Indoor heat exchange
temperature
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the
detection value of the indoor heat exchanger temperature sensor.
(Fig.13 : Heating Overload Protection Control)
01-25
- 20
°C
67
°C
62
°C
59
°C
53
°C
50
°C
Refer to below
Compressor Operation
Over than 18Hz Frequency down every 60 seconds
Less than 18Hz OFF
4. COOLING PRESSURE OVER RISE PROTECTION
On cooling mode, the compressor frequency is controlled as following based on the
detection value of the outdoor heat exchanger temperature sensor.
Outdoor heat exchange
temperature
(Fig.12 : Cooling Pressure Over Rise Protection Control)
Compressor is OFF
Hold
The compressor frequency is
decreased 2Hz every 60seconds.
Release of protection
The forced cooling operation starts up when MANUAL / AUTO button is pressed more than 10 seconds.
During the forced cooling operation, it keeps operation regardless of detection value of room
temperature sensor.
Operation LED and Timer LED light up while the unit is on the forced cooling operation.
The forced cooling operation is released after 60 minutes from starting time.
Cooling
Heating
1-23. FORCED COOLING OPERATION
1-24. COMPRESSOR STOP CONTROL
When the detection value of outdoor temperature sensor is lower than temperature
in the table below, the compressor is stopped.
(Table 14 : Operation temperature of compressor stop control)
Operation
temperature
Temperature