5-10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the following values.
The compressor frequency, the temperatures detected by the discharge temperature sensor
and the outdoor temperature sensor.
The pulse range of the electronic expansion valve control is between 50 to 480 pulses.
At the time of supplying the power to the outdoor unit, the initialization of the electronic
expansion valve is operated (1000 pulses are input to the closing direction).
5-11. TEST OPERATION CONTROL
The compressor won't enter operation status for 3 minutes after the compressor is stopped,
even if any operation is given.
At the time when the air conditioner is switched from the cooling mode to heating mode,
the compressor is stopped, and the 4-way valve is switched in 3 minutes later
after the compressor stopped.
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically resumed with
the memorized operation contents.
When the power is interrupted and recovered during timer operation, timer operation is canceled,
but only setting time is memorized.
[Operation contents memorized when the power is interrupted]
Operation mode
Set temperature
Set air flow
Timer mode and timer time
Air flow Direction
Swing
Thermistor detected position
5-12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
5-13. 4-WAY VALVE EXTENSION SELECT
5-14. AUTO RESTART
05-13
Under the condition where the air conditioner runs, short two metal contacts under the battery
compartment lid, and the test operation control mode will appear.
During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously.
Set the test operation mode, and the compressor will continue to run regardless of whether the room
temperature sensor detects.
The test operation mode is released if 60 minutes have passed after setting up the test operation.
With Wireless Remote Controller
Содержание AB*30LBAG series
Страница 5: ...1 SPECIFICATIONS R410A INVERTER Large Ceiling type ...
Страница 8: ...2 DIMENSIONS R410A INVERTER Large Ceiling type ...
Страница 11: ...3 REFRIGERANT SYSTEM DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 14: ...4 CIRCUIT DIAGRAM R410A INVERTER Large Ceiling type ...
Страница 18: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A Large Ceiling type INVERTER ...
Страница 37: ...6 REFRIGERANT CAUTION R410A R410A INVERTER Large Ceiling type ...
Страница 46: ...7 TROUBLE SHOOTING R410A INVERTER Large Ceiling type ...
Страница 77: ...8 APPENDING DATA R410A INVERTER Large Ceiling type ...
Страница 88: ...9 INSTALLATION MANUAL R410A INVERTER Large Ceiling type ...
Страница 93: ...10 REPLACEMENT PARTS R410A INVERTER Large Ceiling type ...
Страница 112: ...2 TOP PANEL removal Remove the 7 mounting screws Remove the TOP PANEL upward FRONT VIEW REAR VIEW 10 19 ...
Страница 123: ...10 30 2 INTAKE GRILLE removal Remove the 6 mounting screws Remove the 2 INTAKE GRILLES INTAKE GRILLE 2 places 1 2 ...
Страница 126: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2006 Printed in Japan ...