1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation fre-
quency of compressor.
• If the room temperature is 6.0 °C lower than a set temperature, the compressor operation frequen-
cy will attain to maximum performance.
• If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
compressor frequency is controlled within the range shown below.
•
Compressor frequency range
Model name
Minimum frequency
Maximum frequency
AGYG09KVCB
8
120
AGYG12KVCB
AGYG14KVCB
10
130
•
Limit of maximum speed based on outdoor temperature
In heating operation, maximum frequency is defined by outdoor temperature and fan mode.
A zone
12°C
B zone
14°C
C zone
-10°C
-12°C
Outdoor
temperature rises
Outdoor
temperature drops
Unit: rps
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
AGYG09KVCB
A zone
120
74
68
68
B zone
120
74
63
39
C zone
120
74
63
26
AGYG12KVCB
AGYG14KVCB
A zone
130
130
74
74
B zone
130
94
68
42
C zone
130
94
68
28
1-2. Heating operation
- (04-3) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AGYG09KVCB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 10 05 SR_CH01_AG002EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 25 SR_CH02_AG002EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 11 11 SR_CH03_AG002EF_01 ...
Страница 39: ...5 1 Indoor unit 03 44 5 2 Outdoor unit 03 45 CONTENTS continued ...
Страница 40: ......
Страница 87: ...4 CONTROL AND FUNCTIONS 2020 11 11 SR_CH04_AG002EF_01 ...
Страница 121: ...5 FILED WORKING 2020 11 11 SR_CH05_AG002EF_01 ...