![Fuji Electric ZSS-7 Скачать руководство пользователя страница 78](http://html1.mh-extra.com/html/fuji-electric/zss-7/zss-7_instruction-manual_2341920078.webp)
INZ-TN7ZSS-E
- 71 -
6.5.2 Setting of moving average time
When the indication value and output value are set to the average value in the “6.6.1 Setting of instantane-
ous/average value”, set how many minutes the value should be held as a moving average value.
Setting range is from 1 to 60 minutes. When it is less than the moving average time, output the moving av-
erage value during that period.
Change the setting to reset the average value. (The value is reset when pressing the
key.)
Averaging operation
When the moving average time is set to 60 minutes
Sampling cycle is once every 1 second.
After reset, output the average value for 60 minutes. Therefore, it takes 60 minutes to obtain the average
value which has been set.
ENT
Reset
Average value
time
0
60min
Output