34
INZ-TN5A0506-E
Read-Only Word Data (Function Code: 04
H
)
Information of operation history
Relative
address
Register
number (H)
Data
type
Memory contents
Readout
data
Default
value
Stored number of operation history {Upper}
0 to 12
0
3000 33001
WORD
Next storage pointer {Lower}
0 to 11
0
Data storaged head pointer (Latest) {Upper}
0 to 11
0
3001 33002
WORD
Data storaged end pointer (Oldest) {Lower}
0 to 11
0
Error code of data storage position 0 {Upper}
0 to 255
0
3002 33003
WORD
Error code of data storage position 1 {Lower}
0 to 255
0
~ ~ ~
~
~
~
Error code of data storage position 10 {Upper}
0 to 255
0
3007 33008
WORD
Error code of data storage position 11 {Lower}
0 to 255
0
Year of data storage position 0 at operation
generation date {Upper}
00 to 99
0
3008 33009
WORD
Month of data storage position 0 at operation
generation date {Lower}
1 to 12
1
Day of data storage position 0 at operation
generation date {Upper}
1 to 31
1
3009 33010
WORD
Time of data storage position 0 at operation
generation date {Upper}
0 to 23
0
Minute of data storage position 0 at operation
generation date {Upper}
0 to 59
0
3010 33011
WORD
Second of data storage position 0 at operation
generation date {Lower}
0 to 99
0
~ ~ ~
~
~
~
Year of data storage position 11 at operation
generation date {Upper}
00 to 99
0
3041 33042
WORD
Month of data storage position 11 at operation
generation date {Lower}
1 to 12
1
Day of data storage position 11 at operation
generation date {Upper}
1 to 31
1
3042 33043
WORD
Time of data storage position 11 at operation
generation date {Lower}
0 to 23
0
Minute of data storage position 11 at operation
generation date {Upper}
0 to 59
0
3043 33044
WORD
Second of data storage position 11 at operation
generation date {Lower}
0 to 99
0
Содержание ZKM