5.4 Information on Each Parameter

5.4.1Method of Setting Condition Data

This  section  shows  a  typical  example  of  setting  the  peak  hold  parameter.
The  same  method  applies  to  other  parameters.

Indication

Name

Setup options

Default

value

PVH

Peak hold setup

PH (peak hold)/VH (valley hold)/PVH (peak-valley hold)

PH

RANG Measurement range setup

*1

*1

AVG

Number of averaging operations

setup

1/2/4/8/10/20/40/80

1

MAV

Number of moving average

operations setup

OFF/2/4/8/16/32

OFF

S.UD

Step width setup

1(1digit)/2(2digit)/5(5digit)/0(10digit)

1

BLNK

Indication blank setup

OFF/B-3/B-2/B-1/ON

OFF

UNIT

Unit setup

C/F

C

BAUD Baud rate setup

9600/4800/2400/384(38400)/192(19200)

9600

DATA Data length setup

7(7bit)/8(8bit)

7bit

P.BIT

Parity bit setup

E (even number), O (odd number), N (none)

E

S.BIT

Stop bit setup

2(2bit)/1(1bit)

2

T-

Delimiter setup

CR.LF(CR+LF)/CR

CRLF

ADR

Equipment ID setup

01 to 99

00

A.OUT Analog output setup

OFF/0-1(0 to 1V)/0-10(0 to 10V)/1-5(1 to 5V)/4-20(4 to 20mA)

OFF

B.UP

Digital zero backup setup

OFF/ON

OFF

LINE

Linearization setup

OFF/ON

CLR

I.SEL

Input selection

OC (open collector)/LGC (logic)/MAG (magnet)

O.C

TR T

Tracking zeroing time setup

00 to 99

00

TR V

Tracking zeroing width setup *2 00 to 99

01

SNSR Sensor power setup

10(10V)/05(5V)

10

P

ÇnÇm

Power on delay time setup

OFF/ON

OFF

PRO

Protect setup

OFF/1 to 30

OFF

U-NO. Unit number indication setup

OFF/ON

ON

S-HI

HI side judgment value setup

-9999 to 9999

1000

S-LO

LO side judgment value setup

-9999 to 9999

500

H-HI

HI side hysteresis setup

-9999 to 9999

0

H-LO

LO side hysteresis setup

-9999 to 9999

0

FSC

Full scale indication value setup -9999 to 9999

*1

FIN

Full scale input value setup

-9999 to 9999

*1

OFS

Offset indication value setup

-9999 to 9999

*1

OIN

Offset input value setup

-9999 to 9999

*1

PS

Pre-scaling value setup

0.001 to 5.000

1.000

PPR

Frequency division setup

1 to 100

1

DLHI

Digital limiter HI value setup

-9999 to 9999

9999

DLLO Digital limiter LO value setup

-9999 to 9999

-9999

AOHI

Analog output HI indication

setup

-9999 to 9999

9999

AOLO Analog output LO indication

setup

-9999 to 9999

0

DEP

Decimal point indication position

setup

None/place of 10

0

/place of 10

1

/place of 10

2

/place of 10

3

None

*2

*2

ZERO Zero input value

-0.300 to 2.000

0.000

SPIN

Span input value

1.000 to 3.000

2.000

SPAN Span indication

0 to 9999

9000

Condition data

Comparator data

Scaling data

Multi-display unit

Single display unit

or

(1) Press the Mode and Enter keys together

during measurement.

(2) Press the Mode key to change to the peak

hold setup mode.

(3) For a single display unit, press the Mode key

to change to the parameter information indication.

(The display automatically changes to this

indication in about 1 second, except right after

COND is indicated.)

(4) Press the Increment key a few times to set to

Valley Hold.

(5) Press the Enter key to return to measurement

mode. (Pressing the Mode key changes to the

next parameter).

5.4.2    Method  of  Setting  Comparator  Data

This section explains comparator data and shows a typical example of setting
the HI side judgment value. The same method applies to all other parameters.

Note: The setup conditions are HI side judgment value > LO side judgment

value, HI side judgment value 

%

 LO side judgment value + LO side

hysteresis, and LO side judgment value 

$

 HI side judgment value-HI

side hysteresis. If these conditions are not satisfied, an error indica-
tion appears and the display returns to the HI side judgment value
setup.

5.4.3

   

Method  of  Setting  Scaling  Data

This  section  explains  comparator  data  and  shows  a  typical  example  of
setting the full scale indication parameter. The same method applies to all
other  parameters.

Note: For  the  Digital  limiter,  values  larger  than  the  DLHI  setpoint  are

not indicated even if signals greater that the value set in the DLHI
parameter are input (for DLLO parameter, values smaller than the
DLLO  setpoint  are  not  indicated).

HI

GO

GO

LO

GO

HI side hysteresis

range

Indicated value

HI side judgment value

LO side judgment value

LO side hysteresis

range

Judgment

900

500

0

1000

300

150

200

HI side judgment value : 900

HI side hysteresis value

200

:

: 300

150

:

LO side hysteresis value

LO side judgment value

Multi-display unit

Single display unit

or

(1) Press the Mode and Enter keys together

during measurement.

(2) Press the Shift key a few times to display the

comparator data menu.

(6) Press the Enter key to return to the

measurement mode (Pressing the Mode key

changes to the next parameter).

(5) Press the Shift key (change digit) and press

the Increment key (change numeric value) to set

to 10.

&

Note:The decimal point in the selected digit

flashes.

(3) Press the Mode key a few times to display the

parameter to be set.

(4) For a single display unit, press the Mode key

to change to the parameter information indication.

(The display automatically changes to this

indication in about 1 second, except for parameter

S-HI right after COM is indicated.)

Note: For the process signal measuring unit, set the full scale input value

to 5.000 for the 1 V range and to 20.00 for the 2 A range, and set the
offset input value to 1.000 for the 1 V range and to 4.00 for the 2
A range.

The  following  explains  the  frequency  measuring  unit.  (The  same  method
applies to the full scale indication parameter.)

Note: For the frequency measuring unit, set the relationship between the

input and indication using the PS and PPR parameters (parameters
of FSC, FIN, OFS, and OIN are not indicated).

The  following  explains  the  scaling  of  analog  output  (The  same  method
applies to the full scale indication parameter.)

Note: For  analog  output  scaling,  set  the  indication  value  for  an  output

current  of  20  mA  in  the AOHI  parameter  and  set  the  indication
value for an output current 

o

f 4 mA in the AOLO parameter (for 4-

20  mA  output).

Indication

Input

5000

10V

Input voltage : 0 to 10V

0 to 5.000

:

Indication

FSC : 5000

FIN

: 9999

OFS : 0

OIN

: 0

DLHI : 3000

DLLO : -2000

DEP : The place of 10

3

 is lit.

0

DLLO

DLHI

3000

-2000

Multi-display unit

Single display unit

or

(1) Press the Mode and Enter keys together

during measurement.

(2) Press the Shift key a few times to change to

the scaling data  menu.

(6) Press the Enter key to return to the

measurement mode (Pressing the Mode key

changes to the next parameter).

(5) Press the Shift key (change digit) and press

the Increment key (change numeric value) to set

to 10.

&

Note:The decimal point in the selected digit

flashes.

(3) Press the Mode key a few times to display the

parameter to be set.

(4) For a single display unit, press the Mode key

to change to the parameter information indication.

(The display automatically changes to this

indication in about 1 second, except for parameter

FSC right after MET is indicated.)

Indication :

4 to 20mA

0.0 to 500.0

:

Output

AOHI : 5000

AOLO : 0

Output

Indication

20mA

5000

4mA

0

5.4.4Method  of  Setting  Calibration  Data
5.4.4.1 Actual  Load  Calibration

Actual load calibration means that calibration is carried out by applying actu-
ally measured pressure to a sensor such as a load cell connected to the meter.

5.4.4.2    Equivalent  Calibration

Equivalent calibration means that calibration is carried out according to the
ratings (specifications) of such a sensor as a load cell.  It is not necessary to
connect the sensor or to apply pressure to the sensor.

Multi-display unit

Single display unit

or

(1) Press the Shift, Increment, and Enter keys

together during measurement.

(2) Press the Mode key to change to the actual

load calibration mode.

(6) Press the Enter or Mode key to return to the

measurement mode.

(5) Press the Shift key (change digit) and

Increment key (change numeric value) to set

8000.

&

Note:The decimal point in the selected digit

flashes.

(3) Press the Mode key while applying pressure

that will cause the display to show zero.

(4) For a single display unit, press the Mode key

to change to the parameter information indication.

or

(1) Press the Shift, Increment, and Enter key together

during measurement.

(2) Press the Increment key to select the equivalent

calibration mode.

(12) Press the Enter or Mode key to return to the

measurement mode.

(11) Press the Shift key (change digit) and the

Increment key (change numeric value) to set 2000.

&

Note:The decimal point in the selected digit flashes.

(4) Press the Shift key to display the zero-input setup

mode.

(10) For a single display unit, press the Mode key to

display the parameter information indication.

(3) Press the Mode key to move to the equivalent

calibration mode.

&

(5) Press the Shift key (change digit) and the

Increment key (change numeric value) to set 0.004.

Note:The decimal point in the selected digit flashes.

Note:For a single display unit, the unit

automatically returns to ZERO indication if there is

no key operation for about 8 seconds.  In such a

case, press the Mode key to return to the numerical

value indication.

(6) Press the Mode key to change to the span input

value setup mode.

&

(7) For a single display unit, press the mode key to

display the parameter information indication.

(8) Press the Shift key (change digit) and the

Increment key (change numeric value) to set 1.002.

(9) Press the Mode key to change to the span

indicating value setup mode.

Multi-display unit

Single display unit

Instruction Manual for FD5000 Series

6/12

Instruction Manual for FD5000 Series

7/12

Determining the revolution speed (rpm) using the rotary encoder set to 30 pulses per minut

(1)Determine the measurement range by calculating the maximum frequency.

The figure below shows an example where the revolution rises to a maximum speed o

about 100 rpm.

30

100

60

Revolution speed per second
Number of pulses per revolution at the

rotary encoder

=

50

Number of pulses per second

(3)The display unit shows 500 if 50 Hz pulse input is measured under range 11 (when

PS=1 and PPR=1 by default). Therefore, the parameters should be set as PS=2 and

PPR=1 so that the decimal point is positioned in the 10

1

 digit(100.0 is is indicated 50 Hz

input).

(2)Since the number of pulses determined in (1) is 50 per second (50 Hz), set the range 

range 11(for how to set the range, see the section on setting condition data).

Содержание FD5000 series

Страница 1: ... V range 11 99 99 mV range 12 999 9 mV 05 AC voltage measuring unit average rms range 14 99 99 V range 15 600 V 06 AC voltage measuring unit true rms range 11 99 99 mV range 12 999 9 mV 07 AC voltage measuring unit true rms range 14 99 99 V range 15 600 V 08 AC current measuring unit average rms range 23 9 999 mA range 24 99 99 mA 09 AC current measuring unit average rms range 23 9 999 mA range 24...

Страница 2: ...inal 1 2 3 4 5 Name Description 1 23 Positive input terminal for range 23 9 999 mA 2 24 3 25 No 4 LO 5 Negative input terminal Positive input terminal for range 24 99 99 mA Positive input terminal for range 25 999 9 mA 5 8 mm min 5 8mm min Applicable solderless terminals 1 2 Name Description No 1 HI Input terminal 2 LO Input terminal 1 2 3 4 5 Name Description 1 HI Input terminal for all ranges 2 ...

Страница 3: ...wire for the power input except for range 26 external control and comparison output connectors 2 Tighten the screws for the power input except for range 26 external control and comparison output connectors to a torque of 0 5 to 0 6 Nm 3 Use 16 to 28 AWG wire for the analog output connector Tighten the screws of analog output connector to a torque of 0 22 to 0 25 Nm 4 Caution Instruction Manual for...

Страница 4: ...ment indicators HI 2 GO LO Indicates the result of judgment and turns on if the measured value HI judgment value Indicates the result of judgment and turns on if LO judgment value the measured value HI judgment value Indicates the result of judgment and turns on if the measured value LO judgment value 3 Function indicators ME Turns on if digital zero backup is on PH Turns on if peak hold valley ho...

Страница 5: ...side judgment value setup 500 X X X X H HI HI side hysteresis setup 0 X X X X H LO LO side hysteresis setup 0 X X X X FSC Full scale Indication value setup 1 X X X X X 9999 9999 9999 9999 9999 9999 9999 9999 9999 9999 9999 9999 9999 FIN Full scale input value setup 1 X X X X X 9999 9999 9999 9999 9999 9999 9999 9999 5000 9999 5000 9999 3 OFS Offset indication value setup 1 X X X X X 0 0 0 0 0 0 0 ...

Страница 6: ...g measurement 2 Press the Mode key to change to the peak hold setup mode 3 For a single display unit press the Mode key to change to the parameter information indication The display automatically changes to this indication in about 1 second except right after COND is indicated 4 Press the Increment key a few times to set to Valley Hold 5 Press the Enter key to return to measurement mode Pressing t...

Страница 7: ...ress the Enter or Mode key to return to the measurement mode 5 Press the Shift key change digit and Increment key change numeric value to set 8000 Note The decimal point in the selected digit flashes 3 Press the Mode key while applying pressure that will cause the display to show zero 4 For a single display unit press the Mode key to change to the parameter information indication or 1 Press the Sh...

Страница 8: ...For details on the RS 485 function see the separate manual on communication functions 7 4 RS 232C Interface Function The FD5000 series can be equipped with an RS 232C interface when the meter is provided with an RS 232C unit For details on the RS 232C function see the separate manual on communication functions 8 Specifications and External Dimensions 8 1 Input Specifications 8 1 1DC Voltage Measur...

Страница 9: ...e speed About 1 second Dead zone 0 to 99 digits Crest factor 4 1 at full scale Range Measurement range Indication Highest resolution Input impedance Maximum permissible input Accuracy 23 9 999mA 1µA About 10 100mA Offset 9999 Full scale 0 to 9999 0 5 of FS 20digit 500mA 3A About 1 About 0 1 10µA 99 99mA 999 9mA 100µA 24 25 Input circuit Single ended type Operating system conversion Maximum samplin...

Страница 10: ...o 10s 1s 100ms Renewal time of a display Input type Input voltage lebel Maximum permissible input Open collector Logic Magnet LO 1V or less 5V 2 2 k pull up LO 1V or less HI 2 5 to 15V 0 3 to 30Vp p 30V 15V Duty ratio 50 7 segment LED display character height 14 2 mm on main display and 8 mm on sub display Automatically indicated when the calculated result is negative OL or OL for input signals ou...

Страница 11: ...its ASCII code No procedure Error detection RS 232C RS 485 Start and stop synchronization Full duplex Communication system Communication rate 38400bps 19200bps 9600bps 4800bps 2400bps Start bit 1bit Data length Two wire half duplex Polling selecting system 1 Up to 31 meters log Output 8 3 3 Communicating Function 8 4 External Dimensions 9 Warranty and After service 9 1 Warranty The warranty period...

Страница 12: ... 2002 09 Fuji Electric Instruments Co Ltd International Sales Dept No 1 Fuji machi Hino city Tokyo 191 8502 Japan Phone 81 42 585 6201 6202 Fax 81 42 585 6187 Instruction Manual for FD5000 Series UU 33555a 12 12 ...

Отзывы: