Check Point 2 :
Check Point 2 : Check Connector (CN9) / Wire
Check Point 1 : Check Float Switch
Check Point 3 : Replace Controller PCB
ON
ON
OFF
OFF
OK
OK
OK
OK
Trouble shooting 6
INDOOR UNIT Error Method:
Indicate or Display:
Indoor Unit : No LED
Outdoor Unit : No indication
ERROR CODE : E : 09
Detective Actuators:
Detective details:
Forecast of Cause :
Water Drain Abnormal
Indoor Unit Controller PCB Circuit
Float Switch
When Float Switch is ON for more than 3 minutes.
1. Float Switch failure 2. Shorted connector/ wire 3. Controller PCB failure
Check operation of float switch. (any blocking by dust, etc.)
Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is detective, replace it.
Check loose contact of CN9 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
02-09
( For AU Type )