Trouble shooting 16
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Filter PCB and Main PCB
Check Point 4 : Replace Main PCB
YES
NO
OK
Indicate or Display:
ERROR CODE : E : 18
CT error
Outdoor Unit Main PCB Circuit
Outdoor Unit Filter PCB Circuit
(Input current sensor unit)
Check Point 2 :
Check connections of Outdoor Unit Electrical Components
Check if connector is removed.
Check if
the terminal connection
is loose.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring,
reset the power.
Check Point 1-2 :
Check external cause at Indoor and Outdoor
(Voltage drop or Noise)
1. Defective connection of electric components 2. External cause 3. Filter PCB failure 4. Main PCB failure
Instant drop : Check if there is a large load electric
apparatus in the same circuit.
Momentary power failure : Check if there is a defective
contact or leak current in the
power supply circuit.
Noise : Check if there is any equipment causing harmonic
wave near electric line.(Neon bulb or electric
equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
When Input Current Sensor has detected 0A, while Inverter Compressor is
operating at higher than 56Hz(for AB*A18L/ 24L) or 50Hz(for AB*A36L/ 45L),
after 1minute upon starting the Compressor.
(Except during the defrost operation)
07-18
Check DC voltage of CN1 (between 2 (Brown) and 3 (Red)) on Filter PCB.
>> After 40seconds upon starting the Compressor,
If it is higher than 0.2V, Main PCB is failure. (Filter PCB is normal) >> Replace Main PCB
>> If it is lower than 0.2V, Filter PCB is failure. >> Replace Filter PCB
If it does not improve the symptom, change Main PCB.
AB*A18L/ 24L
If Check Point 1, 2 do not improve the symptom, change Main PCB.
Outdoor Unit (AB*A18L/ 24L) : LED 2sec ON/ 2sec OFF
(AB*A36L/ 45L) : No indication
Содержание AB Series A18LATN
Страница 2: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Страница 11: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Страница 16: ...02 05 MODELS AO A18 24LACL Unit mm Air flow Top view Front view AO A18L AO A24L Side view Bottom view ...
Страница 18: ...AOTA24L AOTA18L 02 07 MODELS AOTA18 24LACL Unit mm Air flow Top view Front view Side view Bottom view ...
Страница 20: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 21: ...03 01 MODEL AB A18 24LATN AO A18 24LACL 3 REFRIGERANT CIRCUIT ...
Страница 22: ...03 02 MODEL AB A36 45LATN AO A36 45LATL ...
Страница 23: ...03 03 MODEL ABTA18 24LATN AOTA18 24LACL ...
Страница 24: ...03 04 MODEL ABTA36 45LATN AOTA36 45LATL ...
Страница 25: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 26: ...04 01 MODEL AB A18 24LATN 4 CIRCUIT DIAGRAM ...
Страница 27: ...04 02 MODEL AB A36 45LATN ...
Страница 28: ...04 03 MODEL ABTA18 24LATN ...
Страница 29: ...04 04 MODEL ABTA36 45LATN ...
Страница 30: ...04 05 MODEL AO A18 24LACL ...
Страница 31: ...04 06 MODEL AO A36 45LATL ...
Страница 32: ...04 07 MODEL AOTA18 24LACL ...
Страница 33: ...04 08 MODEL AOTA36 45LATL ...
Страница 34: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Страница 59: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Страница 68: ...7 TROUBLE SHOOTING R410A Large Ceiling type INVERTER ...
Страница 109: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Страница 126: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Страница 131: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan June 2007 Printed in Japan ...