TEST RUN

81 

The test run method may be different for each indoor unit that is connected. Refer to the 

installation instruction sheet included with each indoor unit.

 CAUTION

Always turn on the power 12 hours prior to the start of the operation in order to ensure 

compressor protection.

 Make a test run in accordance with the installation Manual  

81 11 

for the indoor unit

(1) Indoor unit

1

 Is operation of each button on the remote control unit normal?

2

 Does each lamp light normally?

3

 Do the air flow-direction louver operate normally?

4

 Is the drain normal?

5

 Is there any abnormal noise and vibration during operation?

(2) Outdoor unit

1

 Is there any abnormal noise and vibration during operation?

2

 Will noise, wind, or drain water from the unit disturb the neighbors?

3

 Is there any gas leakage?

• Do not operate the air conditioner in the test running state for a long time.

• For the operation method, refer to the operating manual and perform operation check.

Outdoor unit LED

81 21 

When a malfunction occurs in the outdoor unit, the LED on the circuit board lights to 

indicate the error. Refer to the following table for the description of each error according to 

the LED.

Error contents

LED1

LED2

LED2

Serial Communication error (Outdoor unit 

to Indoor unit A)

● 1 time

Serial Communication error (Outdoor unit 

to Indoor unit B)

● 1 time

Serial Communication error (Outdoor unit 

to Indoor unit C)

*1

● 1 time

Discharge temp. sensor error

● 2 times

Outdoor unit Heat Ex. middle temp. 

sensor error

● 3 times

Outdoor temp. sensor error

● 4 times

2-way valve temp. sensor error 

 

(for Indoor unit A)

● 5 times

2-way valve temp. sensor error 

 

(for Indoor unit B)

● 5 times

2-way valve temp. sensor error 

 

(for Indoor unit C)

*1

● 5 times

3-way valve temp. sensor error 

 

(for Indoor unit A)

● 6 times

3-way valve temp. sensor error 

 

(for Indoor unit B)

● 6 times

3-way valve temp. sensor error 

 

(for Indoor unit C)

*1

● 6 times

Compressor temp. sensor error

● 7 times

Heat sink temp. sensor error

● 8 times

High pressure switch 1 error

● 9 times

High pressure switch 2 error

● 10 times

Indoor unit capacity error

● 11 times

Trip detection

● 12 times

Compressor rotor position detection error ● 13 times

Trip terminal L error

● 14 times

Outdoor unit fan motor error

● 15 times

Outdoor unit PCB microcomputer 

communication error

● 17 times

Discharge temperature error

● 18 times

Compressor temperature error

● 19 times

4-way valve error

● 20 times

Outdoor unit PCB model information 

error

● 21 times

Active filter error, PFC circuit error

● 22 times

● : flashing         – : Off

*1: 24 type only

LED4

LED3

LED2

LED1

Hole

LED is on a reverse

side of the board.    

Confirming the operation of indoor unit

81 21 

Run the unit in a normal way, and confirm its operation. (Please end the test run first 

before confirmation)

(1) Cold air (or warm air) must be discharged from the indoor unit.

(2) The indoor unit operates normally when air direction or air volume adjustment buttons 

pressed.

PUMP DOWN

91 

PUMP DOWN OPERATION

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, 

recover refrigerant by doing the cooling operation or forced cooling operation according 

to the following procedure. (When the cooling operation cannot start in winter, and so on, 

start the forced cooling operation.)

(1) Do the air purging of the charge hose by connecting the charging hose of gauge 

manifold to the charging port of 3 way valve (At lease one unit of connected units) and 

opening the low pressure valve slightly.

(2) Close the valve stem of 2 way valve (All connected units) completely.

(3) Start the cooling operation or following forced cooling operation. (All connected 

units) When using the remote control unit Press the TEST RUN button after starting 

the cooling operation by the remote control unit. The operation indicator lamp and 

timer indicator lamp will begin to flash simultaneously during test run. When using 

the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so 

on.) Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 

seconds. (The forced cooling operation cannot start if the MANUAL AUTO button is not 

kept on pressing for more than 10 seconds.)

(4) Close the valve stem of 3 way valve (All connected units) when the reading on the 

compound pressure gauge becomes 0.05

0 MPa (7.3

0 psi).

(5) Stop the operation. (All connected units) Press the START/STOP button of the remote 

control unit to stop the operation. Press the MANUAL AUTO button when stopping the 

operation from indoor unit side. (It is not necessary to press on keeping for more than 

10 seconds.)

 CAUTION

During the pump-down operation, make sure that compressor is off before you remove 

the refrigerant piping. Do not remove the connection pipe while the compressor is 

in operation with 2 or 3 way valve open. This may cause abnormal pressure in the 

refrigeration cycle that breakage and injury.

CUSTOMER GUIDANCE

101 

Explain the following to the customer in accordance with the operating manual:

(1) Starting and stopping method, operation switching, temperature adjustment, timer, air 

flow adjustment, and other remote control unit operations.

(2) Air filter removal and cleaning.

(3) Give the operating manual and installation instruction sheet to the customer.

9374747122_IM_En.indd   12

20/12/2553   13:09:15

Содержание AIR CONDITIONER

Страница 1: ...TIONER OUTDOOR UNIT PART NO 9374747122 INSTALLATION MANUAL For authorized personnel only MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado 9374747122_IM_En indd 1 20 12 2553 13 09 04 ...

Страница 2: ...ly refrigeration compressor oil or equivalent used for the outdoor unit to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run NOTE Depending on the system type liquid and gas lines may be either narrow or wide Therefore to avoid confusion the refrigeran...

Страница 3: ... water etc does not enter the piping than with refrigerant models Also when storing the piping securely seal the openings by pinching taping etc When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Special tools for R410A 222222 Tool name Contents of change Gauge ma...

Страница 4: ...capacity type 222222222 CAUTION The total capacity of the indoor units connected must be between 14 000 and 27 000 BTU Connection patterns are restricted Normal operation is not guaranteed if connected pattern in the combination not listed below The product may be damaged Surely connect in accordance with the combination in the following connection pattern To install an indoor unit refer to the in...

Страница 5: ...ng is neces sary For more information refer to 6 2 Additional charging Selecting pipe sizes 222222222 The diameters of the connection pipes differ according to the capacity of the indoor unit Refer to the following table for the proper diameters of the connection pipes between the indoor and outdoor units Capacity of indoor unit Gas pipe size thickness mm in Liquid pipe size thickness mm in 7 12 ø...

Страница 6: ...topple or fall or other accidents Do not install the outdoor unit near the edge of a balcony Otherwise children may climb onto the outdoor unit and fall off of the balcony CAUTION Do not install the outdoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil o...

Страница 7: ...pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commercially available M10 bolts nuts and washers The bolts should protrude 20 mm 0 78 in Refer to the figure If overturning prevention is required purchase the necessary commercially available items Unit mm in 650 25 19 32 370 14 9 16 Bottom side 4 ø12 1 15 32 hole Fix securely with bolts on a solid block Use 4 sets of co...

Страница 8: ...er and flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that the cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result i...

Страница 9: ...ngth may lead to erroneous operation The static electricity that is charged to the human body can damage the control PC Board when handling the control PC Board for address setting etc Please keep caution to the following points Provide the grounding of Indoor unit Outdoor unit and Option equipment Cut off the power supply breaker Touch the metal section such as the unpainted control box section o...

Страница 10: ... UNIT A DISCONNECT SWITCH FIELD SUPPLY DISCONNECT SWITCH FIELD SUPPLY WARNING Disconnect switch and for over current protection given in the table below is to be installed between the indoor unit and the outdoor unit Disconnect switch 15A CAUTION Be sure to refer the above diagram and do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical codes and also any spec...

Страница 11: ...ps and charging port cap of the 2 way valve and 3 way valve to the specified torque Checking gas leaks with nitrogen gas Check if the piping connections are secure Remove the cap of 3 way valve and connect the gauge manifold charge hoses to the charging port of the 3 way valve Pressurize with nitrogen gas using the 3 way valve charging port Do not pressurize up to the specified pressure all at onc...

Страница 12: ...ng the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Gas Liquid R410A Add refrigerant from the charging valve after the completion of the work If the units are further apart than the maximum pipe length correct operation cannot be guaranteed POWER 777 WARNING The rated voltage...

Страница 13: ...D2 LED1 Hole LED is on a reverse side of the board Confirming the operation of indoor unit 888888 Run the unit in a normal way and confirm its operation Please end the test run first before confirmation 1 Cold air or warm air must be discharged from the indoor unit 2 The indoor unit operates normally when air direction or air volume adjustment buttons pressed PUMP DOWN 999 PUMP DOWN OPERATION To a...

Страница 14: ...9374747122_IM_Es indd 13 20 12 2553 13 13 45 ...

Страница 15: ...9374747122_IM_Es indd 14 20 12 2553 13 13 45 ...

Страница 16: ...9374747122_IM_Es indd 15 20 12 2553 13 13 45 ...

Отзывы: