FSP EssenSolar CFS model User Manual
www.fsp-group.com.tw
19
35
Equalization interval
30days (default)
Setting range is from 0 to 90 days.
Increment of each click is 1 day
36
Equalization activated
immediately
Enable
Disable (default)
If equalization function is enabled in program 30, this program can be
set up. If “Enable” is selected in this program, it’s to activate battery
equalization immediately and LCD main page will shows “
”. If
“Disable” is selected, it will cancel equalization function until next
activated equalization time arrives based on program 35 setting. At
this time, “
” will not be shown in LCD main page.
Display Setting
The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable
information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging
power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in
Watt, DC discharging current, main CPU Version.
Selectable information
LCD display
Input voltage/Output voltage
(Default Display Screen)
Input Voltage=230V, output voltage=230V
Input frequency
Input frequency=50Hz
PV voltage
PV voltage=260V
PV current
PV current = 2.5A