4. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure 7.
On the other hand, if switched in [HIGH] [QU], the indoor motor will run at a constant airflow
of [HEAT] operation modes QU, LOW, MED, HIGH, as shown in Table 5.
5. COOL AIR PREVENTION CONTROL (Heating mode)
6. DRY OPERATION
Refer to the Figure 4.
During the dry mode operation, the fan speed setting can not be changed.
05-06
42°C
30°C
34°C
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
When the compressor operates, the maximum value of the indoor fan speed is set as shown in Figure 8,
based on the detected temperature by the indoor heat exchanger sensor on heating mode.
When the compressor does not operate, the indoor fan motor operates [S-Lo] mode.
( Fig.7 : Airflow change - over ( Heating : AUTO ) )
( Fig.8 : Cool Air Prevention Control )
< [Hi] setting >
Hi
Me+
Lo
Cool air
prevention
39°C
37°C
37°C
32°C
24°C
39°C
32°C
Indoor heat exchanger
temperature
Indoor heat exchanger
temperature
< The other of [Hi] setting >
S-Lo
Lo (Qu)
Cool air
prevention
37°C
30°C
34°C
24°C
Setting
FAN mode
S-Lo
[ AB*A18/24LATN : Cool air prevention 500rpm, S-Lo 300rpm ]
[ AB*A36/45LATN : Cool air prevention 500rpm, S-Lo 250rpm ]
TR-Ts > - 1.5 degC
=
- 2.5 degC > TR-Ts
- 1.5 degC > TR-Ts > - 2.5 degC
=
TR-Ts > - 1 degC
=
- 2 degC > TR-Ts
- 1 degC > TR-Ts > - 2 degC
=
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
LOW mode
MED mode
HIGH mode
Содержание AB Series A18LATN
Страница 2: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Страница 11: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Страница 16: ...02 05 MODELS AO A18 24LACL Unit mm Air flow Top view Front view AO A18L AO A24L Side view Bottom view ...
Страница 18: ...AOTA24L AOTA18L 02 07 MODELS AOTA18 24LACL Unit mm Air flow Top view Front view Side view Bottom view ...
Страница 20: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 21: ...03 01 MODEL AB A18 24LATN AO A18 24LACL 3 REFRIGERANT CIRCUIT ...
Страница 22: ...03 02 MODEL AB A36 45LATN AO A36 45LATL ...
Страница 23: ...03 03 MODEL ABTA18 24LATN AOTA18 24LACL ...
Страница 24: ...03 04 MODEL ABTA36 45LATN AOTA36 45LATL ...
Страница 25: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 26: ...04 01 MODEL AB A18 24LATN 4 CIRCUIT DIAGRAM ...
Страница 27: ...04 02 MODEL AB A36 45LATN ...
Страница 28: ...04 03 MODEL ABTA18 24LATN ...
Страница 29: ...04 04 MODEL ABTA36 45LATN ...
Страница 30: ...04 05 MODEL AO A18 24LACL ...
Страница 31: ...04 06 MODEL AO A36 45LATL ...
Страница 32: ...04 07 MODEL AOTA18 24LACL ...
Страница 33: ...04 08 MODEL AOTA36 45LATL ...
Страница 34: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Страница 59: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Страница 68: ...7 TROUBLE SHOOTING R410A Large Ceiling type INVERTER ...
Страница 109: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Страница 126: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Страница 131: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan June 2007 Printed in Japan ...