.
The desiccant starts to absorb the water content as
soon as the package of dryer is opened.
If it absorbs too much water content when replacing, it
cannot absorb fully the water content in the refrigerat-
ing cycle.
1/8
ø 28.58
1.2
1
– 133 –
Содержание AirStage AB12
Страница 2: ...Multi Air Conditioning System for Buildings VRF FREELY SELECTABLE MULTI TYPE SYSTEM SERVICE MANUAL 2 ...
Страница 76: ...MODELS AB30 AB36 AB45 AB54 RB UNIT For Heat Recovery only 7 2 LARGE CEILING TYPE 76 ...
Страница 77: ...MODELS AR7 AR9 AR12 AR14 AR18 RB UNIT For Heat Recovery only 7 3 COMPACT DUCT TYPE 77 ...
Страница 78: ...MODELS AR25 AR30 AR36 AR45 RB UNIT For Heat Recovery only 7 4 LOW STATIC PRESSURE DUCT TYPE 78 ...
Страница 79: ...MODELS AR36H AR45H AR60H RB For Heat Recovery only UNIT 7 5 HIGH STATIC PRESSURE DUCT TYPE 79 ...
Страница 80: ...MODELS AU7 AU9 AU12 AU14 AU18 RB UNIT For Heat Recovery only 7 6 COMPACT CASSETTE TYPE 80 ...
Страница 81: ...MODELS AU20 AU25 AU30 AU36 AU45 AU54 RB UNIT For Heat Recovery only 7 7 NEW CASSETTE TYPE 81 ...
Страница 82: ...MODELS 7 8 WALL MOUNTED TYPE AS14 20 24 30 82 ...
Страница 83: ...MODEL AOY90 7 9 OUTDOOR UNIT 83 ...
Страница 134: ...Models AOY90TPAMF 134 10 DISASSEMBLY ILLUSTRATION ...
Страница 135: ...Models AOY90TPAMF 135 ...
Страница 137: ...Models AOY90TPAMF 137 ...
Страница 142: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Страница 143: ...Models ABY12TFAMF ABY14TFAMF 416 8 1 417 385 868 771 488 472 443 473 ABY18TFAMF ABY24TFAMF 143 ...
Страница 149: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Страница 150: ...Models ABY12TFAMF ABY14TFAMF 416 8 1 417 385 868 771 488 472 443 473 ABY18TFAMF ABY24TFAMF 143 ...
Страница 155: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 407 876 1 505 408 435 434 506 3 ABY54TFAMF 148 ...
Страница 156: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 387 160 91 91 91 321 386 361 ABY54TFAMF 149 ...
Страница 157: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 63 876 2 385 868 763 227 321 387 436 424 684 438 ABY54TFAMF 150 ...
Страница 162: ...Models AUY20TFAMF AUY25TFAMF AUY30TFAMF AUY36TFAMF AUY45TFAMF AUY54TFAMF 155 ...
Страница 164: ...Models AUY25TLAMA AUY30TLAMA AUY36TLAMA AUY45TLAMA 157 ...
Страница 166: ...Models ARY25TLAMA ARY30TLAMA ARY36TLAMA ARY45TLAMA 57 56 109 67 338 164 67 57 56 126 109 234 143 138 108 159 ...
Страница 167: ...Models ARY25TFAMF ARY30TFAMF ARY36TFAMF ARY45TFAMF 160 ...
Страница 169: ... 162 Model ARY7TFAMF ARY9TFAMF ...
Страница 170: ...Model ARY7TFAMF ARY9TFAMF 163 875 ...
Страница 171: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 164 431 918 918 163 2 184 1 147 ...
Страница 172: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 165 ...
Страница 173: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 166 ...
Страница 175: ...422 126 477 109 477 477 109 164 422 10 75 45 117 3 338 1 338 2 56 2 477 56 1 Model ARY36TFAMF ARY45TFAMF ARY60TFAMF 168 ...
Страница 178: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 171 684 558 554 555 559 557 556 91 320 361 960 321 876 2 ...
Страница 179: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 172 91 876 1 407 1 407 2 407 3 69 ...
Страница 199: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jan 2002 Printed in Japan ...