FSP EssenSolar CFS model User Manual
www.fsp-group.com.tw
6
4.
Connect all battery packs as below chart.
5.
Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with
torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is
correctly connected and conductors are tightly screwed into the battery terminals.
Recommended tool: #2 Pozi Screwdriver
6.
To firmly secure wire connection, you may fix the wires to strain relief with cable tie.
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!!
Before making the final DC connection or closing DC breaker/disconnector, be sure
positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).