1-3. DRY OPERATION
1-3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Fig 3.
Room
temperature
Room
temperature
Compressor ON
Ts+1.5 degC
Ts+0.5 degC
Compressor OFF
( Table 3 : Compressor frequency )
( Fig.3 : Compressor Control based on Room Temperature )
01-03
Operating frequency
Ts : Setting temperature
AB*F18, 24
AR*F18, 24
AU*F18, 24
34Hz
Compressor
ON
OFF
Indoor fan
Dry air flow
S
-
Lo
OFF
( Fig.4 : Indoor Fan Control )
10
30
60
180
60
180
60 10
30
(SEC)
AR*A24LATU
AU*A24LBL
34Hz