FSP EssenSolar CFS model User Manual
www.fsp-group.com.tw
18
27
Floating charging
voltage
3kVA default setting: 27.0V
5kVA default setting: 54.0V
If self-defined is selected in program 5, this program can be set up.
Setting range is from 25.0V to 31.5V for 3kVA model and 48.0V to
61.0V for 5kVA model. Increment of each click is 0.1V.
29
Low DC cut-off voltage
3kVA default setting: 21.0V
5kVA default setting: 42.0V
If self-defined is selected in program 5, this program can be set up.
Setting range is from 21.0V to 24.0V for 3kVA model and 42.0V to
48.0V for 5kVA model. Increment of each click is 0.1V. Low DC cut-off
voltage will be fixed to setting value no matter what percentage of
load is connected.
30
Battery equalization
Battery equalization
Battery equalization disable (default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
31
Battery equalization
voltage
3kVA default setting: 29.2V
5kVA default setting: 58.4V
Setting range is from 25.0V to 31.5V for 3kVA model and 48.0V to
61.0V for 5kVA model. Increment of each click is 0.1V.
33
Battery equalized time
60min (default)
Setting range is from 5min to 900min.
Increment of each click is 5min.
34
Battery equalized
timeout
120min (default)
Setting range is from 5min to 900 min.
Increment of each click is 5 min.