2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
Setting value
Setting description
Factory setting
11
00
Standard (400 hours)
01
Long interval (1,000 hours)
02
Short interval (200 hours)
03
No indication
♦
3) Vertical airflow direction range control
In a concealed installation, change the setting to "Fixed" (02) to restrict the movement of the upper
air outlet so that the airflow is only towards the horizontal direction.
Function number
Setting value
Setting description
Factory setting
23
00
Standard
♦
01
(Setting prohibited)
02
Fixed (Concealed)
4) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of the room temp. sensor - Correction temp. value
Example of correction:
When the temperature of the room temp. sensor is 26°C and the setting value is “03”
(-1.0°C), corrected temp. will be 27°C (26°C - [-1.0°C]).
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Function number
Setting value
Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00
Standard setting
♦
01
No correction 0.0 °C
02
-0.5 °C
More cooling
Less heating
03
-1.0 °C
04
-1.5 °C
05
-2.0 °C
06
-2.5 °C
07
-3.0 °C
08
-3.5 °C
09
-4.0 °C
10
+0.5 °C
Less cooling
More heating
11
+1.0 °C
12
+1.5 °C
13
+2.0 °C
14
+2.5 °C
15
+3.0 °C
16
+3.5 °C
17
+4.0 °C
1-1. Function settings by using remote controller
- (05-3) -
1. Function settings
FIELD
WORKING
FIELD
WORKING
Содержание AGYG09KVCB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 10 05 SR_CH01_AG002EF_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 25 SR_CH02_AG002EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 11 11 SR_CH03_AG002EF_01 ...
Страница 39: ...5 1 Indoor unit 03 44 5 2 Outdoor unit 03 45 CONTENTS continued ...
Страница 40: ......
Страница 87: ...4 CONTROL AND FUNCTIONS 2020 11 11 SR_CH04_AG002EF_01 ...
Страница 121: ...5 FILED WORKING 2020 11 11 SR_CH05_AG002EF_01 ...