Trouble shooting 28
INDOOR UNIT Error Method:
Indicate or Display:
ERROR CODE : E : 2c
Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
OK
OK
4-way valve error
Indoor Unit Controller PCB Circuit
Heat Exchanger Temperature Thermistor
Room Temperature Thermistor
4-way valve
When the indoor heat exchanger temperature is compared with
the room temperature, and either following condition is detected
continuously two times, the compressor stops.
1. Connector connection failure 2. Thermistor failure 3. Coil failure 4. 4-way valve failure
5. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 3 : Check the solenoid coil and 4-way valve
Remove CN30 from PCB and check the resistance value of coil.
Resistance value is about 1.4k
>>If it is Open or abnormal resistance value, replace Solenoid Coil.
07-29
Outdoor Unit : No indication
Cooling or Dry operation
[Indoor heat exchanger temp.] - [Room temp.] > 10degC
Heating operation
[indoor heat exchanger temp.] - [room temp.] < -10degC
If the same operation is repeated 5 times,
the compressor stops permanently.
[ Solenoid coil ]
Check each piping temperature,
and the location of the valve by the temperature difference.
>>If the value location is not proper, replace 4-way valve.
[ 4-way valve ]
OK
OK
Check Point 4 : Replace Controller PCB
If Check Point 1- 3 do not improve the symptom, replace Controller PCB.
Check Point 2 : Check Heat exchanger temp. thermistor and Room temp. thermistor
Isn’t it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor (Refer to Trouble shooting 3, 4),
If defective, replace the thermistor
Содержание AB Series A18LATN
Страница 2: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Страница 11: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Страница 16: ...02 05 MODELS AO A18 24LACL Unit mm Air flow Top view Front view AO A18L AO A24L Side view Bottom view ...
Страница 18: ...AOTA24L AOTA18L 02 07 MODELS AOTA18 24LACL Unit mm Air flow Top view Front view Side view Bottom view ...
Страница 20: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 21: ...03 01 MODEL AB A18 24LATN AO A18 24LACL 3 REFRIGERANT CIRCUIT ...
Страница 22: ...03 02 MODEL AB A36 45LATN AO A36 45LATL ...
Страница 23: ...03 03 MODEL ABTA18 24LATN AOTA18 24LACL ...
Страница 24: ...03 04 MODEL ABTA36 45LATN AOTA36 45LATL ...
Страница 25: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 26: ...04 01 MODEL AB A18 24LATN 4 CIRCUIT DIAGRAM ...
Страница 27: ...04 02 MODEL AB A36 45LATN ...
Страница 28: ...04 03 MODEL ABTA18 24LATN ...
Страница 29: ...04 04 MODEL ABTA36 45LATN ...
Страница 30: ...04 05 MODEL AO A18 24LACL ...
Страница 31: ...04 06 MODEL AO A36 45LATL ...
Страница 32: ...04 07 MODEL AOTA18 24LACL ...
Страница 33: ...04 08 MODEL AOTA36 45LATL ...
Страница 34: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Страница 59: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Страница 68: ...7 TROUBLE SHOOTING R410A Large Ceiling type INVERTER ...
Страница 109: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Страница 126: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Страница 131: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan June 2007 Printed in Japan ...