En-8

ELECTRICAL WIRING

21 

The precautions of electrical wiring

21 11 

 WARNING

Wiring connections must be performed by a qualified person in accordance with 

specifications.

The rated supply of this product is 60Hz, 208/230V. Use a voltage within the range of 

187-253V.
Before connecting the wires, make sure the power supply is OFF.
When installing this system in high humidity locations, install using ground fault 

equipment breakers (often referred to in other countries as an ELCB earth leakage 

current breaker) to reduce the risk of leaking current which may result in electric shock 

or potential fire.
Be sure to install a breaker of the specified capacity. 

When selecting breaker, please comply with the laws and the regulations of each 

country. 

One breaker must be installed on the power supply of the outdoor unit.

Wrong selection and setup of the breaker will cause electric shock or fire.
Do not connect AC power supply to the transmission line terminal board.

Improper wiring can damage the entire system.

Connect the connector cord securely to the terminal.

Faulty installation can cause a fire.
Make sure to secure the insulation portion of the connector cable with the cord clamp. 

A damaged insulation can cause a short circuit.
Never install a power factor improvement condenser. Instead of improving the power 

factor, the condenser may overheat.
Before servicing the unit, turn the power supply switch OFF. Then, do not touch 

electric parts for 10 minutes due to the risk of electric shock.
Make sure to perform grounding work. Improper grounding work can cause electric 

shocks.

 CAUTION

The primary power supply capacity is for the air conditioner itself, and does not include 

the concurrent use of other devices.

Do not use crossover power supply wiring for the outdoor unit.

If the electrical power is inadequate, contact your electric power company.

Install a breaker in a location that is not exposed to high temperatures.

If the temperature surrounding the breaker is too high, the amperage at which the 

breaker cuts out may decrease.
We suggest installing GFEB breakers or follow local electrical code.

This system uses an inverter, which means that when used with a ground fault breaker 

you must use breakers that can handle harmonics such as a (GFEB) Ground Fault 

Equipment Breaker (30 mA or greater) in order to prevent malfunctioning of ground 

fault device.

When the electrical switchboard is installed outdoors, place it under lock and key so 

that it is not easily accessible.

Do not fasten the power supply cable and connection cable together.
Always keep to the maximum length of the connection cable. Exceeding the maximum 

length may lead to erroneous operation.

The static electricity that is charged to the human body can damage the control PC 

Board when handling the control PC Board for address setting, etc.

Please keep caution to the following points.

Provide the grounding of Indoor unit, Outdoor unit and Option equipment.

Cut off the power supply (breaker).

Touch the metal section (such as the unpainted control box section) of the indoor or 

outdoor unit for more than 10 seconds. Discharge the static electricity in your body.

Never touch the component terminal or pattern on the PC Board.

Electrical requirement

21 21 

 CAUTION

Be sure to install a breaker of the specified capacity.

Regulation of cables and breaker differs from each locality, refer in accordance with 

local rules.

Voltage rating

1Φ 208/230V (60Hz)

Operating range

187-264V

Cable

Cable size

 *

1)

Remarks

Power supply cable

10AWG

2 cable + Ground, 1 Ø 208/230V

Connection cable

14AWG

3 cable + Ground, 1 Ø 208/230V

1)  Selected sample: Select the correct cable type and size according to the country or 

region’s regulations.

 

Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the 

wire diameter when the wire length is long.

Breaker

Specification

 *

2)

Circuit breaker (MOCP) *

4)

Current : 25 (A)

Earth leakage breaker

Leakage current : 30mA 0.1sec or less *

3)

2) Select the appropriate breaker of the described specification according to the national 

or regional standards.

3) Select the breaker that enough load current can pass through it.
4) MOCP: Maximum Over Current Protection

Unit wiring

21 21 

When stripping off the coating of a lead wire, always use a special tool such as a wire 

 

stripper. If there is no special tool available, carefully strip the coating with a knife etc.

Power supply cable

and connection cable

30 mm (1-3/16 in.

)

50 mm (2 in.) or more

Earth wire

How to connect wiring to the terminal

Caution when wiring cable

(1)  Use crimp-type terminals with insulating sleeves as shown in the figure to connect 

to the terminal block.

(2)  Securely clamp the crimp-type terminals to the wires using an appropriate tool so 

that the wires do not come loose.

(3)  Use the specified wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 

prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table below for the terminal screw tightening torques.

Sleeve

Strip : 10mm (13/32 in.)

Crimp-type terminal

Wire

Screw with special washer

Crimp-type terminal

Terminal blocks

Screw with special washer 

Wire

Crimp-type 

terminal

Tightening torque [N·m (lbf·in1)]

M4 screw

1.2 to 1.8 (10.6 to 15.9)

9374747122_IM_En.indd   8

20/12/2553   13:09:11

Содержание AIR CONDITIONER

Страница 1: ...TIONER OUTDOOR UNIT PART NO 9374747122 INSTALLATION MANUAL For authorized personnel only MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado 9374747122_IM_En indd 1 20 12 2553 13 09 04 ...

Страница 2: ...ly refrigeration compressor oil or equivalent used for the outdoor unit to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run NOTE Depending on the system type liquid and gas lines may be either narrow or wide Therefore to avoid confusion the refrigeran...

Страница 3: ... water etc does not enter the piping than with refrigerant models Also when storing the piping securely seal the openings by pinching taping etc When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Special tools for R410A 222222 Tool name Contents of change Gauge ma...

Страница 4: ...capacity type 222222222 CAUTION The total capacity of the indoor units connected must be between 14 000 and 27 000 BTU Connection patterns are restricted Normal operation is not guaranteed if connected pattern in the combination not listed below The product may be damaged Surely connect in accordance with the combination in the following connection pattern To install an indoor unit refer to the in...

Страница 5: ...ng is neces sary For more information refer to 6 2 Additional charging Selecting pipe sizes 222222222 The diameters of the connection pipes differ according to the capacity of the indoor unit Refer to the following table for the proper diameters of the connection pipes between the indoor and outdoor units Capacity of indoor unit Gas pipe size thickness mm in Liquid pipe size thickness mm in 7 12 ø...

Страница 6: ...topple or fall or other accidents Do not install the outdoor unit near the edge of a balcony Otherwise children may climb onto the outdoor unit and fall off of the balcony CAUTION Do not install the outdoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil o...

Страница 7: ...pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commercially available M10 bolts nuts and washers The bolts should protrude 20 mm 0 78 in Refer to the figure If overturning prevention is required purchase the necessary commercially available items Unit mm in 650 25 19 32 370 14 9 16 Bottom side 4 ø12 1 15 32 hole Fix securely with bolts on a solid block Use 4 sets of co...

Страница 8: ...er and flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that the cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result i...

Страница 9: ...ngth may lead to erroneous operation The static electricity that is charged to the human body can damage the control PC Board when handling the control PC Board for address setting etc Please keep caution to the following points Provide the grounding of Indoor unit Outdoor unit and Option equipment Cut off the power supply breaker Touch the metal section such as the unpainted control box section o...

Страница 10: ... UNIT A DISCONNECT SWITCH FIELD SUPPLY DISCONNECT SWITCH FIELD SUPPLY WARNING Disconnect switch and for over current protection given in the table below is to be installed between the indoor unit and the outdoor unit Disconnect switch 15A CAUTION Be sure to refer the above diagram and do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical codes and also any spec...

Страница 11: ...ps and charging port cap of the 2 way valve and 3 way valve to the specified torque Checking gas leaks with nitrogen gas Check if the piping connections are secure Remove the cap of 3 way valve and connect the gauge manifold charge hoses to the charging port of the 3 way valve Pressurize with nitrogen gas using the 3 way valve charging port Do not pressurize up to the specified pressure all at onc...

Страница 12: ...ng the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Gas Liquid R410A Add refrigerant from the charging valve after the completion of the work If the units are further apart than the maximum pipe length correct operation cannot be guaranteed POWER 777 WARNING The rated voltage...

Страница 13: ...D2 LED1 Hole LED is on a reverse side of the board Confirming the operation of indoor unit 888888 Run the unit in a normal way and confirm its operation Please end the test run first before confirmation 1 Cold air or warm air must be discharged from the indoor unit 2 The indoor unit operates normally when air direction or air volume adjustment buttons pressed PUMP DOWN 999 PUMP DOWN OPERATION To a...

Страница 14: ...9374747122_IM_Es indd 13 20 12 2553 13 13 45 ...

Страница 15: ...9374747122_IM_Es indd 14 20 12 2553 13 13 45 ...

Страница 16: ...9374747122_IM_Es indd 15 20 12 2553 13 13 45 ...

Отзывы: