Note 1. Monitoring 1 performs the following for 60 seconds and detects the " Room temperature " from the point that
" Operation started ".
" Indoor unit fan motor " : S-L
O
" Shunt controller discharge valve " : OFF
" Shunt controller suction valve " : OFF
" Shunt controller bypass valve " : ON
Note 2. Room temperature monitoring state.
If " Room temperature " ( T
R
) is 2 lower than the " Set temperature " ( T
S
) , " Heating " is decided and if it is higher than
2 , " Cooling " is decided.
The system operates at S-L
O
until the operation mode is decided as " Heating " or " Cool " .
This state is made monitoring 2.
Note 3. 2: [ deg ].
Note 4. When the system is in the " Refrigerant circulation stop " state continuously for 6 minutes after " Heating " or " cooling "
was decided, returns to a.
However ,this 6 minutes do not include " Refrigerant circulation stopped " by a protection function.
COOLING
HEATING
T
S
+2
-2
Fig.7-10 Operation mode at " Automatic operation "
1 Previous Note 2. " Monitoring 1 " measures the room temperature ( T
R
) and if it is " Set temperature TS +2 or less,
" Heating " is decided and " Refrigerant circulation " is started.
2 When T
S
-2 < T
R
< T
S
+2 at 1 , " Monitoring 2 " " Room fan motor " continues and monitoring of the room temperature
continues until " Cooling " or " Heating " operation is decided.
3 When " Heating " or " Cooling " is decided, the respective operation is performed in accordance with " Room temperature
control " to be described later.
4 When " Refrigerant circulation stopped " by " Cooling " or " Heating " "Room temperature adjustment " continues for
6 minutes or more, the room temperature monitoring of 2 above is performed.
5 In the state of room temperature watching stated in the above 4 , the indoor unit fan motor shall be S-L
O
.
C
C
C
6 When " Set temperature " was changed.
A) When changed during " Monitoring 1 ", judgment if performed by means of the " Set temperature " newly input after the end
of " Monitoring 1 ".
B) When changed with in the previously mentioned Note 3 monitoring range, the newly input " Set temperature " is made T
S
.
C) When changed during " Cooling operation in progress " ( including " Refrigerant circulation stopped " for under 6 minutes by
" Room temperature adjustment " ) after " Cooling operation " decision, " Cooling operation " is continued with the newly
input " Set temperature " as T
S
.
D) When changed during " Heating operation in progress " ( including " Refrigerant circulation stopped " for under 6 minutes by
" Room temperature adjustment ") after " Heating operation " decision, " Heating operation " is continued with the newly
input " Set temperature " as T
S
.
7 After entering the room temperature monitoring state after the " Refrigerant circulation state " by " Room temperature
adjustment " has continued for 6 minutes, " Cooling Heating switching is performed even when in a temperature state
which switches " Cooling Heating " by "Set temperature " change.
– 67 –
Содержание AirStage AB12
Страница 2: ...Multi Air Conditioning System for Buildings VRF FREELY SELECTABLE MULTI TYPE SYSTEM SERVICE MANUAL 2 ...
Страница 76: ...MODELS AB30 AB36 AB45 AB54 RB UNIT For Heat Recovery only 7 2 LARGE CEILING TYPE 76 ...
Страница 77: ...MODELS AR7 AR9 AR12 AR14 AR18 RB UNIT For Heat Recovery only 7 3 COMPACT DUCT TYPE 77 ...
Страница 78: ...MODELS AR25 AR30 AR36 AR45 RB UNIT For Heat Recovery only 7 4 LOW STATIC PRESSURE DUCT TYPE 78 ...
Страница 79: ...MODELS AR36H AR45H AR60H RB For Heat Recovery only UNIT 7 5 HIGH STATIC PRESSURE DUCT TYPE 79 ...
Страница 80: ...MODELS AU7 AU9 AU12 AU14 AU18 RB UNIT For Heat Recovery only 7 6 COMPACT CASSETTE TYPE 80 ...
Страница 81: ...MODELS AU20 AU25 AU30 AU36 AU45 AU54 RB UNIT For Heat Recovery only 7 7 NEW CASSETTE TYPE 81 ...
Страница 82: ...MODELS 7 8 WALL MOUNTED TYPE AS14 20 24 30 82 ...
Страница 83: ...MODEL AOY90 7 9 OUTDOOR UNIT 83 ...
Страница 134: ...Models AOY90TPAMF 134 10 DISASSEMBLY ILLUSTRATION ...
Страница 135: ...Models AOY90TPAMF 135 ...
Страница 137: ...Models AOY90TPAMF 137 ...
Страница 142: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Страница 143: ...Models ABY12TFAMF ABY14TFAMF 416 8 1 417 385 868 771 488 472 443 473 ABY18TFAMF ABY24TFAMF 143 ...
Страница 149: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Страница 150: ...Models ABY12TFAMF ABY14TFAMF 416 8 1 417 385 868 771 488 472 443 473 ABY18TFAMF ABY24TFAMF 143 ...
Страница 155: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 407 876 1 505 408 435 434 506 3 ABY54TFAMF 148 ...
Страница 156: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 387 160 91 91 91 321 386 361 ABY54TFAMF 149 ...
Страница 157: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 63 876 2 385 868 763 227 321 387 436 424 684 438 ABY54TFAMF 150 ...
Страница 162: ...Models AUY20TFAMF AUY25TFAMF AUY30TFAMF AUY36TFAMF AUY45TFAMF AUY54TFAMF 155 ...
Страница 164: ...Models AUY25TLAMA AUY30TLAMA AUY36TLAMA AUY45TLAMA 157 ...
Страница 166: ...Models ARY25TLAMA ARY30TLAMA ARY36TLAMA ARY45TLAMA 57 56 109 67 338 164 67 57 56 126 109 234 143 138 108 159 ...
Страница 167: ...Models ARY25TFAMF ARY30TFAMF ARY36TFAMF ARY45TFAMF 160 ...
Страница 169: ... 162 Model ARY7TFAMF ARY9TFAMF ...
Страница 170: ...Model ARY7TFAMF ARY9TFAMF 163 875 ...
Страница 171: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 164 431 918 918 163 2 184 1 147 ...
Страница 172: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 165 ...
Страница 173: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 166 ...
Страница 175: ...422 126 477 109 477 477 109 164 422 10 75 45 117 3 338 1 338 2 56 2 477 56 1 Model ARY36TFAMF ARY45TFAMF ARY60TFAMF 168 ...
Страница 178: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 171 684 558 554 555 559 557 556 91 320 361 960 321 876 2 ...
Страница 179: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 172 91 876 1 407 1 407 2 407 3 69 ...
Страница 199: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jan 2002 Printed in Japan ...