En-2

(1)   Detach the caps and plugs from the pipes. 
(2)   Center the pipe against the port on the outdoor unit, and then turn the flare nut 

by hand.

To prevent gas leakage, coat the flare 
surface with alkylbenzene oil (HAB).
Do not use mineral oil.

(3)   Attach the connection pipe.

Flare nut

Connection pipe

(Liquid)

Connection pipe

(Gas)

Flare nut

3-way valve (Gas) 

2-way valve

(Liquid) 

(4)   When the flare nut is tightened properly by your hand, use a torque wrench to 

finally tighten it.

Torque wrench

Holding spanner

Body side

 CAUTION

Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order to 

tighten the flare nut correctly.

Outer panel may be distorted if fastened only with a wrench. Be sure to fix the 

 

elementary part with a holding wrench (spanner) and fasten with a torque wrench 

(refer to below diagram). Do not apply force to the blank cap of the valve or hang a 

wrench, etc., on the cap. If blank cap is broken, it may cause leakage of refrigerant.

Flare nut [mm (in1)]

Tightening torque [N·m (lbf·in1)]

6.35 (1/4) dia.

16 to 18 (142 to 159)

9.52 (3/8) dia.

32 to 42 (283 to 372)

12.70 (1/2) dia.

49 to 61 (434 to 540)

15.88 (5/8) dia.

63 to 75 (558 to 664)

19.05 (3/4) dia.

90 to 110 (797 to 974)

How to use adapter (connection ports of outdoor unit)

41 11 21 

When using the ADAPTER, be careful not to overtighten the nut, or the smaller pipe 

 

may be damaged.

Apply a coat of refrigeration oil to the threaded connection port of the outdoor unit 

 

where the flare nut comes in.

Use appropriate wrenches to avoid damaging the connection thread by 

 

overtightening the flare nut.
Apply wrenches on both of flare nut (local part), and ADAPTER to tighten them.

 

Adapter tightening torque

Adapter type [mm (in1)]

Tightening torque [N·m (lbf·in1)]

ø12.7 (1/2) → ø9.52 (3/8)

49 to 61 (434 to 540)

PIPE INSTALLATION - 1

41 

Flare connection (pipe connection)

41 11 

 CAUTION

Do not use mineral oil on a flared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

While welding the pipes, be sure to blow dry nitrogen gas through them.

The maximum lengths of this product are shown in the table. If the units are further 

apart than this, correct operation cannot be guaranteed.

Flaring

Use special pipe cutter and flare tool exclusive for R410A.

 

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that the cuttings will not enter the pipe and remove 

any burrs.

(3)  Insert the flare nut (always use the flare nut attached to the indoor and outdoor 

units respectively) onto the pipe and perform the flare processing with a flare tool. 

Leakage of refrigerant may result if other flare nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

L

Check if [L] is flared uniformly 

and is not cracked or scratched.

Pipe

A

B

Die

Pipe outside  

diameter [mm (in1)]

Dimension A  [mm (in1)]

Dimension B

  

0

-  014

 [mm (in1)]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5

(0 to 1/32)

9.1 (3/8)

9.52 (3/8)

13.2 (17/32)

12.70 (1/2)

16.6 (21/32)

15.88 (5/8)

19.7 (25/32)

19.05 (3/4)

24.0 (15/16)

When using conventional flare tools to flare R410A pipes, the dimension A should 

 

be approximately 1/32 in. more than indicated in the table (for flaring with R410A 

flare tools) to achieve the specified flaring. Use a thickness gauge to measure the 

dimension A.

Pipe outside  

diameter  

[mm (in1)]

Width across flats

of Flare nut  

[mm (in1)]

6.35 (1/4)

17 (11/16)

9.52 (3/8)

22 (7/8)

12.70 (1/2)

26 (1-1/32)

15.88 (5/8)

29 (1-5/32)

19.05 (3/4)

36 (1-13/32)

Width across flats

Bending pipes

41 11 11 

 CAUTION

To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of 

curvature of 100mm (4 in.) or more.
If the pipe is bent repeatedly at the same place, it will break.

If pipes are shaped by hand, be careful not to collapse them.

 

Do not bend the pipes at an angle of more than 90°.

 

When pipes are repeatedly bent or stretched, the material will harden, making it 

 

difficult to bend or stretch them any more.
Do not bend or stretch the pipes more than 3 times.

 

Pipe connection

41 11 21 

 CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit 

correctly. If the centering is improper, the flare nut cannot be tightened smoothly. 

 

If the flare nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the outdoor unit pipe until immediately before 

connecting the connection pipe.

After installing the piping, make sure that the connection pipes do not touch the 

compressor or outer panel. If the pipes touch the compressor or outer panel, they will 

vibrate and produce noise.

9374747122_IM_En.indd   7

20/12/2553   13:09:10

Содержание AIR CONDITIONER

Страница 1: ...TIONER OUTDOOR UNIT PART NO 9374747122 INSTALLATION MANUAL For authorized personnel only MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado 9374747122_IM_En indd 1 20 12 2553 13 09 04 ...

Страница 2: ...ly refrigeration compressor oil or equivalent used for the outdoor unit to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run NOTE Depending on the system type liquid and gas lines may be either narrow or wide Therefore to avoid confusion the refrigeran...

Страница 3: ... water etc does not enter the piping than with refrigerant models Also when storing the piping securely seal the openings by pinching taping etc When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Special tools for R410A 222222 Tool name Contents of change Gauge ma...

Страница 4: ...capacity type 222222222 CAUTION The total capacity of the indoor units connected must be between 14 000 and 27 000 BTU Connection patterns are restricted Normal operation is not guaranteed if connected pattern in the combination not listed below The product may be damaged Surely connect in accordance with the combination in the following connection pattern To install an indoor unit refer to the in...

Страница 5: ...ng is neces sary For more information refer to 6 2 Additional charging Selecting pipe sizes 222222222 The diameters of the connection pipes differ according to the capacity of the indoor unit Refer to the following table for the proper diameters of the connection pipes between the indoor and outdoor units Capacity of indoor unit Gas pipe size thickness mm in Liquid pipe size thickness mm in 7 12 ø...

Страница 6: ...topple or fall or other accidents Do not install the outdoor unit near the edge of a balcony Otherwise children may climb onto the outdoor unit and fall off of the balcony CAUTION Do not install the outdoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil o...

Страница 7: ...pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commercially available M10 bolts nuts and washers The bolts should protrude 20 mm 0 78 in Refer to the figure If overturning prevention is required purchase the necessary commercially available items Unit mm in 650 25 19 32 370 14 9 16 Bottom side 4 ø12 1 15 32 hole Fix securely with bolts on a solid block Use 4 sets of co...

Страница 8: ...er and flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that the cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result i...

Страница 9: ...ngth may lead to erroneous operation The static electricity that is charged to the human body can damage the control PC Board when handling the control PC Board for address setting etc Please keep caution to the following points Provide the grounding of Indoor unit Outdoor unit and Option equipment Cut off the power supply breaker Touch the metal section such as the unpainted control box section o...

Страница 10: ... UNIT A DISCONNECT SWITCH FIELD SUPPLY DISCONNECT SWITCH FIELD SUPPLY WARNING Disconnect switch and for over current protection given in the table below is to be installed between the indoor unit and the outdoor unit Disconnect switch 15A CAUTION Be sure to refer the above diagram and do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical codes and also any spec...

Страница 11: ...ps and charging port cap of the 2 way valve and 3 way valve to the specified torque Checking gas leaks with nitrogen gas Check if the piping connections are secure Remove the cap of 3 way valve and connect the gauge manifold charge hoses to the charging port of the 3 way valve Pressurize with nitrogen gas using the 3 way valve charging port Do not pressurize up to the specified pressure all at onc...

Страница 12: ...ng the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Gas Liquid R410A Add refrigerant from the charging valve after the completion of the work If the units are further apart than the maximum pipe length correct operation cannot be guaranteed POWER 777 WARNING The rated voltage...

Страница 13: ...D2 LED1 Hole LED is on a reverse side of the board Confirming the operation of indoor unit 888888 Run the unit in a normal way and confirm its operation Please end the test run first before confirmation 1 Cold air or warm air must be discharged from the indoor unit 2 The indoor unit operates normally when air direction or air volume adjustment buttons pressed PUMP DOWN 999 PUMP DOWN OPERATION To a...

Страница 14: ...9374747122_IM_Es indd 13 20 12 2553 13 13 45 ...

Страница 15: ...9374747122_IM_Es indd 14 20 12 2553 13 13 45 ...

Страница 16: ...9374747122_IM_Es indd 15 20 12 2553 13 13 45 ...

Отзывы: