Trouble shooting 31
Forecast of Cause:
YES
YES
NO
OK
OK
OK
OK
OK
OK
Indoor Unit - No Power
1. Power Supply failure 2. External cause
3. Electrical Components defective
Check Point 1 : Check Installation Condition
Isn’t the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring
to Installation Manual or Data & Technical Manual.
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in
the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
Check Point 3 : Check Electrical Components
Check Voltage of power supply.
>> Check AC198 - 264V appears at Indoor Unit Terminal 1 - 2 (Power Supply).
Check Fuse in Filter PCB.
>> If Fuse is open, check if the wiring between Terminal and Filter PCB
is loose, and replace Fuse.
Check Varistor in Filter PCB.
>> If Varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace Varistor.
If the symptom does not change by above Check3, replace Filter PCB.
07-32
7-3 TROUBLE SHOOTING WITH NO ERROR CODE
Содержание AB Series A18LATN
Страница 2: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Страница 11: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Страница 16: ...02 05 MODELS AO A18 24LACL Unit mm Air flow Top view Front view AO A18L AO A24L Side view Bottom view ...
Страница 18: ...AOTA24L AOTA18L 02 07 MODELS AOTA18 24LACL Unit mm Air flow Top view Front view Side view Bottom view ...
Страница 20: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 21: ...03 01 MODEL AB A18 24LATN AO A18 24LACL 3 REFRIGERANT CIRCUIT ...
Страница 22: ...03 02 MODEL AB A36 45LATN AO A36 45LATL ...
Страница 23: ...03 03 MODEL ABTA18 24LATN AOTA18 24LACL ...
Страница 24: ...03 04 MODEL ABTA36 45LATN AOTA36 45LATL ...
Страница 25: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 26: ...04 01 MODEL AB A18 24LATN 4 CIRCUIT DIAGRAM ...
Страница 27: ...04 02 MODEL AB A36 45LATN ...
Страница 28: ...04 03 MODEL ABTA18 24LATN ...
Страница 29: ...04 04 MODEL ABTA36 45LATN ...
Страница 30: ...04 05 MODEL AO A18 24LACL ...
Страница 31: ...04 06 MODEL AO A36 45LATL ...
Страница 32: ...04 07 MODEL AOTA18 24LACL ...
Страница 33: ...04 08 MODEL AOTA36 45LATL ...
Страница 34: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Страница 59: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Страница 68: ...7 TROUBLE SHOOTING R410A Large Ceiling type INVERTER ...
Страница 109: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Страница 126: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Страница 131: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan June 2007 Printed in Japan ...