Trouble shooting 13
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Compressor
OK
OK
(PARTS INFORMATION 2)
Indicate or Display:
Outdoor Unit : LED 12 times blink
Check Point 4 : Replace Main PCB
OK
OK
Check Point 1 :
Check connections of Outdoor Unit Electrical Components
IPM error (Permanent Stop)
Outdoor Unit Main PCB Circuit
Compressor
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged 4. Compressor failure 5. Main PCB failure
Check if connector is removed.
Check if
the terminal connection
is loose.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off ?
Check Outdoor Fan Motor. (Refer to Trouble shooting 17)
>> If the Fan Motor is locked, replace it.
>> If the Fan Motor is failure, replace it.
Check Compressor.
If Check Point 1, 2, 3 do not improve the symptom, change Main PCB.
When more than normal operating current to IPM in Main PCB flows,
the compressor stops.
After the compressor restarts, if the same operation is repeated within 40sec,
the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
07-14
Indoor Unit : Operation LED: Blink, Timer LED: 10 times blink,
Vertical swing LED: OFF
Содержание AB*30LBAG series
Страница 5: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Страница 8: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Страница 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 14: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 18: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Страница 37: ...6 REFRIGERANT CAUTION R410A R410A INVERTER Large Ceiling type ...
Страница 46: ...7 TROUBLE SHOOTING R410A INVERTER Large Ceiling type ...
Страница 77: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Страница 88: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Страница 93: ...10 REPLACEMENT PARTS R410A INVERTER Large Ceiling type ...
Страница 112: ...2 TOP PANEL removal Remove the 7 mounting screws Remove the TOP PANEL upward FRONT VIEW REAR VIEW 10 19 ...
Страница 123: ...10 30 2 INTAKE GRILLE removal Remove the 6 mounting screws Remove the 2 INTAKE GRILLES INTAKE GRILLE 2 places 1 2 ...
Страница 126: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2006 Printed in Japan ...