Trouble shooting 2
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause:
OK
Indicate or Display:
Indicate or Display:
Outdoor Unit : No indication
YES
YES
NO
N
L
3
2
1
WHITE
BLACK
RED
WHITE
BLACK
+
-
OK
Communication Error
(Serial Reverse Transfer Error)
Outdoor Unit Main PCB Circuit
1. Connection failure 2. External cause 3. Main PCB failure 4. Active Filter Module failure
Check Point 1-1 : Reset the power and operate
Does Error indication show again?
Check Point 1-2:
Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Check Point 2 : Check Connection
Check any loose or removed connection line of
Indoor unit and Outdoor unit.
>> If there is an abnormal condition, correct it by
referring to Installation Manual or Data &
Technical Manual.
Check connection between Outdoor Unit Main PCB
and Filter PCB.
(If there is loose connector or open cable)
Check Point 3 : Check the voltage of power supply
Check the voltage of power supply
>> Check if AC198 - 264V appears at Outdoor Unit Terminal L - N.
Check Point 4 : Check Serial Signal (Reverse Transfer Signal)
Check Serial Signal (Reverse Transfer Signal)
>> Check if Indicated value swings between AC70V and AC130V at Outdoor Unit Terminal 1 - 3.
>> If it is abnormal, Check Active Filter Module. (PARTS INFORMATION 3)
When the indoor unit cannot receive the serial signal from Outdoor unit
more than 10seconds.
>>If Active Filter Module is abnormal, replace it.
>>If Active Filter Module is normal, replace Main PCB.
07-03
Indoor Unit : Operation LED: 5 times blink, Timer LED: Blink,
Vertical swing LED: OFF
7-2 TROUBLE SHOOTING WITH ERROR CODE
Содержание AB*30LBAG series
Страница 5: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Страница 8: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Страница 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 14: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 18: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Страница 37: ...6 REFRIGERANT CAUTION R410A R410A INVERTER Large Ceiling type ...
Страница 46: ...7 TROUBLE SHOOTING R410A INVERTER Large Ceiling type ...
Страница 77: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Страница 88: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Страница 93: ...10 REPLACEMENT PARTS R410A INVERTER Large Ceiling type ...
Страница 112: ...2 TOP PANEL removal Remove the 7 mounting screws Remove the TOP PANEL upward FRONT VIEW REAR VIEW 10 19 ...
Страница 123: ...10 30 2 INTAKE GRILLE removal Remove the 6 mounting screws Remove the 2 INTAKE GRILLES INTAKE GRILLE 2 places 1 2 ...
Страница 126: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2006 Printed in Japan ...