Trouble shooting 30
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Indicate or Display:
Compressor Start-up error
(Permanent Stop)
On start-up the compressor, when detected rotor position is out of phase
with actual rotor position more than 90 degrees,the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
Outdoor Unit Main PCB Circuit
Compressor
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
Check Point 2 : Check connection of around the Compressor components
OK
OK
OK
OK
Check Point 3 : Replace Main PCB
If Check Point 1,2 do not improve the symptom, replace Main PCB.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
07-31
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
ERROR CODE : E : 1A
Outdoor Unit (AB*A18L/ 24L) : LED 0.1sec ON/ 2sec OFF
(AB*A36L/ 45L) : LED 14 times blink
Содержание AB Series A18LATN
Страница 2: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Страница 11: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Страница 16: ...02 05 MODELS AO A18 24LACL Unit mm Air flow Top view Front view AO A18L AO A24L Side view Bottom view ...
Страница 18: ...AOTA24L AOTA18L 02 07 MODELS AOTA18 24LACL Unit mm Air flow Top view Front view Side view Bottom view ...
Страница 20: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 21: ...03 01 MODEL AB A18 24LATN AO A18 24LACL 3 REFRIGERANT CIRCUIT ...
Страница 22: ...03 02 MODEL AB A36 45LATN AO A36 45LATL ...
Страница 23: ...03 03 MODEL ABTA18 24LATN AOTA18 24LACL ...
Страница 24: ...03 04 MODEL ABTA36 45LATN AOTA36 45LATL ...
Страница 25: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 26: ...04 01 MODEL AB A18 24LATN 4 CIRCUIT DIAGRAM ...
Страница 27: ...04 02 MODEL AB A36 45LATN ...
Страница 28: ...04 03 MODEL ABTA18 24LATN ...
Страница 29: ...04 04 MODEL ABTA36 45LATN ...
Страница 30: ...04 05 MODEL AO A18 24LACL ...
Страница 31: ...04 06 MODEL AO A36 45LATL ...
Страница 32: ...04 07 MODEL AOTA18 24LACL ...
Страница 33: ...04 08 MODEL AOTA36 45LATL ...
Страница 34: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Страница 59: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Страница 68: ...7 TROUBLE SHOOTING R410A Large Ceiling type INVERTER ...
Страница 109: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Страница 126: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Страница 131: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan June 2007 Printed in Japan ...