5. Others
PCB LED
1 to 6
LCD
LED display
Remote
controller
Indoor
unit
Outdoor
unit
– 123–
Normal
display
Normal
display
Normal
display
Indoor unit electronic expansion
valve opening faulty.
When the indoor unit power is
reset 5~10 times at a 2~3
minutes interval, the expansion
valve may close.
Coil resistance (red-white,
red-orange, brown-blue,
brown-yellow) : 100~200
Indoor unit
other than
relevant indoor
unit does not
perform cooling.
Indoor unit
makes an
abnormal
sound.
Indoor unit electronic expansion
valve opening faulty.
Area (heat exchanger) near the
air diffuser is not cooled even
after several minutes have
elapsed after the relevant indoor
unit was stopped.
(Gas pipe is cold.)
When the electronic expansion
valve is open excessively, other
indoor units may not operate at
full capacity or a loud refrigerant
rushing sound may be generated.
Indoor unit
other than
relevant indoor
unit does not
perform cooling.
Indoor unit
makes an
abnormal sound.
Icing at indoor
unit heat
exchanger.
Indoor unit electronic expansion
valve opening faulty.
The area (heat exchanger) near
the air diffuser of the stopped
relevant indoor unit is cold.
(Gas pipe is cold.)
When the electronic expansion
valve opens, the stopped indoor
heat exchanger may ice and
water leakage or other trouble
may occur.
Indoor unit
other than
relevant indoor
unit does not
perform heating.
Relevant indoor
unit is making
an abnormal
sound.
Indoor unit electronic expansion
valve opening faulty.
When a relevant indoor unit or
another indoor unit performs the
heating operation, the indoor unit
discharge temperature does not
become high and the high
pressure becomes low.
When the electronic expansion
valve is open excessively, a loud
refrigerant rushing sound may be
generated.
Indoor unit electronic expansion
valve opening faulty.
Discharge
temperature is
high.
Up - down (left - right) swing
switching motor faulty.
Louver does not move even when
a voltage (DC12V) is applied to
the CN10 terminals (across 1-2)
at swing input.
For the left - right swing switching
motor, check the voltage across
the CN11 terminals (1-2).
Discharge
temperature is
high.
Liquid injection solenoid valve
(SV1) faulty.
When a voltage (AC220V) is
applied to CN7, the liquid
injection solenoid valve outlet
pipe is not cold.
When SV1 is faulty, the
discharge gas temperature may
rise and a discharge temperature
error may be generated.
Coil resistance : 1200~1500
High pressure gas bypass
solenoid valve (SV2) faulty.
When a voltage (AC220V) is
applied to CN8, the high
pressure gas bypass solenoid
outlet pipe is not warm.
When SV2 is faulty, the high
pressure may rise and a high
pressure error may be generated.
Coil resistance : 1200~1500
Compressor
error
Oil return solenoid valve (SV3,
SV4, SV5, SV6) faulty.
When a voltage (AC220V) is
applied to CN9, CN10, CN11,
and CN12, the outlet pipe of the
respective solenoid valve (SV3,
SV4, SV5, SV6) does not
become hot.
When SV3, SV4, SV5, and SV6
do not operate normally, the oil
may not return to the compressor
and compressor trouble may
occur.
High pressure
is high.
High pressure switch faulty.
There is a voltage difference
across terminals 1-2 of CN42
even though the high pressure
exceeds 3.0MPa.
Error display
(Outdoor
unit error)
Error display
(Discharge,
liquid pipe
pressure
sensor error)
Error display
(Outdoor
unit error)
High pressure
is high.
Pressure sensor (HP, MP) faulty.
Measure the pressure sensor
output voltage (across terminals
2-3 of CN33 and CN34) and
compare the result to the
pressure gauge indication.
When the pressure sensor is
faulty, protection control is not
entered even if the high pressure
rises and a high pressure error
may be generated.
Refer to the service manual
(section 8-5-2) for the pressure
and pressure sensor output
voltage relationship.
Remakes
Remakes
Remakes
Remakes
When the pressure switch is
faulty, protection control will not
be entered even if the high
pressure rises and a high
pressure error may be generated.
Coil resistance : 1200~1500
Remarks
Check method
(Error state check method)
Cause
Cooling operation.
Fully open (open excessively)
Symptom that
can occur other
than title
Body
LED
Fully open (open excessively)
Cooling stopped.
Fully open (open excessively)
Heating operation.
Fully open (open excessively)
Heating stopped.
Содержание AirStage AB12
Страница 2: ...Multi Air Conditioning System for Buildings VRF FREELY SELECTABLE MULTI TYPE SYSTEM SERVICE MANUAL 2 ...
Страница 76: ...MODELS AB30 AB36 AB45 AB54 RB UNIT For Heat Recovery only 7 2 LARGE CEILING TYPE 76 ...
Страница 77: ...MODELS AR7 AR9 AR12 AR14 AR18 RB UNIT For Heat Recovery only 7 3 COMPACT DUCT TYPE 77 ...
Страница 78: ...MODELS AR25 AR30 AR36 AR45 RB UNIT For Heat Recovery only 7 4 LOW STATIC PRESSURE DUCT TYPE 78 ...
Страница 79: ...MODELS AR36H AR45H AR60H RB For Heat Recovery only UNIT 7 5 HIGH STATIC PRESSURE DUCT TYPE 79 ...
Страница 80: ...MODELS AU7 AU9 AU12 AU14 AU18 RB UNIT For Heat Recovery only 7 6 COMPACT CASSETTE TYPE 80 ...
Страница 81: ...MODELS AU20 AU25 AU30 AU36 AU45 AU54 RB UNIT For Heat Recovery only 7 7 NEW CASSETTE TYPE 81 ...
Страница 82: ...MODELS 7 8 WALL MOUNTED TYPE AS14 20 24 30 82 ...
Страница 83: ...MODEL AOY90 7 9 OUTDOOR UNIT 83 ...
Страница 134: ...Models AOY90TPAMF 134 10 DISASSEMBLY ILLUSTRATION ...
Страница 135: ...Models AOY90TPAMF 135 ...
Страница 137: ...Models AOY90TPAMF 137 ...
Страница 142: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Страница 143: ...Models ABY12TFAMF ABY14TFAMF 416 8 1 417 385 868 771 488 472 443 473 ABY18TFAMF ABY24TFAMF 143 ...
Страница 149: ...Models ABY12TFAMF ABY14TFAMF 755 653 1 581 338 67 56 56 164 109 126 ABY18TFAMF ABY24TFAMF 142 ...
Страница 150: ...Models ABY12TFAMF ABY14TFAMF 416 8 1 417 385 868 771 488 472 443 473 ABY18TFAMF ABY24TFAMF 143 ...
Страница 155: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 407 876 1 505 408 435 434 506 3 ABY54TFAMF 148 ...
Страница 156: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 387 160 91 91 91 321 386 361 ABY54TFAMF 149 ...
Страница 157: ...Models ABY30TFAMF ABY36TFAMF ABY45TFAMF 63 876 2 385 868 763 227 321 387 436 424 684 438 ABY54TFAMF 150 ...
Страница 162: ...Models AUY20TFAMF AUY25TFAMF AUY30TFAMF AUY36TFAMF AUY45TFAMF AUY54TFAMF 155 ...
Страница 164: ...Models AUY25TLAMA AUY30TLAMA AUY36TLAMA AUY45TLAMA 157 ...
Страница 166: ...Models ARY25TLAMA ARY30TLAMA ARY36TLAMA ARY45TLAMA 57 56 109 67 338 164 67 57 56 126 109 234 143 138 108 159 ...
Страница 167: ...Models ARY25TFAMF ARY30TFAMF ARY36TFAMF ARY45TFAMF 160 ...
Страница 169: ... 162 Model ARY7TFAMF ARY9TFAMF ...
Страница 170: ...Model ARY7TFAMF ARY9TFAMF 163 875 ...
Страница 171: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 164 431 918 918 163 2 184 1 147 ...
Страница 172: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 165 ...
Страница 173: ...Model ARY12TFAMF ARY14TFAMF ARY18TFAMF 166 ...
Страница 175: ...422 126 477 109 477 477 109 164 422 10 75 45 117 3 338 1 338 2 56 2 477 56 1 Model ARY36TFAMF ARY45TFAMF ARY60TFAMF 168 ...
Страница 178: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 171 684 558 554 555 559 557 556 91 320 361 960 321 876 2 ...
Страница 179: ...Model ASY20TFAMF ASY24TFAMF ARY30TFAMF 172 91 876 1 407 1 407 2 407 3 69 ...
Страница 199: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Jan 2002 Printed in Japan ...