2-18. E: 94. Trip detection (Outdoor unit)
Indicator
Indoor unit
Operation indicator
9 time flash
Timer indicator
4 time flash
Economy indicator
Continuous flash
Error code
E: 94
Detective actuator
Outdoor unit
Main PCB
Protection stop by over-current generation after inverter
compressor start processing completed generated
consecutively 10 times.
NOTE:
The number of generations is reset when the
compressor starts up.
Compressor
Forecast of cause
Outdoor unit fan operation defective, foreign matter on
heat-exchanger, excessive rise of ambient temperature
Main PCB failure
Inverter compressor failure (lock, winding short)
Check point 1. Check the outdoor unit fan operation, heat-exchanger, ambient temperature
•
No obstructions in air passages?
•
Heat exchange fins clogged
•
Outdoor unit fan motor check
•
Ambient temperature not raised by the effect of other heat sources?
•
Discharged air not sucked in?
↓
Check point 2. Replace main PCB
If Check point 1 do not improve the symptom, change main PCB.
↓
Check point 3. Replace compressor
If Check point 2 do not improve the symptom, change compressor.
↓
End
2-18. E: 94. Trip detection (Outdoor unit)
- (03-21) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AGYG09KVCB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 10 05 SR_CH01_AG002EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 25 SR_CH02_AG002EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 11 11 SR_CH03_AG002EF_01 ...
Страница 39: ...5 1 Indoor unit 03 44 5 2 Outdoor unit 03 45 CONTENTS continued ...
Страница 40: ......
Страница 87: ...4 CONTROL AND FUNCTIONS 2020 11 11 SR_CH04_AG002EF_01 ...
Страница 121: ...5 FILED WORKING 2020 11 11 SR_CH05_AG002EF_01 ...