33
INZ-TN5A0506-E
Read-Only Word Data (Function Code: 04
H
)
Information of alarm history
Relative
address
Register
number (H)
Data
type
Memory contents
Readout
data
Default
value
Stored number of alarm history {Upper}
0 to 12
0
2000 32001
WORD
Next storage pointer{Lower}
0 to 11
0
Data storaged of end pointer (Latest) {Upper}
0 to 11
0
2001 32002
WORD
Data storaged of head pointer (Oldest) {Lower}
0 to 11
0
Error code of data storage position 0 {Upper}
0 to 255
0
2002 32003
WORD
Error code of data storage position 1 {Lower}
0 to 255
0
~ ~ ~
~
~
~
Error code of data storage position 10 {Upper}
0 to 255
0
2007 32008
WORD
Error code of data storage position 11 {Lower}
0 to 255
0
Year of data storage position 0 at alarm
generation date {Upper}
00 to 99
0
2008 32009
WORD
Month of data storage position 0 at alarm
generation date {Lower}
1 to 12
1
Dayof data storage position 0 at alarm generation
date {Upper}
1 to 31
1
2009 32010
WORD
Time of data storage position 0 at alarm
generation date {Lower}
0 to 23
0
Minute of data storage position 0 at alarm
generation date {Upper}
0 to 59
0
2010 32011
WORD
Second of data storage position 0 at alarm
generation date {Lower}
0 to 99
0
~ ~ ~
~
~
~
Year of data storage position 11 at alarm
generation date{Upper}
00 to 99
0
2041 32042
WORD
Month of data storage position 11 at alarm
generation date {Lower}
1 to 12
1
Day of data storage position 11 at alarm
generation date {Upper}
1 to 31
1
2042 32043
WORD
Time of data storage position 11 at alarm
generation date {Lower}
0 to 23
0
Minute of data storage position 11 at alarm
generation date {Upper}
0 to 59
0
2043 32044
WORD
Second of data storage position 11 at alarm
generation date {Lower}
0 to 99
0
Содержание ZKM