background image

En-6

 

CAUTION

•  There should be no gaps between the insulation and the unit.

•  After checking for gas leaks (refer to the Installation Manual of the outdoor unit), 

perform this section.

•  Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to 

do so may cause water leaks.

5.  INSTALLING DRAIN PIPES

5.1. Installing drain pipes (Ceiling concealed type)

 

CAUTION

• Install the drain pipe in accordance with the instructions in this Installation Manual 

and keep the area warm enough to prevent condensation. Problems with the piping 
may lead to water leaks.

Install the drain pipes according to the measurements given in the following 

fi

 gure.

Flange positions for connecting the drain pipes.

139

123 

108 

41

208

356

371

Main drain pipe
ø25.4 (O.D.)

Safety drain pipe 
ø25.4 (O.D.)

Unit : mm

 

CAUTION

•  This UNIT has drain ports in two locations. Follow the procedure in the figure to 

connect drain pipes to each of them.

•  Be sure to properly insulate the drain pipes.

Use general hard polyvinyl chloride pipe (VP25) and connect it with adhesive (polyvinyl 
chloride) so that there is no leakage.
Do not perform air bleeding.
(1)  Main drain pipe
Provide one trap on the main drain pipe near the indoor unit.

H

1

H

2

Trap

Unit

H

1

 = 100 mm (approx.)

H

2

 = 50-100 mm

Drain pipe (main)

(2) Safety drain
There is no need to provide a trap for the safety drain pipe. If the safety drain pipe is 
connected to the main drain pipe, make the connection below the trap on the main drain 
pipe.

Drain pipe (main)

Drain pipe (safety)

Unit

• 

Once installation is complete, check the 

fl

 ow of the drain water.

(1)  Detach the caps and plugs from the pipes.
(2)  Centering the pipe against port on the indoor unit, turn the 

fl

 are nut with your hand.

Flare nut

Connection pipe
(small)

Connection pipe
(large)

Flare nut

(3) When the 

fl

 are nut is tightened properly by your hand, hold the body side coupling 

with a separate spanner, then tighten with a torque wrench. (See the table below for 
the 

fl

 are nut tightening torques.)

 

CAUTION

•  Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to 

tighten the 

fl

 are nut correctly.

• Tighten the 

fl

 are nuts with a torque wrench using the speci

fi

 ed tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to 

leak and generate a hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

•  Connect the piping so that the control box cover can easily be removed for servicing 

when necessary.

•  In order to prevent water from leaking into the control box, make sure that the piping 

is well insulated.

Tighten with 2 wrenches.

Holding wrench

Flare nut 

Connection pipe

Torque wrench

Indoor unit pipe 
(Body side)

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

4.4. Installing heat insulation

After checking for gas leaks, insulate by wrapping insulation around the two parts (Gas 
and Liquid) of the indoor unit coupling, using the coupler heat insulation.
After installing the coupler heat insulation, wrap both ends with vinyl tape so that there is 
no gap.
Secure both ends of the heat insulation material using nylon fasteners.

Coupler heat insulation (Small)

Coupler heat insulation (Large)

Indoor unit side

9379123037-02.indb   6

9379123037-02.indb   6

7/4/12   3:47 PM

7/4/12   3:47 PM

Содержание 9379123037-02

Страница 1: ... autorizzato ǼīȋǼǿȇǿǻǿȅ ǼīȀǹȉǹȈȉǹȈǾȈ īȚĮ İȟȠȣıȚȠįȠIJȘȝȑȞȠ ʌȡȠıȦʌȚțȩ ıȑȡȕȚȢ MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados ɊɍɄɈȼɈȾɋɌȼɈ ɉɈ ɍɋɌȺɇɈȼɄȿ Ⱦɥɹ ɭɩɨɥɧɨɦɨɱɟɧɧɨɝɨ ɩɟɪɫɨɧɚɥɚ KURULUM KILAVUZU Yetkili servis personeli içindir h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I Ȑ k I v Ș Ȝ Ȝ E s ê u g u t r o P h s i l g n E e ç k r ü T ɣ ɢ ɤ ɫ ɫ ɭ Ɋ AIR CONDITIONER PART NO 937912303...

Страница 2: ...ol name Contents of change Gauge manifold Pressure is huge and cannot be measured with a conventional gauge To prevent erroneous mixing of other refrigerants the diameter of each port has been changed It is recommended to use a gauge manifold with a high pressure display range 0 1 to 5 3 MPa and a low pressure display range 0 1 to 3 8 MPa Charging hose To increase pressure resistance the hose mate...

Страница 3: ...can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals growin...

Страница 4: ...ng figure to adjust the levelness B A Level meter The side A of the unit with the drain port should be slightly lower than the opposite side B of the unit The height difference between sides A and B should be from 0 to 20mm 3 3 3 Mounting the duct Follow the procedure in the following figure to install the ducts 865 850 26 295 14 325 14 27 Intake port flange Outlet port flange Unit mm Spacing betw...

Страница 5: ... or less at 20 C 4 3 Flare connection Pipe connection WARNING Tighten the flare nuts with a torque wrench using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special pipe cutter and flare tool exclusive for R410A 1 Cut the con...

Страница 6: ... the pipes 2 Centering the pipe against port on the indoor unit turn the flare nut with your hand Flare nut Connection pipe small Connection pipe large Flare nut 3 When the flare nut is tightened properly by your hand hold the body side coupling with a separate spanner then tighten with a torque wrench See the table below for the flare nut tightening torques CAUTION Hold the torque wrench at its g...

Страница 7: ...the earth leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire could result Always connect the earth ground cable Improper earthing grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so that the air conditioner can...

Страница 8: ...lfunction of the unit Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth ground wire longer than the other wires Power supply cable or connection cable 30 mm 40 mm or more Earth Ground wire Use a 4 core wire cable 6 3 Connection of wiring CAUTION Use care not to mistake the power supply cable and connection wires whe...

Страница 9: ...connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote controller cable sheath with the cable tie as s...

Страница 10: ... few seconds until the setting value stops flashing If the setting value display changes or if is displayed when the flashing stops the setting value has not been set correctly An invalid setting value may have been selected for the indoor unit 6 Repeat steps 2 to 5 to perform additional settings Press the SET TEMP buttons and FAN button simultaneously again for more than 5 seconds to cancel the f...

Страница 11: ...ection location of the room temperature can be selected from the following 2 examples Choose the detection location that is best for the installation location A Indoor unit setting factory setting The room temperature is detected by the indoor unit temperature sensor 1 When the THERMO SENSOR button is pressed the lock display flashes because the function is locked at the factory A Indoor unit B In...

Страница 12: ...gain NOTE When different indoor unit models are connected using the group control system some functions may no longer be available If the group control system contains multiple units that are operated simultaneously con nect and set the units as shown below Auto changeover operates under the same mode with model unit number 00 It should not be connected to any other Gr that is not of the same seri...

Страница 13: ...s No cooling No heating Has heat insulation work been completed Water leakage Does water drain easily from the indoor units Water leakage Are the wires and pipes all connected completely No operation heat or burn damage Is the connection cable the specified thickness No operation heat or burn damage Are the inlets and outlets free of any obstacles No cooling No heating After installation is comple...

Страница 14: ...rror Indoor unit fan motor error Drain pump error Damper error Indoor unit error Outdoor unit main PCB model information error or communication error Inverter error Active filter error PFC circuit error Trip terminal L error Display PCB microcomputers communication error Discharge temp sensor error Compressor temp sensor error Outdoor unit Heat Ex liquid temp sensor error Outdoor temp sensor error...

Страница 15: ...9379123037 02 indb 15 9379123037 02 indb 15 7 4 12 3 47 PM 7 4 12 3 47 PM ...

Отзывы: