1. Error code
1-1. Error code table (Indoor unit and wired remote controller)
The operation, timer, and economy indicators operate according to the error contents.
For confirmation of the error contents, refer the flashing pattern as follows.
Error contents
Indoor unit display
Wired
remote
controller
display
Operation [ ]
(Green)
Timer [ ]
(Orange)
Economy [ ]
(Green)
E: 11. Serial communication error (Serial
reverse transfer error) (Outdoor unit)
1 times
1 times
Continuous
11
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
1 times
1 times
Continuous
11
E: 12. Wired remote controller
communication error (Indoor unit)
1 times
2 times
Continuous
12
E: 32. Indoor unit main PCB error (Indoor
unit)
3 times
2 times
Continuous
32
E: 35. MANUAL AUTO button error (Indoor
unit)
3 times
5 times
Continuous
35
E: 41. Room temperature sensor error
(Indoor unit)
4 times
1 times
Continuous
41
E: 42. Indoor unit heat exchanger sensor
error (Indoor unit)
4 times
2 times
Continuous
42
E: 45. Refrigerant leakage sensor error
(Indoor unit)
4 times
5 times
Continuous
45
E: 45. Refrigerant leakage sensor
deterioration (Indoor unit)
4 times
5 times
Continuous
45
E: 51. Indoor unit fan motor error (Indoor
unit)
5 times
1 times
Continuous
51
E: 57. Damper (Open/Close) detection limit
switch error
5 times
7 times
Continuous
57
E: 57. Damper error (Damper(Open/Close)
simultaneous detection limit switch error)
(Indoor unit)
5 times
7 times
Continuous
57
E: 62. Outdoor unit main PCB error
(Outdoor unit)
6 times
2 times
Continuous
62
E: 71. Discharge thermistor error (Outdoor
unit)
7 times
1 times
Continuous
71
E: 73. Outdoor unit heat exchanger
thermistor error (Outdoor unit)
7 times
3 times
Continuous
73
E: 74. Outdoor temperature thermistor error
(Outdoor unit)
7 times
4 times
Continuous
74
E: 84. Current sensor error (Outdoor unit)
8 times
4 times
Continuous
84
E: 94. Trip detection (Outdoor unit)
9 times
4 times
Continuous
94
E: 95. Compressor motor control error
(Outdoor unit)
9 times
5 times
Continuous
95
E: 97. Outdoor unit fan motor error
(Outdoor unit)
9 times
7 times
Continuous
97
E: 99. 4-way valve error (Outdoor unit)
9 times
9 times
Continuous
99
E: A1. Discharge temperature error
(Outdoor unit)
10 times
1 times
Continuous
A1
E: A8. Refrigerant leakage sensor error
(Indoor unit)
10 times
8 times
Continuous
A8
1-1. Error code table (Indoor unit and wired remote controller)
- (03-1) -
1. Error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AGYG09KVCB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 10 05 SR_CH01_AG002EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 25 SR_CH02_AG002EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 11 11 SR_CH03_AG002EF_01 ...
Страница 39: ...5 1 Indoor unit 03 44 5 2 Outdoor unit 03 45 CONTENTS continued ...
Страница 40: ......
Страница 87: ...4 CONTROL AND FUNCTIONS 2020 11 11 SR_CH04_AG002EF_01 ...
Страница 121: ...5 FILED WORKING 2020 11 11 SR_CH05_AG002EF_01 ...