8) Cold air prevention
This setting is to disable the cold air prevention function during heating operation. When disabled,
the fan setting will always follow the setting on the remote controller. (Excluding defrost mode)
Function number
Setting value
Setting description
Factory setting
43
00
Enable
♦
01
Disable
9) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number
Setting value
Setting description
Factory setting
44
00
A
♦
01
B
02
C
03
D
10) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number
Setting value
Setting description
Factory setting
46
00
Operation/Stop mode
♦
01
(Setting prohibited)
02
Forced stop mode
11) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number
Setting value
Setting description
Factory setting
49
00
Disable
01
Enable
02
Remote controller
♦
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially invalidated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for ener-
gy saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each remote
controller.
1-1. Function settings by using remote controller
- (05-5) -
1. Function settings
FIELD
WORKING
FIELD
WORKING
Содержание AGYG09KVCB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 10 05 SR_CH01_AG002EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 25 SR_CH02_AG002EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 11 11 SR_CH03_AG002EF_01 ...
Страница 39: ...5 1 Indoor unit 03 44 5 2 Outdoor unit 03 45 CONTENTS continued ...
Страница 40: ......
Страница 87: ...4 CONTROL AND FUNCTIONS 2020 11 11 SR_CH04_AG002EF_01 ...
Страница 121: ...5 FILED WORKING 2020 11 11 SR_CH05_AG002EF_01 ...